background image

Page 32

10.4.6

Water Pressure Switch

If the meter shows at least a 220mV signal at test

point 11, move the black lead of the meter to the other
terminal on the water pressure switch (test point 12).

If there is no voltage, the pressure switch contacts

are open. This is almost always due to a water flow
deficiency, the most common one being a blocked
water filter or defective pump. However, sometimes it
is due to blockage of the copper siphon loop tube or
mis-adjustment of the switch. Investigate thoroughly,
referring to Section 7.5 on “Water Pressure Switch
Adjustment”. If there is no problem with the pool
system or pressure switch adjustment, replace the
pressure switch.

10.4.7

Temperature Control Circuit

The temperature control circuit consists of four

major components which must all be working cor-
rectly for the signal to be transmitted to the gas valve.
The four components are the ON/OFF toggle switch,
the variable temperature control (potentiometer), the
temperature sensor (thermistor) and the temperature
control board. Use the following procedure to check
each component for functionality.

Check the temperature control as a complete

circuit before checking each component individually.
With the red lead of the meter still at test point 1,
place the black lead of the meter on the TH terminal of
the temperature control circuit board (test point 16). If
the meter shows more than 220mV at the pressure
switch (test point 12) but not at test point 16, then one
of the components of the temperature control circuit is
faulty. Proceed with the following sections to test the
components.

10.4.7.1 ON/OFF Toggle Switch

Remove the temperature control panel from the

bezel on the front of the heater to gain access to the
switch. Be sure that the toggle switch is in the "ON"
position. Place the black lead of the meter on the
toggle switch terminal (test point 13) that is connected
to the pressure switch. Less than 220mV at this point
indicates that there is a problem with the black wire
that connects the pressure switch to the toggle switch.
If at least 220mV is detected at test point 13, move the
black meter lead to the other terminal on the toggle
switch (test point 14). A reading of less than 220mV
here indicates a faulty switch. If the reading is more
than 500mV, turn the switch "OFF" and then "ON"
again to be sure that the internal contacts are working
correctly. The volt meter reading should drop to zero
when the switch is "OFF" and return to at least 220mV
when the switch is placed back in the "ON" position.

10.4.7.2 Variable Temperature Control

The variable temperature control is a 0-10,000

ohm variable resistor. Set your ohmmeter to the 0-20K

.

P

M

E

T

R

E

T

A

W

R

E

D

A

E

H

N

I

)

C

°

(

F

°

E

C

N

A

T

S

I

S

E

R

.

X

O

R

P

P

A

S

M

H

O

F

O

S

'

0

0

0

1

N

I

)

s

m

h

O

k

(

)

0

1

(

0

5

9

.

9

1

)

5

1

(

0

6

3

.

5

1

)

1

2

(

0

7

9

.

1

1

)

6

2

(

0

8

3

.

9

)

2

3

(

0

9

3

.

7

)

8

3

(

0

0

1

8

.

5

range.  Remove the temperature control wires from
the control circuit board. Place one lead of the meter
on each of the wires (test points 18 & 19). With the
control set to MIN the meter should read near 10,000
ohms. Now turn the control to the MAX position. The
meter should read close to zero. If the meter shows an
open circuit, or readings outside of the range stated
above, replace the controller. If the control is working
correctly, reconnect the wires to the circuit board.

10.4.7.3 Temperature Sensor

The temperature sensor is a 0-20,000 ohm

thermistor. Set your ohmmeter to the 0-20K range.
The meter readings will depend on the temperature of
the water in the header. See the chart below for
approximate readings at various temperatures.

To test the temperature sensor, circulate water

through the heater for 5 minutes. Remove the tempera-
ture sensor wires from the temperature control board.
Place one lead of the meter on each wire of the
temperature sensor (test points 20 & 21). Record the
reading. Measure and record the water temperature of

the pool near the inlet of the filter system. Find the
temperature in the chart that is closest to your tem-
perature reading of the pool water. Compare your
ohmmeter reading to the resistance number in the
chart. Remember that this is an approximate reading
and numbers may vary. If your reading is close to the
numbers indicated in the chart then the temperature
sensor is working correctly. Reconnect the wires to the
circuit board. If your reading is vastly different or
outside of the ranges shown the temperature sensor
should be replaced.

10.4.7.4 Temperature Control Circuit

Board

With the red lead of the meter still at test point 1,

place the black lead of the meter on the TH/PP termi-
nal of the temperature control circuit board (test point
15). If there is more than 220mVDC at this point but
not at the TH terminal of the temperature control
circuit board (test point 16) as tested in section 10.4.7,
then the control circuit board is faulty. Replace the
board.

Summary of Contents for LG125

Page 1: ...H0264600A InstallationandOperationData WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasol...

Page 2: ...Generators and Sanitizing Chemicals 16 SECTION 6 Electrical Connection 6 1 Main Power 17 6 2 Bonding 17 6 3 Auxiliary Time Clock Wiring 17 SECTION 7 Operating Instructions 7 1 Normal Operation 17 7 2...

Page 3: ...Tubs recommended by the U S Consumer Product Safety Commission should be observed when using the spa WARNING The U S Consumer Product Safety Commission warns that elevated water temperature can be ha...

Page 4: ...specified on the back cover of thismanual Make all warranty claims to an authorized Jandy representative or directly to the factory Claims must include the heater serial number and model this informa...

Page 5: ...helter and Outdoor 2 MinimumClearanceFromCombustibleMaterial See Table 2 in Section 2 3 2 3 Gas Pipe Heater Gas Valve Connection Natural Gas 3 4 NPT LP Gas 3 4 NPT For diameter of gas line from meter...

Page 6: ...l application and installationprocedurescompletelybeforecontinuing theinstallation 2 2 Field Assembly The Lite2 heater is shipped from the factory with the top assembly in the low profile configuratio...

Page 7: ...locations where it can cause damage by water or condensate leakage If this is not possible provide a suitable drain pan to catch and divert any leakage The pan must not block natural flow of air aroun...

Page 8: ...ation Lite2 heaters can be installed in the low profile top configuration as received from the factory or with an optional high wind vent cap Locate the heater in an open unroofed area Do not install...

Page 9: ...0 91 m from vertical surfaces e g nearby buildings and walls The addition of a vent cap may be necessary In Florida it is required that the heater be se curely fastened to the equipment pad Use a siz...

Page 10: ...ly through an outside wall each opening should have a minimum free area of one square inch per 4 000 BTU h 1 2kW input of the total input rating of all appliances in the enclosed area If air is provid...

Page 11: ...be desirable to add a vent cap directly to the top of the heater In all cases vent pipes and caps must be of the same diameter as the exhaust outlet of the heater Approved vent caps may be obtained t...

Page 12: ...st be used be sure to carefully inspect the venting system to ensure that it is in good condition and continues to be appropriate for the Lite2 heater Replace any parts that are not in good and servic...

Page 13: ...ring the piping pressure test 7 If the gas supply pressure is less than required check for undersized pipe between the meter and the heater a restrictive fitting or an undersized gas meter Gas supply...

Page 14: ...your manom eter The pressure will be zero when the heater is not running When the heater is operating the manifold gas pressure should be 4 0 WC for natural gas heaters and 9 0 WC for LP gas heaters...

Page 15: ...header of the Lite2 comes equipped with an automatic flow control valve The automatic flow control valve maintains the proper flow through the heater at rates up to approximately 125 Gallons Per Minut...

Page 16: ...retainer bracket off the bulb flange and remove the bulb from the header see Figure 10 Pull pressure switch tube through the hole in the vestibule cover and into the vestibule controls compart ment t...

Page 17: ...tor are installed into the grooves on the front and rear combustion chamber heat shield panels Be sure the sheet metal panels are not pinching any wires 22 Attach the flue collector hold down clamps t...

Page 18: ...m any area occupied during servicing 5 7 Auxiliary Components Chlorinators Ozone Generators and Sanitizing Chemicals The Lite2 heater is manufactured with materials that are not compatible with high c...

Page 19: ...itch into the heater wires see Figure 16 1 Remove heater door 2 Remove the factory installed wire between terminals 1 and 2 on the terminal strip see Figure16 3 Connect the wires from the time clock a...

Page 20: ...Page 18 Figure 17 LG Connection Schematic Wiring Diagram...

Page 21: ...n the pool and that the surface level is above the skimmer or other inlet of the pool s filter system Confirm that pool water is flowing normally through the pool system and equipment With any new poo...

Page 22: ...F 21 C to 40 C Use an accurate pool thermometer to determine the best water temperature for your uses The Lite2 temperature control panel has a rocker switch to turn the heater on and off It also has...

Page 23: ...If pilot goes out repeat steps 1 through 6 TO SHUT OFF HEATER To shut off main burners turn gas control knob clockwise until it stops at PILOT For complete shut off press down slightly on knob while t...

Page 24: ...1 Set the control panel rocker switch to the OFF position see Figure 18 2 Set the Pool temperature control to the Max position 3 Turn filter pump on If a two speed pump is used make sure it is at high...

Page 25: ...y 13 If the temperature rise is within the correct range complete the procedure as follows a Turn heater OFF b Wait 3 minutes turn filter pump OFF c Remove thermometer and Pete s plug d Replace the dr...

Page 26: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy Table 7 Chemical Concentration Levels Test Recommended Level Free Chlorine or 1 0 to 3...

Page 27: ...er or page 21 of this manual 8 3 Inspection and Service The Lite2 LG heater is designed and constructed heater to provide long performance life when installed and operated properly under normal condit...

Page 28: ...bove burner surface see Figure 22 7 Inspect the gas and electronic controls including the following a High temperature limit switch b Water pressure switch c Automatic gas valve d Fusible Link e Tempe...

Page 29: ...equate C Replace with heater of higher input 7 Heater pounding A Inadequate water flow A Check temperature rise between inlet and outlet heater or knocking through heater piping See section 7 6 for re...

Page 30: ...that there is no block age of the vent or louvers which supply combustion air to the burners 10 2 Natural Draft Combustion System The Lite2 model LG pool heater has an atmo spheric combustion system T...

Page 31: ...eater If this current is broken at any time the gas valve is immedi ately shut off and the heater stops firing This voltage is also used to activate the gas valve s pilot coil which allows gas to flow...

Page 32: ...ction 7 3 check the voltage reading between the PP terminal on the gas valve test point 1 and the TH terminal on the gas valve test point 17 If the meter shows less than 220mVDC then there is a proble...

Page 33: ...n This is normally due to excessive water temperature which should be thoroughly investigated before replacement of limit switches Excessive water temperature may be caused by low water flow Water flo...

Page 34: ...he internal contacts are working correctly The volt meter reading should drop to zero when the switch is OFF and return to at least 220mV when the switch is placed back in the ON position 10 4 7 2 Var...

Page 35: ...Model LG Pool and Spa Heater Page 33 Figure 24 Test Point Identification Diagram...

Page 36: ...000 67 Flange Sleeve 2 All S0078200 68 Flange Bolt All F0031700 69 Flange Gasket 1 1 2 2 All S0078100 70 Rubber Grommet for Drain Plug All R0316300 71 Grommet Slitted Not Shown All S0071100 72 Brass C...

Page 37: ...125 S0000300 88 Heat Exchanger End Baffles 2 Required 125 400 R0332301 05 FIREBOX COMPONENTS 89 Complete Combustion Chamber Assy 125 400 R0316701 05 JACKET COMPONENTS 90 Door with Latch 125 400 R03436...

Page 38: ...R TRAY SEE NEXT PAGE FOR DETAIL 44 45 46 54 48 47 49 50 53 UNITED STATES 70 70 73 73 89 90 91 92 93 94 95 96 HEAT EXCHANGER SEE NEXT PAGE FOR DETAIL TEMPERATURE CONTR0L SEE NEXT PAGE FOR DETAIL 19 34...

Page 39: ...e 37 16 14 7 6 8 5 2 4 15 17 32 26 74 85 43 42 69 41 38 39 68 65 67 66 78 81 76 94 79 33 24 25 37 64 75 3 11 18 12 40 36 35 72 77 80 13 1 58 86 84 85 63 60 63 62 83 57 60 61 62 59 61 56 27 28 22 21 23...

Page 40: ...se of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing ch...

Reviews: