24
UMG 804 voltage connection wiring
The UMG 804 must be connected to
the voltage source being monitored.
The Voltage input terminal serves as
the both power source to the monitor
and voltage sensing. All phases that
are to be monitored must be connect-
ed. The current consumption of the
monitor will not exceed 0.2 A at any
operational voltage.
The monitor is fused internally but
additional fusing may be required
per local and national codes
.
Inline fuses are available from Janitza.
VOLTAGE INPUT CONNECTOR
SOLID WIRE: 24-12 AWG / 0.205-3.31 MM²
STRANDED WIRE: 24-12 AWG / 0.205-3.31 MM²
TORQUE: 5.0 Lb-In / 0.56 Nm
G/E N L3 L2 L1
N
N
G/E
Recomended Overcurrent Protection:
0.5 A @ 300 VAC
L2 L3
VOLTAGE INPUT
L1
L2
L3
L1
•
Voltage input 230 V AC
Recommended overcurrent protection:
1.0 A @ 300 V AC
Acceptable wiring confi gurations
The monitor may be connected to any
wiring confi guration shown in fi gure
below except for corner grounded delta
circuits.
3-wire (ungrounded)
Delta
Corner-grounded
Delta - NOT ALLOWED
4-Wire Wye
3-Wire
Phase-Phase
2-Wire
Phase-Phase
120/240V
High-Leg Delta
L3
L3
L3
L3
X
L1
L2
L1
L2
L1
L2
L1
L2
L1
N
N
N
N
2-Wire
Single-Phase
L1
N
L2
L1
NOTE
Devices that can be operated with
DC voltage are protected against
polarity reversal
Summary of Contents for UMG 804