MaInTenanCe
Inspect humidifier when servicing .
• Check system operation and inspect all plumbing connections and piping for signs of cracks or leaks.
• Inspect drain line to make sure it is not blocked and has constant downward slope. Clean or replace if necessary.
• Inspect steam hose to make sure it has no low spots and has constant upward slope from humidifier to dispersion tube in duct. If dispersion
tube is mounted below humidifier, inspect drip tee and drain .
Replace the canister annually and when prompted by the “Service” light .
1 . Press On/Off switch to turn humidifier off .
2 . Allow humidifier to drain . When the green Drain light stops flashing, disconnect main electrical power to humidifier .
3 . Remove front panel .
4 . Pull three wires off posts on top of canister . (Two large electrode conductors and one water level probe conductor .)
5 . Loosen hose clamp at top of canister .
6 . Slide hose off top of canister .
7 . Slide canister up and out of drain assembly . Discard canister .
8 . Remove O-ring from groove in drain assembly using small screw driver .
9 . Inspect drain assembly and remove any debris .
10 . Insert new O-ring into groove in drain assembly . (O-ring is provided with canister .) Dampen O-ring with water before inserting canister .
Do not use oil, grease, or any lubricant besides water .
11 . Make sure strainer is inserted into bottom of new canister .
12 . Insert canister into drain assembly . Position canister with label facing outward .
13 . Slip steam hose over top of canister and tighten hose clamp .
14 . Reattach three wires to posts on top of canister . (Larger electrode conductors are interchangeable .)
15 . Replace front panel .
16 . Restore electrical power to humidifier .
17 . Turn humidifier on and verify green On/Off light is illuminated .
18 . See Start-up procedure .
To RePlaCe THe CanISTeR
To SeRVICe THe fIll ValVe
If water flow from fill valve is restricted, disconnect inlet fitting and remove in-line strainer from inlet port using small screw . Clean or replace
strainer .
CaUTIon
• Allow humidifier to drain and disconnect power before servicing.
• Service should be performed by a qualified HVAC technician.