63
UMG 96RM-EL
Errors
Error description
EEE
810
A failure has been detected in the configu-
ration.
The configuration will be reset and restored
to default values (factory setting) when that
failure was displayed.
Device has to be re-configured where
required.
Errors
Error description
EEE
500
The mains frequency could not be deter-
mined.
Possible causes:
The voltage at L1 is too small.
The mains frequency does not range
between 45 and 65Hz.
Remedy:
Check the mains frequency.
Select fixed frequency on the device.
Fig. Warning mes-
sage with number 500
(mains frequency)
Warnings
Warnings are minor er-
rors that can be acknow-
ledged by buttons 1 or
2. The measured values
continue to be retrieved
and displayed. This error
is displayed after each
voltage return.
Major errors
When a major error occurs, the device must be sent
to the manufacturer's service center for inspection
and adjustment.
Errors
Error description
EEE
910
Error while reading the calibration.
Errors
Error description
0x01
EEPROM does not respond.
0x02
Address overrange.
0x04
Checksum error.
0x08
Error in the internal I2C bus.
Internal causes:
The UMG 96RM-EL sometimes determines the cause
of a major internal error with the following error code.
Summary of Contents for UMG 96 RM-EL
Page 13: ...13 UMG 96RM EL...
Page 29: ...29 UMG 96RM EL...
Page 80: ...80 UMG 96RM EL Dimensional drawings All dimensions in mm Rear view Bottom view 97 91 5...
Page 81: ...81 UMG 96RM EL Side view 92 0 8 92 0 8 Cutout dimensions 96 max 6 42 91 5 104...
Page 87: ...87 UMG 96RM EL...
Page 89: ...89 UMG 96RM EL...