Jetmaster Mark 2 Gas Coal Installation Instructions Manual Download Page 14

 Defective 

thermostat 

or 

thermostat wiring. 

(A) With the pilot adjusted properly, 
(Set-up section, step#7), place a jumper 
wire between TPTH and TH. Take a mV 
reading across the TPTH and TP 
terminals on the valve. This closed 
circuit voltage should not fall below 
300mV. Record reading. 
(B) Remove jumper wire from the TPTH 
and TH connections, and reconnect the 
thermostat wires to the same terminals. 
Take the closed circuit voltage as 
described in the previous step. If the mV 
reading drops below 150mV, excessive 
resistance exists in the thermostat circuit, 
and must be isolated and eliminated. 

 

Defective wall switch 

Repeat the above troubleshooting items 
covered under “Defective thermostat or 
thermostat wiring”, except substitute the 
words “wall switch” where the word 
“thermostat” appears in the instructions. 

                                  Excessive wire                 

resistance 

Make certain that all mV connections are 
made using wire of the proper size. 

 

Valve wired wrong.          Thermo-generator leads must be 

connected to the TPTH and TP 
connections of the main operator. 
Thermostat wires must be connected to 
the TPTH, and TH terminals of the valve. 

Main burner             
lights in the 
PILOT position 

Main operator coil 
Defective 

Verify electrical resistance of main 
operator coil in the following manner. 
(A) Remove all wires from operator head.
(B)With an Ohm meter, measure 
electrical resistance between TPand TH 
terminals. If the resistance does not fall 
within specification, replace valve. 

 

Debris on seat of main 
valve. 

Replace valve. 

 

Main seat blown out as 
a result of exposing 
LPG gas valve to 
unregulated line 
pressure in excess of 
15PSI 

Replace valve. 

 

 

 

 

Summary of Contents for Mark 2 Gas Coal

Page 1: ...Installation instructions Jetmaster Mark 2 Gas Coal Pebble with Millivolt Control...

Page 2: ...imney should be tested and proven to have an adequate updraft which shall be sufficient to remove all waste products of combustion A minimum cross sectional area of 40 000 sq mm is required with a min...

Page 3: ...ol knob on right hand side of valve Depress and turn control knob FIG 1 to the PILOT position FIG 4 Depress the control button and ignite with piezo ignitor FIG 2 whilst keeping control knob firmly de...

Page 4: ...HOW TO ADJUST GAS PRESSURE...

Page 5: ...of coals in a honeycomb pattern to form an elongated pyramid Lay the coals pebbles so that some irregularity to the pile through which the flames may lick is created Your aim is to build windows into...

Page 6: ...which has been designed to ensure a proper draw and to eliminate emission spillage 2 Initially the Jetmaster coal pebble fire may burn with a slightly blue flame After approximately 20 minutes the fir...

Page 7: ...existing masonry fireplace or equivalent approved open fireplace The gas fire consists of an outer decorative grate which houses a mild steel burner tray A front plate is provided to cover controls CA...

Page 8: ...s welded onto a 4 5mm guage mild steel frame to provide the appearance of a solid fuel basket grate A 1 6mm guage folded mild steel tray is located within the basket grate It is welded to the back of...

Page 9: ...located under the burner tray Burner A folded mild steel tray with deflector plate A cast iron venturi tapered mixing tube is welded to the base through which gas is introduced Pilot S I T Pilot asse...

Page 10: ...For LPG the appliance regulator requires removal Note pressures on data plate for natural and LP gas and adjust accordingly The test point is located on the SIT valve HEATING SYSTEM Vermiculite Is var...

Page 11: ...the safety magnet Millivolt systems utilise power from the thermo generator 7 After the pilot has been lit for approximately three minutes and only the thermo generator wires connected to the main ope...

Page 12: ...ure with main burner running see diagram Pilot adjustment screw not properly adjusted Refer to item 7 in the set up guide also see diagram Thermocouple or thermo generator not properly inserted into t...

Page 13: ...and TP If the voltage is above 110mV and the safety magnet does not hold replace the valve Pilot injector blocked Replace injector with a new injector of the exact size and type Pilot drops out Wrong...

Page 14: ...at wiring except substitute the words wall switch where the word thermostat appears in the instructions Excessive wire resistance Make certain that all mV connections are made using wire of the proper...

Page 15: ...Notes For further information contact Jetmaster Australia 10 Martin Avenue Arncliffe NSW 2205 T 02 9597 7222 F 02 9597 7622 E sales jetmaster com au W www jetmaster com au...

Reviews: