background image

A19A
Issue 03/03/2003

© 2003 Johnson Controls Inc.

 

Catalogue Section 1

Order No.

 

PD

-

A19A-E

3

S

ensor styles

Fig. 4

Style 1a (drawn bulb)

Fig.5

Style 1b swaged bulb, can be used with

closed-tank connector FTG13A-600

½" x 14 NPT

33.3

60

Fig. 6

Style 4h

½" x 14 NPT

58.3

60

Fig. 7

Style 2

Fig. 8

Style 20

Fig. 9

Style 3 (coil)

B

ulb size and finish, bulb wells

Range (°C)

Style

Bulb size

(mm)

Finish

Bulb well (optional)

-35 to +10

1b

9.5 x 110

Tin-plated

WEL14A602R

-35 to +10

3

-

Stainless Steel

-

  -5 to +28

1b

9.5 x 135

Tin-plated

WEL14A603R

  -5 to +28

3

-

Stainless Steel

-

-35 to +40

1b

9.5 x 110

Tin-plated

WEL14A602R

-35 to +40

3

-

Stainless Steel

-

   0 to 13

1a

9.3 x   80

-

WEL16A601R

   0 to 43

3

-

Stainless Steel

-

   1 to 60

1b

9.5 x 115

-

WEL14A602R

   5 to 32

1b

9.5 x 155

Tin-plated

No bulb well available

 10 to 95

1a

7.4 x   75

-

WEL11A601R

 40 to 120

1b

9.5 x 100

-

WEL14A602R

 35 to 150

1a

5    x 265

-

No bulb well or closed tank

connector possible

 90 to 290

1a

5    x 155

-

No bulb well or closed tank

connector possible

Summary of Contents for A19D

Page 1: ...inimum number of models On request a built in high or low limit stop is possible and can be adjusted quickly and easily in the field All models have a universal way of adjustment For this purpose a knob and sealing cap are enclosed All A19 style 1 wholesaler code models have a bulb clamp plus screw also enclosed A19A capillary thermostat A19B space thermostat Feature and Benefits Liquid filled sen...

Page 2: ...ential A19BBC space thermostat adjustable differential A19DAC strap on thermostat A19DAF strap on thermostat Adjustment 1 Models set low refer to cover label The dial indicates the low switch point 1 2 open 1 3 closed The high switch point 1 2 closed 1 3 open is obtained by adding the differential to the low switch point 2 Models set high refer to cover label The dial indicates the high switch poi...

Page 3: ...lb well optional 35 to 10 1b 9 5 x 110 Tin plated WEL14A602R 35 to 10 3 Stainless Steel 5 to 28 1b 9 5 x 135 Tin plated WEL14A603R 5 to 28 3 Stainless Steel 35 to 40 1b 9 5 x 110 Tin plated WEL14A602R 35 to 40 3 Stainless Steel 0 to 13 1a 9 3 x 80 WEL16A601R 0 to 43 3 Stainless Steel 1 to 60 1b 9 5 x 115 WEL14A602R 5 to 32 1b 9 5 x 155 Tin plated No bulb well available 10 to 95 1a 7 4 x 75 WEL11A6...

Page 4: ...m 85 C A19 A3 A19ABC 9116 10 to 95 3 5 to 13 1a set high 3 5 m 115 C A19ABC 9106 40 to 120 3 5 to 13 2 set high 145 C A19ABC 9011 bulb well incl 40 to 120 3 5 to 13 4h set high 2 m 145 C A19ABC 9012 bulb well incl Type A19ACC Capillary thermostat lock out low with manual reset 35 to 10 6 M 1b set low 2 m 60 C A19ACC 9100 35 to 10 N 6 M 1b set low 3 5 m 60 C A19ACC 9105 35 to 10 N 6 M 1b set low 5 ...

Page 5: ...5 to 10 2 5 3 set low 60 C A19 B1 A19BAC 9250 5 to 28 2 3 set low 60 C A19 B2 A19BAC 9251 0 to 43 2 3 set high 60 C A19 B3 A19BAC 9001 Type A19BBC Space thermostat adjustable differential 35 to 40 2 8 8 3 set low 60 C A19 B4 A19BBC 9275 Type A19DAC Strap on thermostat fixed differential 40 to 120 4 5 20 set high 145 C A19DAC 9001 92 to 116 2 20 set high 145 C A19DAF 9001 Note If what you need is n...

Page 6: ...8 mm WEL14A603R 147 mm 193 mm 9 8 mm WEL16A601R 71 mm 117 mm 9 5 mm 1 Bushing 2 Set screw 3 Adapter 1 2 14 NPT Fig 10 Bulb well brass copper pipe 76 63 27 ø 5 5 3x 1 2 14 NPT 11 5 Fig 11 Duct flange to be used with closed tank connector FTG13A 600R Order number T 752 1001 3 4 3 5 6 2 1 1 Style 1b bulb support tube 2 Packing nut 3 Washer 4 Packing 5 Adapter 1 2 14 NPT 6 Bulb Fig 12 Closed tank conn...

Page 7: ...rols Inc Catalogue Section 1 Order No PD A19A E 7 Dimensions mm 32 13 19 75 19 7 55 40 13 125 46 5 21 5 6 16 28 3 6 1 2 4 3 1 Reset lever 2 Knob packed separately with the control 3 22 3 mm dia cable inlet hole for PG 16 4 Earth screw Fig 13 ...

Page 8: ...m hole for PG 16 connector Material Case 1 75 mm cold rolled zinc plated steel Cover 1 5 mm ABS plastic Protection Class IP30 Shipping weight Individual pack 0 4 kg Overpack 10 kg 24 pcs Dimensions see dimension drawing The performance specifications are nominal and conform to acceptable industry standards For applications at conditions beyond these specifications consult the local Johnson Control...

Page 9: ...HET INSTALLEREN EN BEWAAR ZE VOOR TOEKOMSTIG GEBRUIK 1 Temperatuur instellingsschijf 2 Knop voor temperatuur afstelling apart verpakt 3 Kap voor afdekking van temperatuurinstelling apart verpakt 4 Differentie instellingshendel alleen bij modellen met verstelbare differentie 5 Deksel niet op A19AGC A19AGF en A19BGC modellen De A19 is een thermostaat ontworpen voor het meten van temperatu ren Volgen...

Page 10: ...r kun beregnet til at blive brugt som driftsregulatorer Hvis en fejl i en driftsregulator kan resultere i fare for personer eller materielle skader er installatøren ansvarlig for at der installeres anordninger eller systemer som beskytter eller advarer mod fejl i regulatoren Installation DREJ IKKE PÅ DE FASTGJORTE SKRUER Forsyningsspænding skal kobles fra før dæksel afmonteres Ved A19AGC A19AGF og...