CLIZIA D 24 A

13

EN

cod. 3541C830  -  Rev. 00 - 09/2012

Recheck both adjustments by pressing the heating buttons and adjust them if nec-
essary by repeating the above procedure.

Press the Eco/Comfort button for 2 seconds to return to the TEST mode.

Deactivate the TEST mode (see cap. 4.1).

Disconnect the pressure gauge.

Heating power adjustment

To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons detail 3 - fig. 1 to increase or decrease the power (min. = 00 - max. =
100). Press the 

reset

 button within 5 seconds and the max. power will remain that just

set. Exit TEST mode (see sec. 4.1).

Configuration Menu

Press the DHW buttons together for 10 seconds to access the configuration Menu. 7 pa-
rameters are available, indicated by the letter "b", which are not modifiable from Remote
Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.

Notes:

1.

Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.

2.

Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.

To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.

Service menu

The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub-
menus are available: press the Heating buttons to select, in increasing or decreasing or-
der, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means
Information Menu,  "Hi" means History Menu: after selecting the submenu, press the  Re-
set button again to access it; "rE" means History Menu Reset: see description.

"tS" - Transparent Parameters Menu

16 parameters indicated by the letter "P" are available: which are also modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.

fig. 10 - Gas valve

A

 - Upstream pressure point

B

 - Downstream pressure point

I

 - Gas valve electrical connection

R

 - Gas outlet

S

 - Gas inlet

fig. 11 - Gas valve connection

TYPE SGV100
Pi max 65 mbar
24 Vdc - class B+A

Contents Description

Range

Default

CLIZIA D 24 A

b01

Gas type selection

0=Natural Gas

0=Natural Gas

0=Natural Gas

1=LPG

b02

Boiler type selection

1=Bithermal instantaneous

1=Bithermal instantane-
ous

2=Monothermal instanta-
neous

2=Monothermal instanta-
neous
3=Heating only (3-way 
valve)
4=Heating only (circulating 
pump)

b03

Combustion chamber 
type selection

0=Sealed Chamber com-
bustion control
(without fume pressure 
switch)

0=Sealed Chamber with
combustion control

1=Open Chamber 
(with fume thermostat)

1=Open Chamber (with 
fume thermostat)
2=Sealed Chamber (with 
fume pressure switch)
3=Sealed Chamber com-
bustion control
(with fume thermostat on 
recuperator)
4=Low-NOx Sealed Cham-
ber (without fume pressure 
switch)
5=Low-Nox Open Cham-
ber (with fume thermostat)

R

B

I

A

S

~ 65

Ω

~ 24

Ω

b04

Primary Exchanger 
type selection
(b03=0)

0=Flat

0=Flat

0=Flat

1=Omega

No effect on adjust-
ment (b03=1)

--

0

No effect on adjust-
ment (b03=2)

--

0

Primary Exchanger 
type selection
(b03=3)

0=Flat

0=Flat

1=Omega

No effect on adjust-
ment (b03=4)

--

0

No effect on adjust-
ment (b03=5)

--

0

b05

Relay card LC32
operation selection 
(b02=1)

0=External gas valve

0=External gas valve

0=External gas valve

1=System filling solenoid 
valve
2=Solar 3-way valve

No effect on adjust-
ment (b02=2)

--

0

No effect on adjust-
ment (b02=3)

--

0

No effect on adjust-
ment (b02=4)

--

0

b06

Mains Voltage Fre-
quency

0=50Hz

0=50Hz

0=50Hz

1=60Hz

b07

Comfort burner on 
time
(b02=1)

0-20 seconds

5 seconds

5 seconds

No effect on adjust-
ment (b02=2)

--

5

No effect on adjust-
ment (b02=3)

--

5

No effect on adjust-
ment (b02=4)

--

5

Contents Description

Range

Default

CLIZIA D 24 A

P01

Ignition ramp Offset

0-40

10

10

P02

Heating ramp 

1-20°C/minute

5°C/minute

5°C/minute

P03

Heating standby time

0-10 minutes

2 minutes

2 minutes

P04

Heating Post-Circulation

0-20 minutes

6 minutes

6 minutes

P05

Heating user max. setpoint

31-85°C

80°C

80°C

P06

Max. power in heating

0-100%

100%

100%

P07

Burner shutdown in hot water 
production (b02=1)

0=Fixed

0=Fixed

0=Fixed

1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)

Burner shutdown in hot water 
production (b02=2)

0=Fixed

0=Fixed

1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)

Hot water tank hysteresis 
(b02=3)

0-4°C

2°C

Hot water tank hysteresis 
(b02=4)

0-4°C

2°C

P08

DHW standby time (b02=1)

0-60 seconds

30 seconds

60 seconds

DHW standby time (b02=2)

0-60 seconds

60 seconds

DHW standby time (b02=3)

0-60 seconds

30 seconds

DHW standby time (b02=4)

0-60 seconds

30 seconds

Contents Description

Range

Default

CLIZIA D 24 A

Summary of Contents for CLIZIA D 24 A

Page 1: ...216 208 131 75 234 77 9 725 5 676 5 49 5 76 5 54 51 79 5 75 5 A B C D F E 58 5 178 126 76 54 51 80 5 80 330 A B C D E F IT ISTRUZIONE PER L USO L INSTALLAZIONE E LA MANUTENZIONE EN INSTRUCTIONS FOR U...

Page 2: ...sto decremento impostazione temperatura impianto riscaldamento 4 Tasto incremento impostazione temperatura impianto riscaldamento 5 Display 6 Tasto Ripristino selezione modalit Estate Inverno Men Temp...

Page 3: ...rve di compensazione Regolazioni da Cronocomando Remoto A Se alla caldaia collegato il Cronocomando Remoto opzionale le regolazioni descritte in precedenza vengono gestite secondo quanto riportato nel...

Page 4: ...partire dall antirefouleur deve avere un tratto verticale di lun ghezza non inferiore a mezzo metro Per quanto riguarda il dimensionamento e la posa in opera delle canne fumarie e del tubo di raccordo...

Page 5: ...Valvola gas A Presa di pressione a monte B Presa di pressione a valle I Connessione elettrica Valvola gas R Uscita gas S Entrata gas fig 11 Connessione valvola gas TYPE SGV100 Pi max 65 mbar 24 Vdc c...

Page 6: ...che in quella di produzione d acqua sanitaria Verificare la buona accensione della caldaia effettuando diverse prove di accensio ne e spegnimento per mezzo del termostato ambiente o del comando remoto...

Page 7: ...re danneggiato Verificare il cablaggio o sostituire il sen sore Cablaggio in corto circuito Cablaggio interrotto F11 Anomalia sensore sanitario Sensore danneggiato Verificare il cablaggio o sostituire...

Page 8: ...ione gas max al bruciatore G20 mbar 12 0 Pressione gas min al bruciatore G20 mbar 1 5 Portata gas max G20 m3 h 2 73 Portata gas min G20 m3 h 0 88 Ugelli bruciatore G31 n x 11 x 0 79 Pressione gas alim...

Page 9: ...ma elettrico fig 16 Circuito elettrico A Attenzione Prima di collegare il termostato ambiente o il cronocomando UHmoto togliere il ponticello sulla morsettiera 81 1kW L N 230V 50 Hz 32 L N T T 278 T 4...

Page 10: ...re setting increase button 5 Display 6 Sliding Temperature Menu Summer Winter mode selection Reset button 7 Unit On Off Economy Comfort mode selection button 8 DHW symbol 9 DHW mode 10 Summer mode 11...

Page 11: ...from Remote Timer Control A If the Remote Timer Control optional is connected to the boiler the above ad justments are managed according to that given in table 1 Table 1 System water pressure adjustme...

Page 12: ...ackflow device Starting from the anti backflow device it must have a vertical section at least 50 cm long Current standards must be complied with regarding sizing and installation of the flues and con...

Page 13: ...connection TYPE SGV100 Pi max 65 mbar 24 Vdc class B A Contents Description Range Default CLIZIA D 24 A b01 Gas type selection 0 Natural Gas 0 Natural Gas 0 Natural Gas 1 LPG b02 Boiler type selectio...

Page 14: ...rning it on and off with the room thermostat or remote control Make sure the fuel consumption indicated on the meter matches that given in the technical data table in cap 5 Make sure that with no dema...

Page 15: ...t Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F11 DHW sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected...

Page 16: ...e G20 mbar 20 0 Max gas pressure at burner G20 mbar 12 0 Min gas pressure at burner G20 mbar 1 5 Max gas delivery G20 m3 h 2 73 Min gas delivery G20 m3 h 0 88 Burner nozzles G31 no x 11 x 0 79 Gas sup...

Page 17: ...iring diagram fig 16 Electrical circuit A Attention Remove the jumper on the terminal block before connecting the room thermostat or the remote timer control 81 1kW L N 230V 50 Hz 32 L N T T 278 T 42...

Page 18: ...encendido apagado del equipo 8 S mbolo de agua caliente sanitaria 9 Indicaci n de funcionamiento en ACS 10 Indicaci n de modo Verano 11 Indicaci n de multifunci n 12 Indicaci n de modo Eco Economy 13...

Page 19: ...or a distancia A Si la caldera tiene conectado el reloj programador a distancia opcional los ajustes descritos anteriormente se gestionan seg n lo indicado en la tabla 1 Tabla 1 Regulaci n de la presi...

Page 20: ...A partir del cortatiro ha de presentar un tramo vertical de longitud superior a medio metro Las dimensiones y la colocaci n de la chimenea y del tubo de conexi n han de respetar las normas vigentes B...

Page 21: ...icamente fig 10 V lvula del gas A Toma de presi n aguas arriba B Toma de presi n aguas abajo I Conexi n el ctrica de la v lvula del gas R Salida de gas S Entrada de gas fig 11 Conexi n de la v lvula d...

