UMG 508
4
UMG 508
5
General
General
Type
Size
Minimum Maximum
char
8
bit
0 255
byte
8
bit
-128
127
short
16
bit
-2
15
2
15
-1
int
32
bit
-2
31
2
31
-1
uint
32
bit
0 2
32
-1
long64
64 bit
-2
63
2
63
-1
float
32 bit
IEEE 754
IEEE 754
double
64 bit
IEEE 754
IEEE 754
Number formats
Transfer parameters
The UMG508 supports the following transfer parameters:
Baud rate
: 9.6kbps, 19.2kbps, 38.4kbps, 57.6kbps, 115.2 kbps and 921.6 kbps
Data bits
: 8
Parity
:
none
Stop bits (UMG508)
: 2
Stop bits external
: 1 or 2
Byte sequence
The data in the modbus address list can be called up in the
•
Big-Endian (high-Byte before low-Byte) and in the
•
Little-Endian (low-byte before high-byte)
format.
The addresses described in this address list supply the data in the „Big-Endian“ format.
If you require the data in the „Little-Endian“ format, you must add the value 32768 to the address.
Update rate
The modbus register addresses are updated every 200ms.
Symbols and definitions
N
Total number of sample points per period
(For example, in a period of 20 ms)
k
Sample value or number of samples per period
( 0 <= k < N)
p
Number or identification of the phase conductor
(p = 1, 2 oder 3)
i
pk
Sample value k of the current of the phase conductor p
u
pNk
Sample value k of the neutral voltage of the phase
conductor p
P
p
Real power of the phase conductor p
Summary of Contents for UMG 508
Page 29: ...UMG 508 29 Modbus address list...