A19A

Issue 03/03/2003

Catalogue Section 1

© 2003 Johnson Controls Inc.

Order No.

 

PD-A19A-E

2

N

ote

These controls are designed for use only

as operating controls. Where an operating

control failure would result in personal injury

or loss of property it is the responsibility of

the installer to add devices or systems that

protect against, or warn of, control failure.

SPDT contacts are standard on all models.

Instruments have compact sizes. Types

A19ACC and A19ADC have a trip-free manual

reset . Reset button must be pressed and

released. Contact cannot be blocked in closed

position. All types have VDE and SEV approval.

To facilitate ordering, wholesaler codes have

been added on some universal models.

All models are provided with a separate knob

and sealing cap.

T

ype number matrix

A19AAC

  capillary thermostat, fixed differential.

A19AAF

  capillary thermostat, special close 

fixed differential.

A19ABC

  capillary or immersion thermostat,   

adjustable  differential.

A19ACC

   capillary  thermostat,  lock-out low

with manual reset.

A19ADC

    immersion thermostat, lock-out high 

with manual reset.

A19BAC

   space thermostat, fixed differential.

A19BBC

   space  thermostat, adjustable 

differential.

A19DAC

   strap-on thermostat.

A19DAF

strap-on thermostat

A

djustment

1.  Models “set low” (refer to cover label)

    The dial indicates the low switch point

(1 - 2 open, 1 - 3 closed).

     The high switch point (1 - 2 closed,

1 - 3 open) is obtained by adding the

differential to the low switch point.

2.  Models “set high” (refer to cover label)

    The dial indicates the high switch point

(1 - 2 closed, 1 - 3 open). The low switch

point (1 - 2 open, 1 - 3 closed) is obtained by

deducting the differential from the high switch

point.

Exception: Type A19ADC, dial indicates high

switch point ( 1 - 3 closed, 1 - 2 open).

N

ote

The standard screwdriver adjustment can

be converted easily in the field to knob

adjustment. Also concealing of adjustment

and scale is possible after installation.

C

ontact functions

Types A19AAC,

A19AAF, A19ABC,

A19BAC, A19BBC,

A19DAC

Fig. 1

1-2 closes on temperature increase

Type A19ACC

Fig. 2

1-2 opens on temperature decrease

Type A19ADC

Fig.3

1-2 opens on temperature increase

R

epair and replacement

Repair is not possible. In case of an improperly

functioning control, please check with your

nearest supplier. When contacting the supplier

for a replacement you should state the

type/model number of the control. This number

can be found on the data plate or cover label.

1

2

3

θ

 >

1

2

3

θ

 <

1

2

3

θ

 >

Summary of Contents for A19D

Page 1: ...inimum number of models On request a built in high or low limit stop is possible and can be adjusted quickly and easily in the field All models have a universal way of adjustment For this purpose a knob and sealing cap are enclosed All A19 style 1 wholesaler code models have a bulb clamp plus screw also enclosed A19A capillary thermostat A19B space thermostat Feature and Benefits Liquid filled sen...

Page 2: ...ential A19BBC space thermostat adjustable differential A19DAC strap on thermostat A19DAF strap on thermostat Adjustment 1 Models set low refer to cover label The dial indicates the low switch point 1 2 open 1 3 closed The high switch point 1 2 closed 1 3 open is obtained by adding the differential to the low switch point 2 Models set high refer to cover label The dial indicates the high switch poi...

Page 3: ...lb well optional 35 to 10 1b 9 5 x 110 Tin plated WEL14A602R 35 to 10 3 Stainless Steel 5 to 28 1b 9 5 x 135 Tin plated WEL14A603R 5 to 28 3 Stainless Steel 35 to 40 1b 9 5 x 110 Tin plated WEL14A602R 35 to 40 3 Stainless Steel 0 to 13 1a 9 3 x 80 WEL16A601R 0 to 43 3 Stainless Steel 1 to 60 1b 9 5 x 115 WEL14A602R 5 to 32 1b 9 5 x 155 Tin plated No bulb well available 10 to 95 1a 7 4 x 75 WEL11A6...

Page 4: ...m 85 C A19 A3 A19ABC 9116 10 to 95 3 5 to 13 1a set high 3 5 m 115 C A19ABC 9106 40 to 120 3 5 to 13 2 set high 145 C A19ABC 9011 bulb well incl 40 to 120 3 5 to 13 4h set high 2 m 145 C A19ABC 9012 bulb well incl Type A19ACC Capillary thermostat lock out low with manual reset 35 to 10 6 M 1b set low 2 m 60 C A19ACC 9100 35 to 10 N 6 M 1b set low 3 5 m 60 C A19ACC 9105 35 to 10 N 6 M 1b set low 5 ...

Page 5: ...5 to 10 2 5 3 set low 60 C A19 B1 A19BAC 9250 5 to 28 2 3 set low 60 C A19 B2 A19BAC 9251 0 to 43 2 3 set high 60 C A19 B3 A19BAC 9001 Type A19BBC Space thermostat adjustable differential 35 to 40 2 8 8 3 set low 60 C A19 B4 A19BBC 9275 Type A19DAC Strap on thermostat fixed differential 40 to 120 4 5 20 set high 145 C A19DAC 9001 92 to 116 2 20 set high 145 C A19DAF 9001 Note If what you need is n...

Page 6: ...8 mm WEL14A603R 147 mm 193 mm 9 8 mm WEL16A601R 71 mm 117 mm 9 5 mm 1 Bushing 2 Set screw 3 Adapter 1 2 14 NPT Fig 10 Bulb well brass copper pipe 76 63 27 ø 5 5 3x 1 2 14 NPT 11 5 Fig 11 Duct flange to be used with closed tank connector FTG13A 600R Order number T 752 1001 3 4 3 5 6 2 1 1 Style 1b bulb support tube 2 Packing nut 3 Washer 4 Packing 5 Adapter 1 2 14 NPT 6 Bulb Fig 12 Closed tank conn...

Page 7: ...rols Inc Catalogue Section 1 Order No PD A19A E 7 Dimensions mm 32 13 19 75 19 7 55 40 13 125 46 5 21 5 6 16 28 3 6 1 2 4 3 1 Reset lever 2 Knob packed separately with the control 3 22 3 mm dia cable inlet hole for PG 16 4 Earth screw Fig 13 ...

Page 8: ...m hole for PG 16 connector Material Case 1 75 mm cold rolled zinc plated steel Cover 1 5 mm ABS plastic Protection Class IP30 Shipping weight Individual pack 0 4 kg Overpack 10 kg 24 pcs Dimensions see dimension drawing The performance specifications are nominal and conform to acceptable industry standards For applications at conditions beyond these specifications consult the local Johnson Control...

Page 9: ...HET INSTALLEREN EN BEWAAR ZE VOOR TOEKOMSTIG GEBRUIK 1 Temperatuur instellingsschijf 2 Knop voor temperatuur afstelling apart verpakt 3 Kap voor afdekking van temperatuurinstelling apart verpakt 4 Differentie instellingshendel alleen bij modellen met verstelbare differentie 5 Deksel niet op A19AGC A19AGF en A19BGC modellen De A19 is een thermostaat ontworpen voor het meten van temperatu ren Volgen...

Page 10: ...r kun beregnet til at blive brugt som driftsregulatorer Hvis en fejl i en driftsregulator kan resultere i fare for personer eller materielle skader er installatøren ansvarlig for at der installeres anordninger eller systemer som beskytter eller advarer mod fejl i regulatoren Installation DREJ IKKE PÅ DE FASTGJORTE SKRUER Forsyningsspænding skal kobles fra før dæksel afmonteres Ved A19AGC A19AGF og...

Reviews: