page 3
www.jayline.co.nz
APRIL 2018
• Flue exiting more than 3 metres from the ridgeline must terminate no less than 1 metre above the
roof penetration (see diagram 1 below).
• Where the top of the flue pipe is more than 2 metres above its highest fixing point, it must be stayed
against high winds.
9. Drill and fix flue system into flue spigot with stainless steel self-tapping screws.
10. Drill and secure the appliance to the floor protector using the two holes in the rear legs of the
appliance.
11. Our fires have been tested in a standard 4.2m flue installation. If your installation requires additional
flue lengths (i.e. 2 storey homes) its important to note that each additional length will create more
draw. Therefore for best performance, extended burn time and to preserve the components in your
fire, we recommend moving the air slide to low (once the fire is established)
12. Extending the flue can improve fire draw in some cases. If planning to use more than 2 additional
lengths of flue, please contact the manufacturer for best performance and technical assistance.
FITTING SEISMIC RESTRAINT
The Floor Protector must be mechanically fixed to the floor by bolting or screwing.
Note:
Floor Protector
to be fixed by gluing when on a concrete floor that may have water pipes or electrical wires present. The
appliance can then be bolted to the floor protector with two 6mm x 50mm dynabolts.
BAFFLE
Before lighting your appliance for the first time, make sure the baffle is in the correct position being as
far to the rear as possible, and ensure all packing material has been removed.