background image

 

 

- 9

 

-

 

 

Note:

   

1)    All  installation  methods  herein  are  only  for  reference,  and  Jinko  solar  will  not 

provide related mounting components, the system installer or trained professional 

personnel  must  be  responsible  for  the  PV  system‟s  design, 

installation,  and 

mechanical load calculation and security of the system. 

2)    Before installing, you should confirm below important things:   

1) Visual check before installation, to make sure there is no bug in the packing 

and junction box as well as the surface of module, If have , remove and clean 
it . 

2) Check the series number is right or not. 

3) 

 

The modules installed at screws and the normal PV modules installed at the long 

sides with clamps are designed to meet a maximum positive (or downward) 
pressure of 5400Pa and negative (or upward) pressure of 2400 Pa (Refer to the 
mentioned module type in Table 1 and 2 in this manual). The light PV module and 
the modules installed at the short sides with clamps are designed to meet a 
maximum positive (or downward) pressure of 2400Pa and negative (or upward) 
pressure of 2400 Pa (Refer to the mentioned module type in Table 3 and 4 in this 
manual). When mounting modules in snow-prone or high-wind environments, 
Special care should be taken to mount the modules in a manner that provides 
sufficient design strength while meeting local code requirements. 

 

2.3.1 Fixation with screws 

 

The applicable products please refer to table 1. 
 
 
The frame of each module has 8 mounting holes (Length* Width: 14mm*9mm) used 
to secure the modules to support structure. Always use all the eight mounting holes to 
secure the modules. The module frame must be attached to a mounting rail using M8 
corrosion-proof  screws  together  with  spring  washers  and  flat  washers  in  eight 
symmetrical locations on the PV module. The applied torque should be big enough to 
fix it steadily. Please find detailed mounting information in the below illustration, 
 
 

Summary of Contents for JKM M-48 Series

Page 1: ...JinkoSolar Photovoltaic Module Installation Manual ...

Page 2: ...roduction 2 2 1 Climate condition 2 2 2 Site selection 2 3 1 Fixation with screws 2 3 2 Fixation with clamps at long sides of frames 2 2 3 Tilt angle selection 3 Wiring and connection 4 Maintenance and care 5 Electrical specification Edition 03 2015 4 1 Visual Inspection 4 3 Inspection of Connector and Cable 24 16 26 6 Disclaimer of Liability 24 4 2 Cleaning 2 3 3 Fixation with clamps at short sid...

Page 3: ... xxx 250 335 in steps of 5 72 cells JKMxxxM 60 xxx 210 280 in steps of 5 60 cells JKMxxxM 60 J xxx 210 280 in steps of 5 60 cells JKMxxxM 60 Plus xxx 210 280 in steps of 5 60 cells JKMxxxM 48 xxx 170 220 in steps of 5 48 cells JKMxxxM 48 J xxx 170 220 in steps of 5 48 cells JKMxxxM 72B xxx 250 335 in steps of 5 72 cells JKMxxxM 60B xxx 210 280 in steps of 5 60 cells JKMSxxxM 72 xxx 250 335 in step...

Page 4: ...steps of 5 48 cells JKMxxxPP 48 xxx 170 225 in steps of 5 48 cells JKMxxxPP 48 J xxx 170 225 in steps of 5 48 cells JKMxxxPP 48 Plus xxx 170 225 in steps of 5 48 cells JKMxxxPP 48 J4 xxx 170 225 in steps of 5 48 cells JKMxxxP 72B xxx 250 340 in steps of 5 72 cells JKMxxxP 60B xxx 210 280 in steps of 5 60 cells JKMSxxxP 72 xxx 250 340 in steps of 5 72 cells JKMSxxxP 72 J xxx 250 340 in steps of 5 7...

Page 5: ...lar cell types with 4 busbars Plus the eagle Series module Make sure the array of modules installed within the Maximum permitted system voltage and the rating current and voltage of the sub equipments such as regulators and inverters The maximum permitted system voltage DC of the modules sold in Europe is 1000V The assembly is to be mounted over a fire resistant roof covering rated for the applica...

