Jetmaster Mark 2 Gas Coal Installation Instructions Manual Download Page 2

Jetmaster gas coal / pebble burners are fuel effect
appliances intended for use in a fireplace suitable for the
burning of wood. It is recommended that the Jetmaster
gas log be placed in a properly installed Jetmaster
Convector firebox in order to ensure an adequate
draught and greater efficiency. The Jetmaster open fire
is an approved open fire to burn wood. The following
size fireboxes are available for the Type 1 Burner to be
inserted into. The firebox can be installed into an
existing fireplace subject to the chimney being the
appropriate size and in sound condition. The firebox
can also be installed from new with a gather and a flue.

( D I M E N S I O N S   I N   M I L L I M E T E R S )

A

A1

B

C

D

E

500

500

700

350

650

200

200

600

670

700

350

650

200

200

600 LOW

670

700

350

600

200

200

700SH

770

800

350

650

200

200

700SH LOW

770

800

350

600

200

200

700D

770

800

400

700

225

200

IMPORTANT: Installation of this appliance should only be
carried out by an authorised person in accordance with the
manufacturers instructions. All relevant codes and regulations
laid down by the gas supply authorities, uniform building
regulations and the requirements of local municipal authorities
must be observed. The installation should comply with
AS5601/AG601 Clauses 5.12.13.2 and 5.12.13.5.

Model Type  1: Decorative
Gas Coal / Pebble Fire 

500/600/700 MARK 2 GAS COAL / PEBBLE BURNER

DATA PLATE: Refer to date place for information in
respect of gas pressure, consumption and gas type, Natural
or LPG.The data place is located to the side of the grate.

Location Requirements

1. The fireplace construction must be non-combustible
and in accordance with the current Building Regulations
for chimney and fireplace intended for solid fuel use.

2. The flue and/or chimney should be tested and
proven to have an adequate updraft which shall be
sufficient to remove all waste products of combustion.
A minimum cross-sectional area of 40,000 sq mm is
required with a minimum chimney flue height of 3.6
meters.The installer must satisfy himself that the fireplace
is functioning properly and a smoke test is recommended.
When using a Jetmaster firebox the appropriate diameter
flue for the model fireplace should be used.

3. The appliance must comply with AG601 Gas
Installation Code.

4. In cases where a twin walled metal flue is used and
provided such flue shall comply with the clearances
specified in AS2918 or manufacturers instructions in
respect of clearance to combustibles.

5. In cases where a metal is used, such flue shall
comply with the standards relating to grade, quality and
thickness as are current.

6. An approved flue cowl with a minimum cross-sections
of 40,000sq mm shall be affixed to the top of the flue or
chimney.

7. The installer must remove or fix in an open position
any damper which may be affixed to or contained in any
fireplace.

8. It should be noted that the Code AS2286 (space
heating appliances-secondary guards) requires a dress
guard to be affixed to the appliance or fireplace.

9. Ventilation. An opening to outside with a minimum
free ventilation area of 400sq cm shall be provided for
each decorative gas log fire.

NOTE: The chimney in which the appliance is installed
is not to be considered as a ventilation opening.

10. The appliance shall be installed into a fireplace with a
minimum opening of 600mm width and 217mm depth
and shall be no greater than 10650mm width and
400mm depth.

11. Combustible materials to be no closer than
100mm either side of fireplace opening and no closer
than 150mm above the opening. The firebox should
have a non combustible hearth in front of the firebox.

Installation instructions Jetmaster Mark 2 Gas Coal / Pebble

Electricity
Supply

Gas
Supply

Fan
Switch

Summary of Contents for Mark 2 Gas Coal

Page 1: ...Installation instructions Jetmaster Mark 2 Gas Coal Pebble with Millivolt Control...

Page 2: ...imney should be tested and proven to have an adequate updraft which shall be sufficient to remove all waste products of combustion A minimum cross sectional area of 40 000 sq mm is required with a min...

Page 3: ...ol knob on right hand side of valve Depress and turn control knob FIG 1 to the PILOT position FIG 4 Depress the control button and ignite with piezo ignitor FIG 2 whilst keeping control knob firmly de...

Page 4: ...HOW TO ADJUST GAS PRESSURE...

Page 5: ...of coals in a honeycomb pattern to form an elongated pyramid Lay the coals pebbles so that some irregularity to the pile through which the flames may lick is created Your aim is to build windows into...

Page 6: ...which has been designed to ensure a proper draw and to eliminate emission spillage 2 Initially the Jetmaster coal pebble fire may burn with a slightly blue flame After approximately 20 minutes the fir...

Page 7: ...existing masonry fireplace or equivalent approved open fireplace The gas fire consists of an outer decorative grate which houses a mild steel burner tray A front plate is provided to cover controls CA...

Page 8: ...s welded onto a 4 5mm guage mild steel frame to provide the appearance of a solid fuel basket grate A 1 6mm guage folded mild steel tray is located within the basket grate It is welded to the back of...

Page 9: ...located under the burner tray Burner A folded mild steel tray with deflector plate A cast iron venturi tapered mixing tube is welded to the base through which gas is introduced Pilot S I T Pilot asse...

Page 10: ...For LPG the appliance regulator requires removal Note pressures on data plate for natural and LP gas and adjust accordingly The test point is located on the SIT valve HEATING SYSTEM Vermiculite Is var...

Page 11: ...the safety magnet Millivolt systems utilise power from the thermo generator 7 After the pilot has been lit for approximately three minutes and only the thermo generator wires connected to the main ope...

Page 12: ...ure with main burner running see diagram Pilot adjustment screw not properly adjusted Refer to item 7 in the set up guide also see diagram Thermocouple or thermo generator not properly inserted into t...

Page 13: ...and TP If the voltage is above 110mV and the safety magnet does not hold replace the valve Pilot injector blocked Replace injector with a new injector of the exact size and type Pilot drops out Wrong...

Page 14: ...at wiring except substitute the words wall switch where the word thermostat appears in the instructions Excessive wire resistance Make certain that all mV connections are made using wire of the proper...

Page 15: ...Notes For further information contact Jetmaster Australia 10 Martin Avenue Arncliffe NSW 2205 T 02 9597 7222 F 02 9597 7622 E sales jetmaster com au W www jetmaster com au...

Reviews: