7
BASIC OPERATION
The water heaters covered in this manual have a helical coil
shaped heat exchanger that is submerged in the storage tank.
The water heater’s Main Burner is a radial design burner, it
is mounted on the top and fires downward through the heat
exchanger. This is a forced draft burner; hot burning gases are
forced through the heat exchanger under pressure and exit
through the exhaust/vent connection located at the bottom of the
water heater. See Figure 1 and Figure 2.
INTAKE AIR
(combustion air)
CONNECTION
3 INCH PVC
MAIN
BURNER
(radial design)
BLOWER
BURNER
ASSEMBLY
HEAT
EXCHANGER
HELICAL
COIL
VENT (exhaust)
OUTLET
Figure 1
FEATURES AND COMPONENTS
MODULATION
The water heaters covered by this manual are capable of
modulating their firing rate. The CCB monitors the water
temperature in the tank and regulates the firing rate to achieve
the target temperature setpoint. The firing rate is dictated by
the hot water draw, proximity to the tank temperature setpoint,
and various other temperature limitations. Periodically, when the
heater is in modulation mode, the CCB will increase the blower
speed for a short period of time to clear out any condensation
that has accumulated in the heat exchanger then decreases
the blower speed back to the modulating firing rate required to
maintain the desired tank temperature setpoint. This ramping up
and down of the blower speed is considered normal operation of
the water heater.
BLOWER/BURNER ASSEMBLY DETAIL
COMBUSTION
BLOWER
ASSEMBLY
FLAME
SENSOR
SPARK IGNITER
MAIN
BURNER
(radial design)
BURNER
FLANGE
INTAKE AIR
(combustion air)
CONNECTION
3 INCH PVC
Figure 2
Spark Igniter
The control system energizes the spark ignition control with 120
VAC during the ignition cycle. The spark ignition control then
sends a high-voltage current to the spark igniter which in turn
ignites the main burner air/gas mixture.
Flame Sensor
The control system also monitors the flame sensor to confirm
a flame is present at the Main Burner. If a flame is not verified
during the ignition trial period (3-5 seconds) the control system
will immediately de-energize the 24 Volt Gas Valve. See the
Sequence Of Operation Flow Chart on page 57.