background image

 

FANs 121, 125 

 

Temperature Controls Section  A

 

Technical Bulletin  A19ZBA 

  

Issue 

Date 

1291 

©  1991 Johnson Controls, Inc. 

1

 

  Code No. LIT-121065 
  Part No. 997-778 

 

A19ZBA Type Temperature Control 

 

Application 

The A19ZBA temperature control 
is designed for water chiller 
applications.  The control has a 
range of 38 to 80

°

F (3 to 27

°

C) 

with contacts that open on a 
temperature drop. 

A packing nut assembly, Part 
No. FTG13A-600R, (Fig. 2) is 
supplied with the control for 
immersion applications where a 
bulb well is not required.  Bulb 
well No. WEL14A-600R (Fig. 3) 
for immersion applications is 
available, if required. 

All Series A19 controls are 
designed for use

 only

 as 

operating controls.  Where an 
operating control failure 
would result in personal injury 
and/or loss of property, it is 
the responsibility of the 
installer to add devices 
(safety, limit controls) or 
systems (alarm, supervisory 
systems) that protect against, 
or warn of, control failure. 

Installation 

When provided, follow the 
equipment manufacturer’s 
instructions.  If instructions are 
not supplied, follow the 
instructions in this sheet. 

!

 CAUTION:  Do not dent or 

deform the sensitive bulb of 
this control.  A dent or 
deformation will change the 
calibration and cause the 
control to cycle at a 
temperature lower than the 
dial setting. 

Mounting 

When installing the control, use 
the mounting bracket as a 
template and mark the location 
for the two mounting screws. 

Drill or punch two holes and start 
the mounting screws.  Place the 
slot in the bottom of the bracket 
under the head of the lower 
mounting screw.  Position the 
control so the top screw is in the 
top slot.  Tighten both screws.  It 
is not necessary to level the 
control except for appearance. 

For closed tank applications 
without a bulb well, use the 
FTG13A-600R packing nut.  (See 
Fig. 2.)  Put parts over the support 
tube section of the element and 
place bulb in the tank.  Install the 
1/2 in. NPT adapter in the tank 
opening and tighten.  Screw the 
packing nut with the retaining 
washers and packing into the 
adapter as shown in Fig. 2. 

!

 CAUTION:  Turn off the 

liquid supply and relieve the 
pressure before installing or 
removing the bulb or bulb 
well. 

For applications requiring a bulb 
well, install the bulb well in the tank 
opening.  Remove the bushing 
from the bulb well and slide the 
bushing over the capillary.  Insert 
the bulb into the bulb well and 
replace the bushing.  Push the 
bulb into position in the bottom of 
the well.  Tighten the set screw in 
the adapter end to hold the bulb in 
position. 

Wiring 

!

 WARNING:  Disconnect the 

power supply before wiring 
connections are made to 
avoid possible electrical 
shock or damage to the 
equipment. 

Make all wiring connections 
using copper conductors only, 
and in accordance with the 
National Electrical Code and 
local regulations. 

 

Fig. 1 -- A19ZBA-1 Temperature 

Control.  Note the mounting 

bracket on the back of the case. 

Note

:  Use the terminal screws 

furnished (8-32 

×

 1/4 in. binder 

head).  Substitution of other 
screws may cause problems in 
making proper connections. 

 