JetWeb
29
Jetter AG
5.4.4
Register Description
Register 1m100: Status Register
Each status register bit has got its specific meaning. This is a read-only register.
Bit Number
Status
Comment
0
0
1
The buffer configuration is invalid.
The buffer configuration is correct.
1
0
1
A station address has not been defined
yet.
The set station address is valid.
2
0
1
The PROFIBUS controller has not been
configured yet / it has not been configured
correctly.
Initialization has been successful.
3
0
1
The module has not been configured by
the PROFIBUS master yet.
The module is in the data exchange state,
i.e. communication with the master has
been established successfully.
4
1
The PROFIBUS master has sent a "read
data block" request.
5
1
The PROFIBUS master has sent a "write
data block" request.
6
1
Acyclic busy bit: Acyclic data are
exchanged between the module and the
PROFIBUS master; the acyclic data
cannot be accessed at the moment.
7
1
Acyclic error bit: Although bit 6 had been
set, an acyclic data range has been
accessed.
13
1
Busy bit: This bit indicates that the latest
action has not been completed by the
module yet. After reset, this bit will be set.
At the end of the initialization phase, it will
be reset again. The same applies to
command 5.
After writing the station address, this bit will
remain set, until the PROFIBUS controller
has been initialized completely.
0
no error
Summary of Contents for JetWeb JX2-PR0FI1
Page 1: ...Article 608 641 01 November 2002 Printed in Germany ...
Page 4: ...JX2 PROFI1 Table of Contents Jetter AG 4 ...
Page 13: ...1 Safety Instructions JetWeb 13 Jetter AG ...
Page 15: ...JetWeb 15 Jetter AG Fig 3 Side View JX2 PROFI1 Fig 4 Top View JX2 PROFI1 ...
Page 19: ...JetWeb 19 Jetter AG ...
Page 21: ...JetWeb 21 Jetter AG ...
Page 23: ...JetWeb 23 Jetter AG 5 3 Features ...
Page 43: ...JetWeb 43 Jetter AG ...
Page 45: ...JetWeb Jetter AG 45 ...
Page 62: ...JX2 PROFI1 8 Sample Programs 62 Jetter AG ...
Page 63: ...JX2 PROFI1 Appendices Jetter AG 63 Appendices ...