14.   SERVICING & MAINTENANCE

 

IMPORTANT:

 Before commencing any servicing or 

component replacement. Ensure the ELECTRICAL 
SUPPLY to the unit is ISOLATED.

 

NOTE: 

This unit is suspended and care MUST be 

taken when removing the access panel. Take care no 
components fall out. 

14.1 

All filters must be cleaned first before commencing 
servicing and maintenance. See Figure 14.

14.2 

Remove the magnetic strips and remove the filters. See 
Section 15 for cleaning.

14.3 

The supply and extract fans and heat exchanger need 
cleaning annually. See Paragraph 14.5 & 14.7.

14.4 

GAINING ACCESS TO THE UNIT

14.4.1  To gain access to the unit, remove the 2 magnetic filter strips then remove the filters. See Figure 14.
14.4.2  To remove the cover panel release the 2 screws securing the left of the cover plate access panel, slide off 

the locating slots and remove. See Figure 15.

14.4.3  Swivel the clear plastic insulator away from the PCB boards. See Figure 16.

FIGURE 15.  REMOVING COVER PLATE

FIGURE 14.  REMOVING FILTERS

FIGURE 16.   REMOVAL STRAP

REMOVAL 

STRAP

PLASTIC 

INSULATOR

MAGNETIC 

FILTER 

STRIPS

FILTERS

SCREWS

REMOVAL 

STRAP

PLASTIC 

INSULATOR

Summary of Contents for Q-VENT COMPACT-L

Page 1: ...tarley co uk INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Q VENT COMPACT L High Efficiency Ventilation System with Heat Recovery These instructions are to be left with the user Publication No ZZ...

Page 2: ...cal Room Layout 8 Duct Duct Connections 9 9 Installation Instructions 10 10 Electrical 10 11 Fan Performance Graph 10 12 Circuit Diagrams 11 13 Commissioning 12 Pre Commissioning Check Fan Adjustment...

Page 3: ...single duct and grille 2 2 The case is constructed in aluminium zinc coated steel Internal faces of the casing are acoustically lined with flame retardant acoustic foam 2 3 The unit is fitted with a...

Page 4: ...L H Fixing Bracket Screws 2 3 6mm x 19mm 21 3mm Condense Adapter 1 4 10mm Straight Hose Connector 1 5 Installation Servicing Maintenance Instructions 1 PCB RTC PCB FEATURES 18 RV1 Speed Adjuster 19 R...

Page 5: ...be in accordance with the appropriate standards The equipment must be provided with a local triple pole isolator switch 3 3 Ensure safety regulations and practices are adhered to when installing and...

Page 6: ...79 Sound Power Level LWA 42 Reference Flow Rate m h 72 Reference Pressure Difference Pa 50 SPI W m h 0 500 CONTROL FACTOR TYPOLOGY Control Factor and Control Typology 0 65 Local Demand Control INTERN...

Page 7: ...h 7 2 4 The unit has 4 connection spigots and each one is labelled Ensure that the correct duct is connected to the appropriate spigot 7 2 5 Consideration must be given to access and servicing The ser...

Page 8: ...elative to where the heat recovery unit is to be installed is to be checked for any appreciable connection misalignment and necessary adjustment made before proceeding any further NOTE The Q Vent Comp...

Page 9: ...he rigid ducting to grilles and the unit should be made with a flexible connection 8 4 The duct layout must be designed to suit the requirements for the ventilation recovery system and building layout...

Page 10: ...ARTHED ALL WIRING MUST CONFORM TO INSTITUTE OF ELECTRICAL ENGINEERS I E E REGULATIONS BS 7671 10 1 The unit is suitable for a 230V 50Hz single phase supply fused at 3A 10 2 The unit needs a mains flex...

Page 11: ...lacement Telephone 01604 762881 12 CIRCUIT DIAGRAMS FIGURE 10 Q VENT COMPACT L WIRING DIAGRAMS COLOUR CODE BN BROWN BU BLUE BK BLACK GNYE GREEN YELLOW RD RED WH WHITE YE YELLOW FIGURE 11 JS9 SWITCH WI...

Page 12: ...le see paragraph 13 4 4 13 3 4 To set boost see paragraph 13 5 4 13 3 5 Once both setting are correct press installer mode switch 13 3 6 When out of installer mode the Red LED will stop flashing NOTE...

Page 13: ...rate decreases lowering the thermal heat recovery through the heat exchanger lowering the supply air temperature NOTE If fans do not boost with mains present at the switched live terminal block then p...

Page 14: ...SWITCH FUNCTIONS Information Only SWITCH SWITCH POSITION DEFAULT SETTINGS SWITCH POSITION 1 ON Both fans externally controlled at the same time OFF Single fan externally controlled supply fan with CT...

Page 15: ...r cleaning 14 3 The supply and extract fans and heat exchanger need cleaning annually See Paragraph 14 5 14 7 14 4 GAINING ACCESS TO THE UNIT 14 4 1 To gain access to the unit remove the 2 magnetic fi...

Page 16: ...WATER OR ANY OTHER FLUIDS NOTE Under no circumstance must any sharp implements which are likely to distort or puncture the heat exchanger air passage walls be used 14 5 5 Wipe clean the condensate tr...

Page 17: ...shaped tool push the battery out of the casing and replace with new 14 8 5 If there is no power from the mains and battery and the unit is dead Replace the battery before using the RTC Kit to set the...

Page 18: ...www johnsonandstarley co uk 18 FIGURE 21 Q VENT COMPACT L DIMENSIONS 16 DIMENSIONS...

Page 19: ...18 SPARES LIST 2 1 3 6 4 3 ITEM PART No DESCRIPTION QTY 1 HR36 0119005 Air Circulation Fan Assembly Complete 1 2 HR36 0116005 Heat Exchanger Condense Tray Assembly Complete 1 3 HR34 0120055 Front Cove...

Page 20: ...7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales joh...

Reviews: