-2-
Do not use this module to replace or partly replace roofs and walls of living buildings.
Do not install modules where flammable gas may be present.
Do not touch live terminals with bare hands. Use insulated tools for electrical connections.
Do not use water to extinguish the fire when the power supply is not disconnected.
Do not remove any part installed by Jinko Solar or disassemble the module.
All instructions should be read and understood before attempting to install, wire, operate and
maintain the module.
Don’t lift up PV modules using the attached cables or the junction box.
All Dual glass PV systems except the non-metallic frame must be earthed. If there is no
special regulation, please follow the National Electrical Code or other national code.
Under normal conditions, a photovoltaic module is likely to experience conditions that
produce more current and/or voltage than reported at standard test conditions. Accordingly,
the value of Isc and Voc marked on the module should be multiplied by 1.25 when
determining PV system component voltage ratings, conductor current ratings, fuse sizes,
and size of controls connected to the PV output.
Once the PV module has been shipped to the installation site, all of the parts should be
unpacked properly with care.
Do not stand or step on the PV module like below pictures show. This is prohibited and there
is a risk of damage to the module and cause injury for you.
Only PV modules with the same cell size should be connected in series.
During transporting modules, please attempt to minimize shock or vibration to the module,
as this may damage the module or lead to cell micro cracks.
Use insulated tools for
electrical connection