Page 22: ...ia Controlar que la caldera se encienda correctamente efectuando varias pruebas de encendido y apagado con el termostato de ambiente o el mando a distancia Comprobar que el consumo de gas indicado en...

Page 23: ...ambiar el sen sor Cableado en cortocircuito Cableado interrumpido F11 Anomal a del sensor de AS Sensor averiado Controlar el cableado o cambiar el sen sor Cableado en cortocircuito Cableado interrumpi...

Page 24: ...n gas G20 mbar 20 Presi n m xima en el quemador con G20 mbar 12 Presi n m nima en el quemador con G20 mbar 1 5 Caudal m ximo gas G20 m3 h 2 73 Caudal m nimo gas G20 m3 h 0 88 Inyectores quemador G31 n...

Page 25: ...ctrico fig 16 Circuito el ctrico A Atenci n Antes de conectar el termostato de ambiente o el reloj programa dor a distancia quitar el puente de la regleta de conexiones 81 1kW L N 230V 50 Hz 32 L N T...

Page 26: ...297 A6 5 C 15 C 2 2 1 1 1 2 3 4 5 6 7 8 9 10 11 12 Eco 13 14 15 16 17 11 1 d2 11 1 d1 Comfort 11 1 cap 4 4 11 1 d3 d4 2 3 5 7 1 5 2 7 1 5 3 B sez 3 3 2 4 6 1 2 10 1 6 1 2 3 4 1 30 C 80 C 45 C 4 0 1 4...

Page 27: ...rt 7 1 ECO 12 1 7 1 3 1 5 6 1 CU 1 1 1 10 0 3 1 OF 1 1 6 5 6 1 6 A 1 1 17 1 1 0 F37 1 7 7 3 3 1 3 2 EN 297 pr A6 5 C 15 C A I I I I I I I I I 20 30 40 50 60 70 80 90 85 20 10 0 10 20 1 2 3 4 5 6 8 9 1...

Page 28: ...B 4 4 1 1 cap 5 2 1 2 1 10 b01 1 2 1 00 01 1 2 1 10 3 4 TEST 3 4 1 5 TEST 9 9 TEST 100 3 4 1 00 100 1 1 0 2 1 100 TEST TEST 3 TEST 3 4 1 5 TEST 15 B TEST cap 4 1 Eco Comfort 2 q02 q02 1 2 10 3 1 1 2 3...

Page 29: ...0 b03 2 0 b03 3 0 0 1 Omega 2 b03 4 0 b03 5 0 R B I A S 65 24 b05 LC32 b02 1 0 0 0 1 2 3 b02 2 0 b02 3 0 b02 4 0 b06 0 50 0 50 0 50 1 60 b07 b02 1 0 20 5 5 b02 2 5 b02 3 5 b02 4 5 CLIZIA D 24 A P01 0...

Page 30: ...cap 5 4 3 12 1 4 4 11 1 A RESET 6 1 1 RESET F P10 b02 1 70 85 C 70 C 0 b02 2 0 b02 3 70 85 C 80 C b02 4 70 85 C 80 C P11 b02 1 0 5 0 30 b02 2 0 60 b02 3 0 60 b02 4 0 60 P12 0 100 100 100 P13 0 100 0 0...

Page 31: ...A02 A03 F04 20 F05 A06 F07 A09 F10 1 F11 F14 2 A16 F20 A21 A23 A24 F34 180 F35 F37 F39 A41 F42 F43 H 2O F50 7 44 8 56 9 72 10 74 11 78 14 81 19 95 22 114 27 126 32 138 36 139 37 194 38 241 39 278 42...

Page 32: ...36 194 CLIZIA D 24 A 25 8 Q 8 3 Q 23 5 P 7 0 P 23 5 7 0 Pmax 80 60 C 91 0 30 89 6 92 42 EEC NOx 3 150 NOx G20 x 11 x 1 35 G20 20 0 G20 12 0 G20 1 5 G20 3 2 73 G20 3 0 88 G31 x 11 x 0 79 G31 37 G31 35...

Page 33: ...CLIZIA D 24 A 33 RU cod 3541C830 Rev 00 09 2012 5 5 16 A 81 1kW L N 230V 50 Hz 32 L N T T 278 T 42 4 3 2 1 44 38 114 ABM01 LC32 3 2 1 95 126 72 139 138...

Page 34: ...rmit Il costruttore dichiara che questo apparecchio conforme alle seguenti direttive CEE Direttiva Apparecchi a Gas 2009 142 Direttiva Rendimenti 92 42 Direttiva Bassa Tensione Direttiva Compatibilit...

Page 35: ......

Page 36: ...95 GRUGLIASCO TORINO ITALIA TEL 011 40221 CAS POSTALE 1393 10100 TORINO TELEX 220364 IOTERM I TELEGR TF78 42 42 JOANNES TORINO TELEFAX 011 780 40 59 BRUCIATORI DI GASOLIO GAS NAFTA CALDAIE MURALI A GA...

Reviews: