Doc ref. :
332190D –
EN
28.04.2014
Page 20 / 49
5.4.5 Wiring of a wired safety shutdown device.
The external safety shutdown devices (wired safety shutdown palmswitches ...) must be wired to the « Emergency
stop » inputs. To do so, you must use external safety shutdown devices comprising two redundant contacts. One of
the contacts must be connected across terminals S11-S12, and the other across S13-S14 (fig 2).
Note :
If this wired emergency stop function is not used,
you must wire
two jumpers across S11-S12 and S13-
S14.
5.4.6 Wiring of a machine area access authorisation request function.
- The enabling handle must be configured in the « 4 control buttons » operating mode.
- Output 27 (associated to button B1) or output 37 (associated to button B2) must be connected to input S34 to
ensure the machine area access authorisation request.
- Using the Dialog RSP PC software, you can load a pictogram suited to this application on the enabling handle
screen.
See pictograms available in Dialog RSP PC software library.
Note :
The wiring diagram shown below is designed for an area access request using button B1 (output 27)
Note :
The wiring is the same for an access by gate or an access protected by a safety light barrier .