background image

3

Tools and Parts

Gather the required tools and parts necessary for correct LP gas 
conversion.

Tools needed

Flat-blade screwdriver

³⁄₃₂

" (#0 [2.0 mm]) flat-blade screwdriver (screwdriver shaft 

must be a minimum of 2½" [6.4 cm] long)

Adjustable wrench

7.0 mm nut driver

7.0 mm wrench

Parts supplied

LP orifice package (W105990568)

Conversion label (W10590570)

High Altitude Conversion

To convert the cooktop for elevations above 6,560 ft (1999.5 m), 
order a High Altitude Conversion Kit.

Part Number W10593220 - LP high altitude

Part Number W10593221 - Natural gas high altitude

To order, see the “Assistance or Service” section of the Use and 
Care Guide.
IMPORTANT: Gas conversions from Natural gas to LP gas must 
be done by a qualified installer. Before proceeding with 
conversion, shut off the gas supply to the cooktop prior to 
disconnecting the electrical power.

Convert from Natural Gas to LP 

Gas

1. Turn manual shutoff valve to the closed position.

2. Unplug cooktop or disconnect power.

To Convert Gas Pressure Regulator

WARNING

This conversion kit shall be installed by a 
qualified service agency in accordance 
with the manufacturer's instructions and 
all applicable codes and requirements of 
the authority having jurisdiction. If the 
information in these instructions is not 
followed exactly, a fire, explosion or 
production of carbon monoxide may 
result causing property damage, personal 
injury or loss of life. The qualified service 
agency is responsible for the proper 
installation of this kit. The installation is 
not proper and complete until the 
operation of the converted appliance is 
checked as specified in the 
manufacturer's instructions supplied with 
this kit.

A. To cooktop
B. Shutoff valve (closed position)

C. Gas supply line

A. Access cap
B. Rear of cooktop

C. Gas pressure regulator
D. Gas flow

WARNING

Explosion Hazard

Use a new CSA International approved gas supply line.

Install a shut-off valve.

Securely tighten all gas connections.

If connected to LP, have a qualified person make sure 
gas pressure does not exceed 14" (36 cm) water 
column. 

Examples of a qualified person include: 

licensed heating personnel, 
authorized gas company personnel, and
authorized service personnel.

Failure to do so can result in death, explosion, or fire.

A

B

C

A

B

C

D

Summary of Contents for JGC7530B SERIES

Page 1: ...lled or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and tell you what can happen if the instructions are not followed Your safety and the safety of others are very important We have provided many important safety messages in this manual and on your appliance Always read and obey all safety messages...

Page 2: ...upplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Gas leaks cannot always be detected by smell Gas suppliers recommend that you use a gas detector approved by UL or CSA For more information contact your gas supplier If a gas leak is detected follow the What to do if you smell gas instructions In the State...

Page 3: ...version kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agenc...

Page 4: ... 14 WCP or lower The cooktop must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than psi 3 5 kPa 5 If they are installed remove the burner grates Use the following chart to match the correct gas orifice spud with the burner location and model being converted...

Page 5: ...e you have completed converting all of the cooktop burners test the cooktop for leaks by brushing on an approved noncorrosive leak detection solution If bubbles appear a leak is indicated Correct any leaks found 12 Plug in cooktop or reconnect power 13 Adjust valve according to Flame Height Adjustment section A Left rear burner B Center rear burner C Right rear burner D Right front burner E Center...

Page 6: ...o the NAT is showing on the bottom Snap the spring retainer back into the cap Reinstall the cap onto the regulator 4 If they are installed remove the burner grates Use the following chart to match the correct gas orifice spud with the burner location and model being converted Natural Gas Orifice Spud Chart Burner Models A To cooktop B Shutoff valve closed position C Gas supply line A Access cap B ...

Page 7: ...ith correct Natural gas orifice spud See the Natural Gas Orifice Spud Chart 7 Place LP gas orifice spuds in plastic parts bag for future use and keep with package containing literature 8 Replace burner bases and burner caps IMPORTANT Be sure that the electrode aligns with the notch in the burner base The igniter electrode is ceramic and could break during installation of the burner base 9 Open shu...

Page 8: ...ver each burner can be adjusted To Adjust The flame can be adjusted using the adjustment screws underneath the control knob 1 Set the burner flame to LO 2 Remove the control knob 3 Hold knob stem with a pair of pliers Use a 0 2 0 mm flat blade screwdriver to turn the screw located within the shaft of the control knob stem until the flame is the proper size For LP gas conversion Completely tighten ...

Page 9: ... ou d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil électroménager QUE FAIRE DANS LE CAS D UNE ODEUR DE GAZ Ne pas tenter d allumer un appareil Ne pas toucher à un commutateur électrique Ne pas utiliser le téléphone se trouvant sur les lieux Appeler immédiatement le fournisseur de gaz à partir du téléphone d un voisin Suivre ses instructions À défaut...

Page 10: ...alifié d une agence de service en conformité avec les instructions du fabricant et les prescriptions de tous les codes en vigueur et des autorités juridictionnelles Si les présentes instructions ne sont pas rigoureusement respectées ceci peut provoquer un incendie une explosion ou la génération de monoxyde de carbone provoquant des dommages corporels ou matériels ou même la mort La responsabilité ...

Page 11: ...du circuit d alimentation en gaz Essai de pression de circuit à lb po 14 de colonne d eau ou moins La table de cuisson devra être isolée des canalisations d alimentation en gaz par la fermeture du robinet d arrêt manuel individuel durant un essai de pression des canalisations d alimentation en gaz à une pression égale ou inférieure à lb po 3 5 kPa 5 Enlever les grilles de brûleur si elles sont ins...

Page 12: ...bien alignée avec l encoche de la base du brûleur L électrode d allumage est en céramique et peut se briser durant l installation de la base du brûleur 10 Ouvrir le robinet d arrêt de la canalisation de gaz Le robinet est ouvert lorsque la manette est parallèle à la canalisation de gaz A Brûleur arrière gauche B Brûleur central C Brûleur arrière droit D Brûleur avant droit E Brûleur avant gauche A...

Page 13: ...tyle 2 Le chapeau ne comporte pas de rainure on doit utiliser une clé pour la dépose Utiliser une clé pour enlever le chapeau de l ouverture d accès faire tourner le chapeau dans le sens antihoraire Dégager le ressort de retenue du chapeau en poussant contre le côté plat du ressort de retenue Examiner le ressort de retenue pour identifier la position LP ou NAT Retourner le ressort de retenue pour ...

Page 14: ...gicleur du brûleur Remplacer le gicleur par un gicleur pour gaz naturel de taille correcte Voir le Tableau de sélection des gicleurs pour gaz naturel Puissance thermique Empreinte A Taille 6 000 BTU 110 1 10 mm A Empreinte de la taille 9 000 BTU 132 1 32 mm 12 000 BTU 155 1 55 mm 15 000 BTU 170 1 70 mm 18 000 BTU 193 1 93 mm Modèle n Avant droit Ar rière droit Central central avant Cen tral arrièr...

Page 15: ...sur le bouton de commande et le fait tourner jusqu à la position HI réglage élevé le système génère des étincelles pour l inflammation du gaz sur le brûleur Ces étincelles se produisent jusqu à l apparition d une flamme Contrôle du fonctionnement des brûleurs de la table de cuisson 1 Appuyer sur le bouton de commande et le tourner à la position HI réglage élevé La flamme doit apparaître sur le brû...

Page 16: ...r la vis dans le sens antihoraire pour augmenter la hauteur de flamme 4 Réinstaller le bouton de commande 5 Répéter les étapes 1 à 5 pour chaque brûleur 6 Contrôler la taille et la forme des flammes sur chaque brûleur Pour le réglage au débit thermique faible on doit observer des flammes stables bleues d environ 0 64 cm de haut 7 Compléter l étiquette de conversion fixer l étiquette sur le fond de...

Reviews: