Operation
Instruments
48
9831/0650-3
48
•
Activation of an auxiliary input that has been configured to remote startActivation of the inbuilt exercise
scheduler.
Starting Sequence
To allow for `false' start requests, the start delay timer begins.
Should all start requests be removed during the start delay timer, the unit returns to a stand-by state.
If a start request is still present at the end of the start delay timer, the fuel relay is energised and the engine
is cranked.
If the unit has been configured for CAN, compatible ECU's receive the start command via CAN and transmit
the engine speed to the DSE controller.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest
duration after which the next start attempt is made. Should this sequence continue beyond the set number of
attempts, the start sequence is terminated and the display shows Fail to Start.
Engine Running
Once the engine is running and all starting timers have expired, the animated `Engine Running' icon is
displayed. The generator is placed on load if configured to do so.
The load transfer signal remains inactive until the oil pressure has risen. This prevents excessive wear on the
engine.
If all start requests are removed, the stopping sequence will begin.
Stopping Sequence
The return delay timer operates to ensure that the starting request has been permanently removed and isn't
just a short term removal. Should another start request be made during the cooling down period, the set returns
on load.
If there are no starting requests at the end of the return delay timer, the load is removed from the generator
to the mains supply and the cooling timer is initiated.
The cooling timer allows the set to run off load and cool sufficiently before being stopped. This is particularly
important where turbo chargers are fitted to the engine.
After the cooling timer has expired, the set is stopped.
Manual/Start Mode
If a digital input configured to panel lock is active, changing module modes is not be possible. Viewing the
instruments and event logs is NOT affected by panel lock.
Waiting In Manual Mode
To begin the starting sequence, press the Manual/Start Mode button. If `protected start' is disabled, the start
sequence begins immediately.
If `Protected Start' is enabled, the waiting in MANUAL mode icon is displayed and the LED above the MANUAL/
START mode button flashes to indicate `Waiting in MANUAL mode'.The MANUAL/START mode button must
be pressed once more to begin the start sequence.
Starting Sequence
There is no start delay in this mode of operation.
The fuel relay is energised and the engine is cranked.
Summary of Contents for G20
Page 3: ...9831 0650 3 Notes...
Page 7: ...Notes iv 9831 0650 3 iv...
Page 65: ...Attachments Working with Attachments 58 9831 0650 3 58 Fork Pockets Figure 44 A A Fork pocket...
Page 81: ...Attachments Working with Attachments 74 9831 0650 3 74 Socket Box Figure 64 A A Socket box...
Page 87: ...Notes 80 9831 0650 3 80...
Page 147: ...Notes 140 9831 0650 3 140...
Page 156: ...Technical Data Electrical System 149 9831 0650 3 149 Figure 99 335 F5093 3 sheet 2 of 6...
Page 157: ...Technical Data Electrical System 150 9831 0650 3 150 Figure 100 335 F5093 3 sheet 3 of 6...
Page 158: ...Technical Data Electrical System 151 9831 0650 3 151 Figure 101 335 F5093 3 sheet 4 of 6...
Page 159: ...Technical Data Electrical System 152 9831 0650 3 152 Figure 102 335 F5093 3 sheet 5 of 6...
Page 160: ...Technical Data Electrical System 153 9831 0650 3 153 Figure 103 335 F5093 3 sheet 6 of 6...
Page 161: ...Technical Data Electrical System 154 9831 0650 3 154 Figure 104 336 E4738 B sheet 1 of 7...
Page 162: ...Technical Data Electrical System 155 9831 0650 3 155 Figure 105 336 E4738 B sheet 2 of 7...
Page 163: ...Technical Data Electrical System 156 9831 0650 3 156 Figure 106 336 E4738 B sheet 3 of 7...
Page 164: ...Technical Data Electrical System 157 9831 0650 3 157 Figure 107 336 E4738 B sheet 4 of 7...
Page 165: ...Technical Data Electrical System 158 9831 0650 3 158 Figure 108 336 E4738 B sheet 5 of 7...
Page 166: ...Technical Data Electrical System 159 9831 0650 3 159 Figure 109 336 E4738 B sheet 6 of 7...
Page 167: ...Technical Data Electrical System 160 9831 0650 3 160 Figure 110 336 E4738 B sheet 7 of 7...
Page 168: ...Technical Data Electrical System 161 9831 0650 3 161 Figure 111 336 E5832 1 sheet 1 of 7...
Page 169: ...Technical Data Electrical System 162 9831 0650 3 162 Figure 112 336 E5832 1 sheet 2 of 7...
Page 170: ...Technical Data Electrical System 163 9831 0650 3 163 Figure 113 336 E5832 1 sheet 3 of 7...
Page 171: ...Technical Data Electrical System 164 9831 0650 3 164 Figure 114 336 E5832 1 sheet 4 of 7...
Page 172: ...Technical Data Electrical System 165 9831 0650 3 165 Figure 115 336 E5832 1 sheet 5 of 7...
Page 173: ...Technical Data Electrical System 166 9831 0650 3 166 Figure 116 336 E5832 1 sheet 6 of 7...
Page 174: ...Technical Data Electrical System 167 9831 0650 3 167 Figure 117 336 E5832 1 sheet 7 of 7...