JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS
Unitronics
5
Inputs
1.
All the products comprise I0-I5; these digital inputs are arranged in a single group. Via wiring,
the entire group may be set to either pnp or npn.
2.
The following information concerns JZ20-T10/JZ20-J-T10 and JZ20-T18/JZ20-J-T18:
I0 and I1 can function as high-speed counters or as normal digital inputs.
3.
The following information concerns JZ20-J-T20HS:
▪
I0, I1, and I4 can function as high-speed counters, as part of a shaft-encoder, or as
normal digital inputs.
▪
I2, I3, and I5 can function as either counter reset, as part of a shaft-encoder, or as
normal digital inputs.
▪
If I0, I1, I4 are set as high-speed counters (without reset), I2, I3, I5 can function as normal
digital inputs.
4.
The following information concerns JZ20-T18/JZ20-J-T18 and JZ20-J-T20HS in addition to I0-
I5, these comprise the following:
I6 and I7 may be wired as either digital or analog inputs. These may be wired as either:
▪
npn digital inputs
▪
pnp digital inputs
▪
analog (voltage) inputs
In addition, one input may be wired as a pnp input, while the other is wired as an analog input.
Note that if one input is wired as an npn input, the other may not be wired as an analog input.
5.
The following information concerns JZ20-T18/JZ20-J-T18 and JZ20-J-T20HS:
AN0 and AN1 are analog (current) inputs.
Digital Inputs, Controller’s Power Supply
JZ20-T10/JZ20-J-T10
Input wiring (I0-I5), npn (sink)
Input wiring (I0-I5), pnp (source)