Page 6: ...taic module produces Electricity when exposed to the sun To reduce the risk of electrical shocks or burns modules may be covered with an opaque material during installation to avoid shocks or burns The installation work of the PV array can only be done under the protection of sun sheltering covers or sunshades and only qualified person can install or perform maintenance work on this module Follow ...

Page 7: ...ning component voltage ratings conductor current ratings fuse sizes and size of controls connected to the PV output Once the PV module has been shipped to the installation site all of the parts should be unpacked properly with care Do not stand or step on the PV module like below pictures show this is prohibited and there can be risks of micro crack which may cause a sharp decline of module s powe...

Page 8: ... all connections The interconnect cable should be securely fastened to the module frame Cable support should be done in a way to avoid the connector from scratching or impacting the back sheet of the module Do not touch the terminal box and the end of the interconnect cables connectors with bare hands during installation or under sunlight regardless of whether the PV module is connected to or disc...

Page 9: ...cent of their power output If the module faces 60 degrees away from true South or North the power loss will be 20 to 30 percent When choosing a site avoid trees buildings or obstructions which could cast shadows on the solar photovoltaic modules especially during the winter months when the arc of the sun is lowest over the horizon Shading causes loss of output even though the factory fitted bypass...

Page 10: ...es maximum output power when it faces the sun directly Figure1 PV module tilt angle For standalone systems with batteries where the PV modules are attached to a permanent structure the tilt angle of the PV modules should be selected to optimize the performance based on seasonal load and sunlight In general if the PV output is adequate when irradiance is low e g winter then the angle chosen should ...

Page 11: ...this manual The light PV module and the modules installed at the short sides with clamps are designed to meet a maximum positive or downward pressure of 2400Pa and negative or upward pressure of 2400 Pa Refer to the mentioned module type in Table 3 and 4 in this manual When mounting modules in snow prone or high wind environments Special care should be taken to mount the modules in a manner that p...

Page 12: ... Cell Pmax Dimensions mm JKMXXXM 72 JKMXXXM 72 I JKMXXXM 72 J JKMXXXM 72B 5 inch Mono 6 12 160 215Wp Module 1580 808 Frame 35 25 35 35 40 30 40 35 45 35 50 35 JKMXXXM 96 JKMXXXM 96 I JKMXXXM 96 J JKMXXXM 96B 5 inch Mono 8 12 210 285Wp Module 1575 1082 Frame 40 30 40 35 45 35 50 35 ...

Page 13: ...oly 6 12 250 340Wp Module 1956 992 Frame 40 30 40 35 50 35 JKMXXXM 72 JKMXXXM 72 J JKMxxxM 72 Plus JKMXXXM 72B 6 inch Mono 6 12 250 335Wp Module 1956 992 Frame 40 30 40 35 50 35 JKMXXXP 72L 6 inch Quasi mono 6 12 255 330Wp Module 1956 992 Frame 40 30 40 35 50 35 JKMXXXP 60L 6 inch Quasi mono 6 10 215 275Wp Module 1650 992 Frame 40 30 40 35 50 35 35 35 JKMSXXXM 72 JKMSXXXM 72 J 5 inch Mono 6 12 160...

Page 14: ...no 6 10 215 275 Module 1650 992 Frame 40 30 50 35 JKMxxxM 48 JKMxxxM 48 J 6 inch Mono 6 8 170 220 Module 1324 992 Frame 40 35 JKMSxxxM 48 J JKMSxxxM 48 Plus 6 inch Mono 6 8 170 220 Module 1324 992 Frame 40 35 JKMxxxP 48 JKMxxxPP 48 JKMxxxPP 48 J4 JKMxxxPP 48 J JKMxxxPP 48 Plus 6 inch Poly 6 8 170 225 Module 1324 992 Frame 40 35 JKMSxxxP 48 J JKMSxxxP 48 J4 JKMSxxxP 48 Plus 6 inch Poly 6 8 170 225 ...

Page 15: ...hod please be sure to use at least four clamps on each module two clamps should be attached on each long sides of the module Depending on the local wind and snow loads if excessive pressure load is expected additional clamps or support would be required to ensure the module can bear the load The applied torque should be big enough to fix it steadily about 8 Nm for safety you d better follow the cl...

Page 16: ... JKMSXXXP 60 J JKMSxxxP 60 J4 JKMSxxxP 60 Plus 6 inch Poly 6 10 210 280 1650 992 280 420 35 25 40 20 40 30 40 35 45 35 50 35 JKMSXXXM 60 JKMSXXXM 60 J JKMSxxxM 60 Plus 6 inch Mono 6 10 210 280 1650 992 280 420 35 25 40 20 40 30 40 35 45 35 50 35 JKMSXXXP 72 JKMSXXXP 72 J JKMSxxxP 72 J4 JKMSxxxP 72 Plus 6 inch Poly 6 12 250 335 1956 992 280 480 40 20 40 30 50 35 40 35 JKMSXXXM 72 JKMSXXXM 72 J JKMS...

Page 17: ... 40 35 45 35 50 35 1650 990 40 20 40 35 JKMXXXM 60 JKMXXXM 60 J JKMxxxM 60 Plus JKMXXXM 60B 6 inch Mono 6 10 210 280 1650 992 280 420 35 25 40 30 40 20 40 35 45 35 50 35 JKMXXXP 72 JKMXXXP 72 J JKMXXXPP 72 JKMXXXPP 72 J JKMSxxxP 72 J4 JKMSxxxP 72 Plus JKMXXXP 72B 6 inch Poly 6 12 250 340 1956 992 280 480 40 30 40 20 40 35 50 35 JKMXXXM 72 JKMXXXM 72 J JKMxxxM 72 Plus JKMXXXM 72B 6 inch Mono 6 12 2...

Page 18: ...J4 JKMxxxPP 48 J JKMxxxPP 48 Plus 6 inch Poly 6 8 170 225 1324 992 240 270 40 35 JKMSxxxP 48 J JKMSxxxP 48 J4 JKMSxxxP 48 Plus 6 inch Poly 6 8 170 225 1324 992 240 270 40 35 Max Pressure 5400Pa mechanical load Table 2 Mechanical dimensions when modules installed at long side with Clamp fitting method 2 Light PV module ...

Page 19: ...no 6 12 160 215 1580 808 280 320 270 JKMXXXM 96 JKMXXXM 96 I JKMXXXM 96 J JKMXXXM 96B 5 inch Mono 8 12 210 285 1575 1082 280 320 270 JKMXXXP 60 JKMXXXP 60 I JKMXXXP 60 J JKMXXXPP 60 JKMXXXPP 60 J JKMxxxP 60 J4 JKMxxxPP 60 J4 JKMxxxP 60 Plus JKMxxxPP 60 Plus JKMXXXP 60B 6 inch Poly 6 10 210 280 1650 992 300 340 330 Dimension mm mm Longer Frame Section 28 6 9 Short Frame Section 28 15 Beam Section 1...

Page 20: ...XM 96 JKMSXXXM 96 J 5 inch Mono 8 12 210 280 1580 1060 280 320 270 1575 1082 JKMSXXXP 60 JKMSXXXP 60 J JKMSxxxP 60 J4 JKMSxxxP 60 Plus 6 inch Poly 6 10 210 280 1636 990 300 340 330 1650 992 JKMSXXXM 60 JKMSXXXM 60 J JKMSxxxM 60 Plus 6 inch Mono 6 10 210 280 1636 990 300 340 330 1650 992 JKMSXXXP 72 JKMSXXXP 72 J JKMSxxxP 72 J4 JKMSxxxP 72 Plus 6 inch Poly 6 12 250 335 1952 990 420 460 330 1956 992...

Page 21: ...ng clamps at short side of frames The considerations and requirements about mounted by using clamps please refer to the instructions in 2 3 2 and find detailed mounting information in the below illustration the mounting place distance is suggested bigger than J and less than K as shown below Figure 5 PV module installed at short side with Clamp fitting method ...

Page 22: ...SXXXM 72 J JKMSxxxM 72 Plus 6 inch Mono 6 12 250 335 1956 992 50 240 40 35 JKMSxxxP 60L 6 inch Quasi mono 6 10 215 275 1650 992 50 240 40 35 JKMSXXXP 72L 6 inch Poly 6 12 255 330 1956 992 50 240 40 35 JKMXXXM 72 JKMXXXM 72 I JKMXXXM 72 J JKMXXXM 72B 5 inch Mono 6 12 160 215 1580 808 50 200 40 35 JKMXXXM 96 JKMXXXM 96 I JKMXXXM 96 J JKMXXXM 96B 5 inch Mono 8 12 210 285 1575 1082 50 260 40 35 JKMXXX...

Page 23: ... 215 275 1650 992 50 240 40 35 JKMXXXP 72L 6 inch Poly 6 12 255 330 1956 992 50 240 40 35 JKMxxxM 48 JKMxxxM 48 J 6 inch Mono 6 8 170 220 1324 992 50 240 40 35 JKMSxxxM 48 J JKMSxxxM 48 Plus 6 inch Mono 6 8 170 220 1324 992 50 240 40 35 JKMxxxP 48 JKMxxxPP 48 JKMxxxPP 48 J4 JKMxxxPP 48 J JKMxxxPP 48 Plus 6 inch Poly 6 8 170 225 1324 992 50 240 40 35 JKMSxxxP 48 J JKMSxxxP 48 J4 JKMSxxxP 48 Plus 6 ...

Page 24: ...voltage As reference the maximum number of modules in parallel M can be easily calculated by dividing the maximum rated current indicated in the electrical specification below by Isc value of the module and then plus 1 Any more please always take into consideration the variation of the current under different temperatures the Isc of the modules will be rise when the temperature goes up For example...

Page 25: ...igure 8 The graph of Grounding f Follow the requirements of applicable local and national electrical codes g These modules contain factory installed bypass diode if these modules are incorrectly connected to each other the bypass diodes cable or junction box may be damaged h The cable of the junction box is defined as L as showed below For Jinko standard module L is 900 1200mm and for customized m...

Page 26: ...re damaged during the installation or transportation f Whether there is burning vestige on the backsheet g Check fixing screws and mounting brackets are tight adjust and tighten as necessary 4 2 Cleaning a A built up of dust or dirt on the module s front face will result in a decreased energy output Clean the panel s preferably once per annum if possible depend on site conditions using a soft clot...

Page 27: ...cal leakage to ground 5 Electrical specification The module electrical rating are measured under Standard Test Conditions which are 1000W m2 irradiance with AM 1 5 spectrum and 25 deg 77 F ambient temperature The module might produce more or less voltage or current than rating value in uncertainty condition Accordingly the values of ISC and VOC marked on this module should be multiplied by a facto...

Page 28: ...ty is assumed by Jinko for any infringement of patents or other rights of third parties which may result from use of the PV product NO license is granted by implication or otherwise under any patent or patent rights The information in this manual is based on Jinko s knowledge and experience and is believed to be reliable but such information including product specification without limitations and ...

Page 29: ... com After sales cs jinkosolar com Global Sales Marketing Center No 1 Jinko Road Shangrao Economic Development Zone Jiangxi Province China 334100 Tel 86 793 858 8188 Fax 86 793 846 1152 Jiangxi Manufacture Base No 58 Yuanxi Road Haining Yuanhua Industrial Park Zhejiang Province China 314416 Tel 86 573 8798 5678 Fax 86 573 8787 1070 Zhejiang Manufacture Base ...

Reviews: