background image

Technical specifications

Table 9: IOM3723 technical specifications

Product Code Number

MS-IOM3723-0 Input/Output Module

Note: 

The IOM3723 model is only available in certain regions. Contact your local

Johnson Controls representative for more information.

Power Requirement

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2

(North America), Safety Extra-Low Voltage (SELV) (Europe)

Power Consumption

14 VA maximum

Ambient Conditions

Operating:

 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing

Storage:

 -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing

Addressing

DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and 128–255

are reserved and not valid expansion module addresses.)

Communications Bus

BACnet

®

 MS/TP, RS-485:

3-wire FC Bus between the supervisory controller and other controllers (for MS/TP bus

communications at 38,400 baud)
4-wire SA bus between expansion module, network sensors and other sensor/actuator

devices, includes a lead to source 15 VDC supply power (from expansion module) to bus

devices (for MS/TP bus communications at 38,400 baud)

Processor

RX631 Renesas

®

 32-bit microcontroller

Memory

4 MB external serial flash memory and 768 KB internal flash and 128 KB internal RAM

Input and Output Capabilities

16 - Binary Inputs:

 Defined as Dry Contact Maintained or Pulse Counter/Accumulator

Mode

Terminations

Input:

 Fixed Screw Terminal Blocks

SA/FC Bus and Supply Power:

 4-Wire and 3-Wire Pluggable Screw Terminal Blocks

Mounting

Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface

with three integral mounting clips on controller

Housing

Enclosure material:

 ABS and polycarbonate UL94 5VB; self-extinguishing, plenum-rated

Protection Class: IP20 (IEC529)

Dimensions (Height x Width x Depth)

150 mm x 164 mm x 53 mm (5-7/8 in. x 6-1/2 in. x 2-1/8 in.) including terminals and

mounting clips

Note: 

Mounting space requires an additional 50 mm (2 in.) space on top, bottom

and front face of expansion module for easy cover removal, ventilation, and wire

terminations.

Weight

0.5 kg (1.1 lb)

Compliance

United States:

 UL Listed, File E107041, CCN PAZX, UL 916, Energy Management

Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A

Canada:

 UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment

Industry Canada Compliant, ICES-003

Europe:

 Johnson Controls declares that this product is in compliance with the essential

requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand

: RCM Mark, Australia/NZ Emissions Compliant

BACnet International:

 BACnet Testing Laboratories (BTL) Protocol Revision 18 Listed and

Certified BACnet Smart Actuator (B-SA)

The performance specifications are nominal and conform to acceptable industry standard. For application at

conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be

liable for damages resulting from misapplication or misuse of its products.

IOM3723 Input/Output Module Installation Guide

13

Summary of Contents for 24-10143-1124

Page 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Page 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Page 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Page 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Page 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Page 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Page 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Page 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Page 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Page 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Page 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Page 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Page 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Page 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Reviews: