Johnson Controls 24-10143-1124 Installation Manual Download Page 5

Terminal blocks and bus ports

See Figure 1 for terminal block and bus port

locations on the expansion module. Observe the

following guidelines when wiring an expansion

module.

Input terminal blocks

The IOM3723 has inputs only (no outputs). The

inputs are located on both the top and bottom

of the expansion module. See Table 2 for more

information about I/O terminal functions,

requirements, and ratings.

SA/FC bus terminal block

An IOM can be connected to an SA bus or an FC bus,

but not to both buses simultaneously. The SA/FC

bus terminal block is a removable, 4-terminal plug

that fits into a board-mounted jack.
When connecting the IOM to an FC bus, wire the

bus terminal block plugs on the expansion module,

and the other expansion modules in a daisy-chain

configuration using 3-wire twisted, shielded cable as

shown in the following figure.

Figure 4: FC bus terminal block wiring

When connecting the IOM to an SA bus, wire the bus

terminal block plugs on the expansion module and

other SA bus devices in a daisy-chain configuration

using 4-wire twisted, shielded cable as shown in

Figure 5.

Figure 5: SA bus terminal block wiring

Note: 

The SA PWR/SHLD terminal does not

supply 15 VDC. The SA PWR/SHLD terminal

is isolated and can be used to connect (daisy

chain) the 15 VDC power leads on the SA bus

(Figure 5), or the cable shields on the FC bus

(Figure 4). The SA bus supervisor supplies 15

VDC to devices on the SA bus requiring power.

Supply power terminal block

The 24 VAC supply power terminal block is a gray,

removable, 3-terminal plug that fits into a board-

mounted jack on the top right of the expansion

module.
Wire the 24 VAC supply power wires from the

transformer to the HOT and COM terminals on the

terminal plug as shown in Figure 6. The middle

terminal on the supply power terminal block is not

used.

IOM3723 Input/Output Module Installation Guide

5

Summary of Contents for 24-10143-1124

Page 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Page 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Page 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Page 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Page 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Page 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Page 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Page 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Page 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Page 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Page 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Page 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Page 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Page 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Reviews: