Johnson & Starley Q-VENT COMPACT-L Installation, Commissioning & Servicing Instructions Download Page 13

NOTE:   

In manual modes 1 & 2, if the switch live is turned ON,       
both fans turn to the setting which was set in the auto 
mode. 

13.7  

WATER DETECTION IN CONDENSE TRAY

13.7.1  If the condensate build up is unable to flow out of the drain pipe and the water rises above a 

predetermined level it will be detected by the sensors in the condense tray and the red LED will 
flash every 3 seconds until the condense tray is drained.

13.7.2  The fans will stop to prevent any further water to build up.
13.7.3  If you are running in installer mode, you will not be able to continue with fan speed adjustments.
13.7.4  The LED will revert back to flashing every second after water level has dropped below predetermined 

level the fans will restart.

13.7.5  If condition persists, investigate the cause and rectify.

13.8 

HANDING

 

This unit is delivered configured for right hand configuration.

13.9 

THERMAL BY-PASS

 

The thermal by-pass is manually operated by turning the remote users control to By-Pass position. In

 

By-Pass mode the supply air flow rate increases and the extract flow rate decreases lowering the thermal 
heat recovery through the heat exchanger, lowering the supply air temperature.

NOTE:  If fans do not boost with mains present at the switched live terminal block then press blue switch on the 

RTC PCB.

FIGURE 12.

POTENTIOMETERS ON REVERSE OF SWITCH COVER

POSITION 1

POSITION 2

TABLE 4

AUTO

1

2

BY-PASS

SWITCH POSITION

% OF FULL SPEED

% OF FULL SPEED

% OF FULL SPEED

SWITCH LIVE NOT ACTIVATED

EXTRACT

10-35%

13-53%

53-99%

Extract Fan Returns to Commissioning Speed

SUPPLY

10-35%

13-53%

53-99%

Supply Fan Runs at Switch Position 2 Speed

SWITCH LIVE ACTIVATED

EXTRACT BOOST 

SWITCH LIVE

30-98%

Returns to 

Commissioning 

Speed

Returns to 

Commissioning 

Speed

Extract Fan Returns to Commissioning Speed

SUPPLY BOOST 

SWITCH LIVE

30-98%

Returns to 

Commissioning 

Speed

Returns to 

Commissioning 

Speed

Supply Fan Returns to Commissioning Speed

NOTES

GENERAL

Commissioning 

Speed

 Set in Installer 

Mode

Both Supply 

and Extract 

Track Together 

at Set Speed

Both Supply 

and Extract 

Track Together

at Set Speed

In By-Pass mode the supply air fan runs at the speed 

set at switch position 2 with the Extract fan running at 

the speed set at position Auto. When switch live has 

been activated both fans return to the commissioning 

speed set at position Auto.

Summary of Contents for Q-VENT COMPACT-L

Page 1: ...tarley co uk INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Q VENT COMPACT L High Efficiency Ventilation System with Heat Recovery These instructions are to be left with the user Publication No ZZ...

Page 2: ...cal Room Layout 8 Duct Duct Connections 9 9 Installation Instructions 10 10 Electrical 10 11 Fan Performance Graph 10 12 Circuit Diagrams 11 13 Commissioning 12 Pre Commissioning Check Fan Adjustment...

Page 3: ...single duct and grille 2 2 The case is constructed in aluminium zinc coated steel Internal faces of the casing are acoustically lined with flame retardant acoustic foam 2 3 The unit is fitted with a...

Page 4: ...L H Fixing Bracket Screws 2 3 6mm x 19mm 21 3mm Condense Adapter 1 4 10mm Straight Hose Connector 1 5 Installation Servicing Maintenance Instructions 1 PCB RTC PCB FEATURES 18 RV1 Speed Adjuster 19 R...

Page 5: ...be in accordance with the appropriate standards The equipment must be provided with a local triple pole isolator switch 3 3 Ensure safety regulations and practices are adhered to when installing and...

Page 6: ...79 Sound Power Level LWA 42 Reference Flow Rate m h 72 Reference Pressure Difference Pa 50 SPI W m h 0 500 CONTROL FACTOR TYPOLOGY Control Factor and Control Typology 0 65 Local Demand Control INTERN...

Page 7: ...h 7 2 4 The unit has 4 connection spigots and each one is labelled Ensure that the correct duct is connected to the appropriate spigot 7 2 5 Consideration must be given to access and servicing The ser...

Page 8: ...elative to where the heat recovery unit is to be installed is to be checked for any appreciable connection misalignment and necessary adjustment made before proceeding any further NOTE The Q Vent Comp...

Page 9: ...he rigid ducting to grilles and the unit should be made with a flexible connection 8 4 The duct layout must be designed to suit the requirements for the ventilation recovery system and building layout...

Page 10: ...ARTHED ALL WIRING MUST CONFORM TO INSTITUTE OF ELECTRICAL ENGINEERS I E E REGULATIONS BS 7671 10 1 The unit is suitable for a 230V 50Hz single phase supply fused at 3A 10 2 The unit needs a mains flex...

Page 11: ...lacement Telephone 01604 762881 12 CIRCUIT DIAGRAMS FIGURE 10 Q VENT COMPACT L WIRING DIAGRAMS COLOUR CODE BN BROWN BU BLUE BK BLACK GNYE GREEN YELLOW RD RED WH WHITE YE YELLOW FIGURE 11 JS9 SWITCH WI...

Page 12: ...le see paragraph 13 4 4 13 3 4 To set boost see paragraph 13 5 4 13 3 5 Once both setting are correct press installer mode switch 13 3 6 When out of installer mode the Red LED will stop flashing NOTE...

Page 13: ...rate decreases lowering the thermal heat recovery through the heat exchanger lowering the supply air temperature NOTE If fans do not boost with mains present at the switched live terminal block then p...

Page 14: ...SWITCH FUNCTIONS Information Only SWITCH SWITCH POSITION DEFAULT SETTINGS SWITCH POSITION 1 ON Both fans externally controlled at the same time OFF Single fan externally controlled supply fan with CT...

Page 15: ...r cleaning 14 3 The supply and extract fans and heat exchanger need cleaning annually See Paragraph 14 5 14 7 14 4 GAINING ACCESS TO THE UNIT 14 4 1 To gain access to the unit remove the 2 magnetic fi...

Page 16: ...WATER OR ANY OTHER FLUIDS NOTE Under no circumstance must any sharp implements which are likely to distort or puncture the heat exchanger air passage walls be used 14 5 5 Wipe clean the condensate tr...

Page 17: ...shaped tool push the battery out of the casing and replace with new 14 8 5 If there is no power from the mains and battery and the unit is dead Replace the battery before using the RTC Kit to set the...

Page 18: ...www johnsonandstarley co uk 18 FIGURE 21 Q VENT COMPACT L DIMENSIONS 16 DIMENSIONS...

Page 19: ...18 SPARES LIST 2 1 3 6 4 3 ITEM PART No DESCRIPTION QTY 1 HR36 0119005 Air Circulation Fan Assembly Complete 1 2 HR36 0116005 Heat Exchanger Condense Tray Assembly Complete 1 3 HR34 0120055 Front Cove...

Page 20: ...7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales joh...

Reviews: