A19ZBA Technical Bulletin 

 

Adjustments (See Fig. 4) 

The A19ZBA control has a 
locked low cutout stop.  Pointer 
"B" is locked in place with a 
screw that requires a special 
spanner wrench, Part No.  
836-61, to change the setting.  
The special wrench is supplied 
with each control.  To change 
the low cutout stop setting, 
proceed as follows: 

1.  Loosen screw "C" with the 

special wrench. 

2.  Slide pointer arm "B" to the 

desired cutout setting 
(adjustable from 
approximately 38 to 48

°

[3 to 9

°

C]).  The cutout 

setting is indicated by the 
flat of arm "B." 

3.  Tighten screw "C." 

The cut-in temperature is set by 
moving knob "A" to the desired 
cut-in setting.  This knob 
adjustment does not change the 
cutout setting, but provides for a 
short or long recycle time as 
required by the application. 

Checkout Procedure 

Before leaving the installation, 
observe at least three complete 
operating cycles to be sure that 
all components are functioning 
correctly. 

Repairs and Replacement 

Field repairs must not be made.  
For a replacement control, 
contact the nearest Johnson 
Controls distributor. 

 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls Group 

 

507 E. Michigan Street 

 

P.O. Box 423 

Printed in U.S.A. 

Milwaukee, WI   53202 

 