Jetmaster QUADRO Installation Instructions Download Page 5

1.ODQ.3E

A

B

C

Dimensions in mm

If the appliance is installed at floor level the appliance and 

hearth must be installed as outlined in AS/NZS 2918:2001.  

C1.3.3.3.(c).  The base of the firebox and floor protector must     

* A minimum 75mm thickness refers only to Hebel Block.

Minimum 100mm thickness required if poured concrete.

M

INIMUM FLOOR PROTECTOR

Head Office & Showroom

12 Tawari St, Mt Eden, Auckland

 

Ph: 09 623 699

0

thefireplace.co.nz

Floor Protecter

A

B

C

 

Raised 500mm

1400

800

*

75

Floor Level

1400

1000

75

Table 

2

G

ENERAL MAINTENANCE

When the fire is not in use, ensure the stainless steel cover is fitted at all times. This will assist in protecting the

 

firebox.

DO NOT

 attach the cover when the fire is in use.

This fire is 

NOT

 warranted against rust.

A seasonal touch-up is recommended. Simply remove surface rust with some steel wool and repaint using Black VHT

 

paint

(available from your nearest showroom)

. Please ensure all areas around the firebox are protected when re-painting.