Telephone: 01604 762881
TABLE 7
TERMINAL POSITION
MINIMUM DISTANCE
A
Directly below an opening, air brick, opening window etc
300mm
B
Above an opening, air brick, opening window, etc.
300mm
C
Horizontally to an opening, air brick, opening window etc.
300mm
D
Below gutters, soil pipes or drain pipes.
75mm
E
Below eaves.
200mm
F
Below balconies.
200mm
G
From a vertical drain pipe or soil pipe.
150mm
H
From an internal or external corner. Greater than 450mm protrusion.
300mm
I
Above ground, roof or balcony level.
300mm
J
From a surface facing the terminal.
600mm
K
From a terminal facing the terminal.
1,200mm
M
Vertically from a terminal on the same wall.
1,500mm
N
Horizontally from a terminal on the same wall.
300mm
Q
Above intersection with roof.
530mm
P
From a vertical structure on the roof
300mm
R
From the terminal to the boundary
300mm
FIGURE 3
TERMINAL POSITIONS
TABLE 2
TERMINAL POSITIONS
Summary of Contents for ECONOMAIRE 32
Page 19: ...19 Telephone 01604 762881 FIGURE 12 CONTROL FLOWCHART 17 DIAGNOSIS FLOWCHARTS...
Page 20: ...www johnsonandstarley co uk 20 FIGURE 13 AIR HEATER DIAGNOSIS FLOWCHART...
Page 21: ...21 Telephone 01604 762881 FIGURE 14 CONTROL FLOWCHART...
Page 22: ...www johnsonandstarley co uk 22 18 LOGIC DIAGRAM FIGURE 15 LOGIC DIAGRAM...
Page 23: ...23 Telephone 01604 762881 3 19 SCHEMATIC DIAGRAM FIGURE 16 SCHEMATIC DIAGRAM...
Page 25: ...25 Telephone 01604 762881 21 DIMENSIONS FIGURE 18 DIMENSIONS...
Page 27: ...27 Telephone 01604 762881 FIGURE 19 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...
Page 31: ......