background image

 
P/N IM-520/MH Rev. E 

5

 

© 2017 Johnson Controls. All rights reserved. All specifications and other information 
shown were current as of document revision date and are subject to change without notice.

 

 

Wiring between the sounders is accomplished by connecting between them using TB1 
input and output. Install conduit into the knockout located at the bottom edge of the back 
box. Use this conduit to run wires between units. Terminals 1+2 are sync output and 3+4 
are sync input. Wiring must start at the master. Connect the sync output from the master to 
the sync input of the first slave. Observe polarity of the connections. Terminal 1 on the 
master should go to terminal 4 on the slave and terminal 2 on the master should go to 
terminal 3 on the slave. To connect more than one slave, continue to wire from output to 
input slave to slave until the last one is connected. Refer to figure 4 for the wiring diagram 
of interconnected sounders.  
 
Problems with wiring or improper jumper settings will cause an EOL/Config trouble at the 
control panel. Check the wiring and jumper settings and correct any wiring/configuration 
issues. 

Note: The sounders will still activate as programmed even if an EOL/Config 

error is present on the control panel but they may not be synchronized. 

 

 

FIGURE 4 

 
Pseudo Master Feature 

If a slave loses its sync communication with its master it will automatically switch to pseudo 
master mode. In this mode the pseudo master will assume master functions and generate 
supervision and sync pulses to keep connection integrity monitored and any other down 

Summary of Contents for 520

Page 1: ...on an installation location Refer to the individual sections in this manual to perform the sound level and signal survey testing Sound output level and RF signal survey tests must be conducted prior to and after mounting the product Once successful sound and signal survey tests have been completed the 520 MH can be mounted Mounting options include single gang dual gang 4 conduit box or surface mou...

Page 2: ... test will produce the temporal 3 pattern for 5 seconds to allow a db sound output measurement to be obtained at the desired location This test can be performed without the unit being enrolled into a panel or in a network making for a good tool for pre installation testing Loud Norm jumper 520 only The model 520 has an optional loud setting of the sound level output The J8 jumper can be selected f...

Page 3: ...one or two beeps One beep indicates an unacceptable location and two beeps indicate an acceptable location If only one beep is heard then relocate the model 520 MH mounting position closer to the nearest repeater or control panel and perform the test again Continue this procedure until 2 beeps are achieved Do not mount the appliance detector unless 2 beeps are heard when performing 5 consecutive s...

Page 4: ...thin one room Note Interconnection of models 520 and MH is not recommended as synchronization is not guaranteed between different models When connected together the sounders will synchronize their temporal 3 and 4 520 only patterns when multiple sounders are activated To achieve synchronization the sounders must be both correctly configured as master and slave s and wired together Master and slave...

Page 5: ...and terminal 2 on the master should go to terminal 3 on the slave To connect more than one slave continue to wire from output to input slave to slave until the last one is connected Refer to figure 4 for the wiring diagram of interconnected sounders Problems with wiring or improper jumper settings will cause an EOL Config trouble at the control panel Check the wiring and jumper settings and correc...

Page 6: ...y 90 seconds The RF and sounder batteries send two uniquely identified low battery troubles If the RF battery is low a low battery trouble will be present on the panel If the sounder driver batteries are low a low battery2 trouble signal will be present on the control panel If more than one type of trouble exists all will be repeated in increments of 90 seconds Always replace the low battery with ...

Page 7: ...r The 520 MH contains a built in tilt switch that will cause a Tamper signal to be transmitted if the front cover of the sounder is removed A tamper signal is transmitted and repeated every 90 seconds until the front cover is put back into position Where more than one type of trouble exists all will be repeated in increments of 90 seconds Note The tamper trouble is self restoring on CP 3500D or ne...

Page 8: ...l and NFPA 72 or local requirements Transmission In compliance with FCC part 15 Test Transmission Every 90 seconds Overall dimensions 8 25 x 5 5 x 2 5 Weight 19 2 oz without battery FCC Statement Important Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment This device complies with part 15 of the FCC ...