www.janitza.com
25
800-CON Modules
Transport and storage
The following specifications apply for devices transported and stored in the original packaging.
Free fall
1 m (39.37 in)
Temperature
K55: -25° C (-13 °F) to +70° C (158 °F)
Relative humidity
5 to 95% at 25 °C (77 °F), no condensation
Interface
JanBus (proprietary)
NOTE!
To connect the transfer modules, use a stranded twisted pair,
shielded data cable (cable connection 1:1)!
· Via bus connector to device and module series
· Via shield terminals between the transfer modules with stranded
twisted pair, shielded data cable (cable connection 1:1) -
see Sect. “5.2 Data cable for connecting the 800-CON transfer mod-
· The maximum bus length of the JanBus is
100 m
.
Terminal connection capacity
Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded
0.2 - 1.5 mm
2
, AWG 24-16
Wire ferrules (non-insulated)
0.2 - 1.5 mm
2
, AWG 26-16
Wire ferrules (insulated)
0.2 - 1 mm
2
, AWG 26-18
Tightening torque
0.2 - 0.25 Nm (1.77 - 2.21 lbf in)
Strip length
7 mm (0.2756 in)
General
Net weight (with plug-in terminals)
approx. 55 g (0.12 lb) - 1 device
Device dimensions
Approx. B = 18 mm (0.71 in), H = 90 mm (3.54 in),
D = 76 mm (2.99 in)
Mounting orientation
As desired
Fastening/mounting -
Suitable DIN rails - (35 mm / 1.38 in)
TS 35/7.5 according to EN 60715
TS 35/10
TS 35/15 x 1.5
Impact resistance
IK07 according to IEC 62262
Environmental conditions during operation
The device:
·Is for weather-protected and stationary use.
·Fulfills operating conditions according to DIN IEC 60721-3-3.
·Has protection class II according to IEC 60536 (VDE 0106, part 1), a ground wire connection is not required!
Rated temperature range
-10 °C (14 °F) to +55 °C (131 °F)
Relative humidity
5 to 95% at 25 °C (77 °F), no condensation
Pollution degree
2
Ventilation
No forced ventilation required.
Protection against foreign matter and water
IP20 according to EN60529
8. Technical data