Johnson & Starley Q-VENT COMPACT-L Installation, Commissioning & Servicing Instructions Download Page 12

www.johnsonandstarley.co.uk

12

13.   COMMISSIONING

13.1 

PRE COMMISSIONING CHECK

 

Before commencing the commissioning procedure, refer to the design drawing for correct air flows. 

 

See Figure 5.

 

NOTE:

 Extract air and supply air volumes will not always be equal, therefore, when setting up, the extract 

system should be the datum.
13.1.1  Ensure that the exhaust and supply grilles or valves are open.
13.1.2  Check the airflow at the grilles or valves, and adjust to suit the design figures.
13.1.3  For bathroom extract this unit is factory set for 8 l/s in trickle mode and 24 l/s in boost mode, based 

on the system configuration in Figure 3.

13.1.4  Check the voltage of the RTC PCB battery. Refer to paragraph 14.8.3.

 

NOTE:

 If changes are required to meet differing system specifications the following on site adjustments can 

be made.

13.2 

FAN ADJUSTMENT FOR EXTRACT

 

At the start of any fan adjustment, you MUST check the trickle airflow rate and boost airflow rate before 
commencing.

13.3 

INSTALLER MODE

 

NOTE:

 The install mode has a time out function. If the unit has been powered up but not commissioned 

within 3 hours then you will not be able to access the installer mode without first turning the power supply off 
for 10 seconds and then back on again.

 

This function is there to allow for situations where the unit is not taken out of installer mode.
13.3.1  To start installer mode, press installer mode switch.
13.3.2  When installer mode is ready the red LED indicator will start flashing every second. Now extract 

and supply fans can be adjusted. 

13.3.3  To set trickle see paragraph 13.4.4.
13.3.4  To set boost see paragraph 13.5.4.
13.3.5  Once both setting are correct press installer mode switch.
13.3.6  When out of installer mode the Red LED will stop flashing.

NOTE:

  When switch live is OFF there is no switch live present.

 

When switch live is ON switch live is present.

13.4 

TRICKLE AIRFLOW ADJUSTMENT ONLY

13.4.1  Trickle airflow rate needs to be 8 l/s. To adjust this the switch live should be OFF.

NOTE: 

  During the adjustment do not put switch live ON at any point.  

13.4.2  Put unit into installer mode.
13.4.3  To adjust the TRICKLE setting turn RV1 (extract fan) and RV2 (supply air fan) clockwise 

 to 

increase the airflow rate and anti-clockwise 

 to decrease the airflow rate.

13.4.4  When it is set to 8 l/s, take the unit out of installer mode. Red LED will stop flashing.

13.5 

BOOST AIRFLOW ADJUSTMENT ONLY

13.5.1  Boost airflow rate needs to be 24 l/s. To adjust this switch live should be 

ON

.

NOTE:

   During the adjustment do not switch OFF the switch live at any point.

13.5.2  To adjust the BOOST setting turn RV1 (extract fan). 
 

(In default mode only the extract fan will boost.)

13.5.3  When it is set to 24 l/s, take the unit out of installation mode. Red LED will stop flashing.

13.6  

SETTING SPEED POSITIONS

POSITION 1 

 

13.6.1  After setting the required airflows in auto mode turn the switch to position 1.

 

 

 

13.6.2  Ensure unit is out of installer mode and switch live is OFF.

 

 

 

13.6.3  Rotate the potentiometer 1 (on reverse side of the switch) to the  

 

 

 

required position to provide the required airflow.

 

POSITION 2

 

 

13.6.4  Turn switch to position 2.

 

 

 

13.6.5  Ensure unit is out of installer mode and switch live is OFF.

 

 

 

13.6.6  Rotate the potentiometer 2 (on the reverse side of the switch) to the  

 

 

 

required position to provide the required airflow.

Summary of Contents for Q-VENT COMPACT-L

Page 1: ...tarley co uk INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Q VENT COMPACT L High Efficiency Ventilation System with Heat Recovery These instructions are to be left with the user Publication No ZZ...

Page 2: ...cal Room Layout 8 Duct Duct Connections 9 9 Installation Instructions 10 10 Electrical 10 11 Fan Performance Graph 10 12 Circuit Diagrams 11 13 Commissioning 12 Pre Commissioning Check Fan Adjustment...

Page 3: ...single duct and grille 2 2 The case is constructed in aluminium zinc coated steel Internal faces of the casing are acoustically lined with flame retardant acoustic foam 2 3 The unit is fitted with a...

Page 4: ...L H Fixing Bracket Screws 2 3 6mm x 19mm 21 3mm Condense Adapter 1 4 10mm Straight Hose Connector 1 5 Installation Servicing Maintenance Instructions 1 PCB RTC PCB FEATURES 18 RV1 Speed Adjuster 19 R...

Page 5: ...be in accordance with the appropriate standards The equipment must be provided with a local triple pole isolator switch 3 3 Ensure safety regulations and practices are adhered to when installing and...

Page 6: ...79 Sound Power Level LWA 42 Reference Flow Rate m h 72 Reference Pressure Difference Pa 50 SPI W m h 0 500 CONTROL FACTOR TYPOLOGY Control Factor and Control Typology 0 65 Local Demand Control INTERN...

Page 7: ...h 7 2 4 The unit has 4 connection spigots and each one is labelled Ensure that the correct duct is connected to the appropriate spigot 7 2 5 Consideration must be given to access and servicing The ser...

Page 8: ...elative to where the heat recovery unit is to be installed is to be checked for any appreciable connection misalignment and necessary adjustment made before proceeding any further NOTE The Q Vent Comp...

Page 9: ...he rigid ducting to grilles and the unit should be made with a flexible connection 8 4 The duct layout must be designed to suit the requirements for the ventilation recovery system and building layout...

Page 10: ...ARTHED ALL WIRING MUST CONFORM TO INSTITUTE OF ELECTRICAL ENGINEERS I E E REGULATIONS BS 7671 10 1 The unit is suitable for a 230V 50Hz single phase supply fused at 3A 10 2 The unit needs a mains flex...

Page 11: ...lacement Telephone 01604 762881 12 CIRCUIT DIAGRAMS FIGURE 10 Q VENT COMPACT L WIRING DIAGRAMS COLOUR CODE BN BROWN BU BLUE BK BLACK GNYE GREEN YELLOW RD RED WH WHITE YE YELLOW FIGURE 11 JS9 SWITCH WI...

Page 12: ...le see paragraph 13 4 4 13 3 4 To set boost see paragraph 13 5 4 13 3 5 Once both setting are correct press installer mode switch 13 3 6 When out of installer mode the Red LED will stop flashing NOTE...

Page 13: ...rate decreases lowering the thermal heat recovery through the heat exchanger lowering the supply air temperature NOTE If fans do not boost with mains present at the switched live terminal block then p...

Page 14: ...SWITCH FUNCTIONS Information Only SWITCH SWITCH POSITION DEFAULT SETTINGS SWITCH POSITION 1 ON Both fans externally controlled at the same time OFF Single fan externally controlled supply fan with CT...

Page 15: ...r cleaning 14 3 The supply and extract fans and heat exchanger need cleaning annually See Paragraph 14 5 14 7 14 4 GAINING ACCESS TO THE UNIT 14 4 1 To gain access to the unit remove the 2 magnetic fi...

Page 16: ...WATER OR ANY OTHER FLUIDS NOTE Under no circumstance must any sharp implements which are likely to distort or puncture the heat exchanger air passage walls be used 14 5 5 Wipe clean the condensate tr...

Page 17: ...shaped tool push the battery out of the casing and replace with new 14 8 5 If there is no power from the mains and battery and the unit is dead Replace the battery before using the RTC Kit to set the...

Page 18: ...www johnsonandstarley co uk 18 FIGURE 21 Q VENT COMPACT L DIMENSIONS 16 DIMENSIONS...

Page 19: ...18 SPARES LIST 2 1 3 6 4 3 ITEM PART No DESCRIPTION QTY 1 HR36 0119005 Air Circulation Fan Assembly Complete 1 2 HR36 0116005 Heat Exchanger Condense Tray Assembly Complete 1 3 HR34 0120055 Front Cove...

Page 20: ...7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales joh...

Reviews: