www.johnsonandstarley.co.uk
8
FIGURE 9. Q-VENT CE50 CIRCUIT DIAGRAM
13. CIRCUIT DIAGRAM
14. COMMISSIONING
14.1
PRE COMMISSIONING CHECK
Before commencing the commissioning procedure, refer to the design drawing for correct airflows.
14.1.1 Ensure that the extract valves are open.
14.1.2 Check the airflow at the valves, and adjust to suit the design figures.
14.2
INSTALLER MODE
NOTE:
The install mode has a time out function. If the unit has been powered up but not commissioned within 3
hours then you will not be able to access the installer mode without first turning the power supply off for 10
seconds and then back on again.
This function is there to allow for situations where the unit is not taken out of installer mode.
14.2.1 To activate ‘Installer Mode’ Isolate the electrical supply, wait 5 seconds and reconnect.
14.2.2 When installer mode is ready the red LED indicator will start flashing every second. Now extract
and supply fans can be adjusted.
14.2.3 To set trickle see paragraph 14.3.4.
14.2.4 To set boost see paragraph 14.4.4.
14.2.5 Once both setting are correct press installer mode switch.
14.2.3 To exit Installer Mode once both settings are correct isolate the electrical supply, wait 5 seconds
and reconnect.
14.2.4 When out of installer mode the Red LED will stop flashing.
FIGURE 10. ADDITIONAL CONTROLS
COLOUR CODE
BN
BROWN
BU
BLUE
BK
BLACK
GNYE
GREEN/YELLOW
RD
RED
WH
WHITE
YE
YELLOW
12.1
ADDITIONAL CONTROLS
i)
Humidistat Sensor
ii)
Pull Cord, i.e bathroom
iii)
Air Quality Sensor
iv)
Boost Override