background image

 

 
 
 
 
 

BOILER INTRODUCTION 

 

When introducing the boiler, it should be ensured that the system is filled with water and air is 
removed. The tightness of the piping should also be checked to avoid leaking damage to the 
system.  
 
The  manometer  must  be  observed  in  conjunction  with  the  usage  of  the  apparata.  In  coated 
expansion container systems the pressure should be above 0,5 bar (but below 1,5 bar when 
hot). Furthermore, check that the opening pressure of the safety valve is 1,5 bar. 

 
Burner choice 

 

All modern oil burners that are equipped with pre-heating and designed for 1.4-2.3 kg of oil/h, 
are suitable. These values are reached at 0,5 US gall/h with a 60° nozzle when oil pressure is 
6-14 bar.  

 

 

Burner installation 

 

 

An  installation  and  usage  manual  is  delivered  with  the  boiler  and  it  should  be  followed  at  all   
times.

 

 

Burner adjustment 

 

The  exit  gas  values,  required  for  burner  adjustment, are  measured  from  the  analysis  hole  in 
the duct connection piece.  The analysis is taken on the first time of usage and  the burner is 
adjusted accordingly. Thus unnecessary smutting is avoided if ventilation is not sufficient. The 
final adjustment is performed when boiler water r75 °C. 

 

In  oil  usage  the  adjusted  values  are  appropriate  when  the  smut  value  is  0-1  in  the  bachrah 
scale, O

% 3,5…4,5, CO

> 12 % and CO < 30 ppm. 

 

   Once the burner is correctly adjusted, the boiler needs sweeping approx. once a year! 

 
NOTICE! Incorrect burner adjustment can damage the burner hatch and exit gas controls.   
 
In normal boilers the exit gas temperature is approx. 140 °C. If this temperature is too low for 
the  chimney  material,  the  temperature  can  be  raised  by  removing  some  of  the  hindermost 
plates  of  the  exit  gas  controls  (nr.  4,  figure  3)  in  the  convection  part.  Removing  one  plate  is 
equivalent to approx. a 10 °C rise in exit gas temp erature. 
  

Wood part gear 
 

damper (nr. 7, figure 1) according to instructions. 

 
 
 
 
 
 
 

Suitable burners include e.g. Oilon Junior Pro LJ 10, (LF-1) and Riello B10.  

The burner can only be installed by a person qualified for the job.  

The  traction  control  is  installed  in  the  traction  control connection   (nr.  5,  figure  1)  and  the 

WWW.JASPI.UK

Summary of Contents for TRIPLEX

Page 1: ...USER MANUAL INSTALLATION AND J A S P I K N O W S H E A T I N G Multifuel boilers JASPI TRIPLEX WWW JASPI UK...

Page 2: ...Expansion Container Systems 3 Driving Water System 3 Heating System 4 Electricity Connections 4 BOILER INTRODUCTION 5 Burner choice 5 Burner installation 5 Burner adjustment 5 Wood side equipment inst...

Page 3: ...one in accordance with good engineering practices In Raisio Finland 5 6 2002 Raimo Aaltonen General Manager powerful hot water coil flange chimney extension liner Recommend chimney brick 250 cm steel...

Page 4: ...o the amount of water The safety valve is installed unclamped to the boiler s boiling aggregate The valve s exhaust pipe should not be reduced from it s nominal size and it should be directed thus tha...

Page 5: ...electrician The connections are made according to the following scheme S2 1 c c N L1 1 2 3 IMIT 2 TG 1 THERMOSTAT S1 FEED FROM BURNER SWITC MAX 240V 10A CUT OFF THERMOSTAT BURNER BURNER BURNER X1 4mm...

Page 6: ...sis is taken on the first time of usage and the burner is adjusted accordingly Thus unnecessary smutting is avoided if ventilation is not sufficient The final adjustment is performed when boiler water...

Page 7: ...h nr 3 figure 3 and cleansing hatch nr 1 figure 3 are opened and the exit gas control found behind the latter hatch is removed nr 4 figure 3 The chambers are cleansed by removing and extracting the sm...

Page 8: ...and tightly so that the billets touch the rear wall of the furnace Then put a new charge of billets onto remaining coals When coals burn down close the air dampers in order to avoid heat losses from t...

Page 9: ...the boiler water temperature has remained unchanged for 45 minutes after the beginning of combustion Secondary air is adjusted by changing the clearance of the air damper on the maintenance hole lower...

Page 10: ...sed temperature limiter can be retuned by pressing the temperature limiter nr 21 24 figure 1 button strongly pressing with a narrow tipped stick on the control panel WARRANTY Boiler warranty is two ye...

Reviews: