background image

Page 30

Note: Pump must be running during the
troubleshooting procedure.

These procedures require a voltmeter with a

minimum 0-1000 mVDC range. Figure 24 shows the
pilot generator and control circuits, and where to take
measurements. Location numbers and letters in circles
have been added, and will be referenced in the follow-
ing sections.

As stated at the beginning of this manual, some

of these procedures are hazardous. Only a qualified
service technician should service the heater.

During the trouble shooting procedure, the filter

pump must be on, the pilot on the heater must be lit,
the ON/OFF switch on the heater must be in the ON
position and the control knob must be turned to the
maximum setting so that there is a call for heat. We
recommend turning the gas valve control knob to the
"PILOT" position to prevent the main burners from
firing throughout the procedure. Before starting the
procedure, be sure that the pilot has been lit for at least
2 minutes and that the pilot generator (thermopile) is
positioned correctly within the flame of the pilot.

The pilot generator also operates the pilot coil of

the gas valve, allowing gas to flow to the pilot when
the gas valve knob is released from the pilot lighting
position (see Section 7.3 "Lighting and Shutdown
Procedures"). If the pilot will not stay lit when the gas
valve knob is released, check the pilot generator
output as described in Section 10.4.2 and replace if
necessary. If the pilot generator output is sufficient,
then check the gas valve as outlined in Section 10.4.1.

10.4.1

Gas Valve

The gas valve consists of two separate internal

operating valves. The main valve supplies gas to the
main burners for heater operation. The pilot valve
supplies gas to the pilot when the pilot generator
activates the pilot coil.

If the pilot will not stay lit after following the

lighting instructions in Section 7.3, check for the
following:

• Pilot generator output
• Correct type of gas supplied
• Correct gas supply pressure
• Air in the gas line
• Pilot coil wire connections clean and tight

If the pilot will not stay lit after checking the

items listed above, the pilot coil may be causing the
fault. Replace the gas valve.

If the main burners will not light after following

the lighting instructions in Section 7.3, check the
voltage reading between the PP terminal on the gas

valve (test point 1) and the TH terminal on the gas
valve (test point 17). If the meter shows less than
220mVDC then there is a problem with the pilot
generator, the sensors in the safety loop or the control
panel. Follow the trouble shooting procedure as
outlined in sections 10.4.2 through 10.4.7.

If the meter shows more than 220mVDC at test

point 17, then check for the following:

• Correct type of gas supplied
• Correct gas supply pressure
• Correct gas manifold pressure
• Correct orifice size
• Air in the gas line

If the main burners will not stay lit after check-

ing the items listed above, the gas valve may be
causing the fault. Replace the gas valve.

10.4.2  Pilot Generator

The pilot generator generates a 700-750mVDC

signal when heated by the pilot flame. When the pilot
generator is connected to the heater's control compo-
nents, there will be some voltage drop in the circuit so
that the measured voltage will be less than 750mVDC.
But the measured voltage should never be below
500mVDC when the ON/OFF switch is in the "OFF"
position or 220mVDC when the ON/OFF switch is in
the "ON" position.

With the pilot generator connected to the gas

valve and the ON/OFF switch in the OFF position,
place the red lead of the voltmeter on the PP terminal
(test point 1) of the gas valve. Place the black lead of
the meter on the PP/TH terminal (test point 2) of the
gas valve. The meter should show a minimum of
500mVDC. If the meter show less than 500mV, check
for partial shorts, loose or corroded connections or
partially broken wires between the pilot generator and
the gas valve.

If the wires and connections are sound, check the

pilot generator output. Disconnect the pilot generator
from the gas valve. The pilot will go out. Light the
pilot while pressing down on the gas valve control
knob. Continue holding the knob for at least one
minute. Immediately measure the voltage between the
two wires of the pilot generator. If the meter does not
show at least 700mV, replace the pilot generator.

10.4.3

Fusible Link

Check the voltage going to the safety circuit. Be

sure that the pilot generator is correctly wired to the
gas valve, the pilot is light and the control knob on the
gas valve is in the "PILOT" position. Leave the red
voltmeter lead in place at test point 1.  Touch the
black lead of the meter to the terminal of the fusible
link where the white wire from the gas valve is
connected (test point 3).

Summary of Contents for LG125

Page 1: ...H0264600A InstallationandOperationData WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasol...

Page 2: ...Generators and Sanitizing Chemicals 16 SECTION 6 Electrical Connection 6 1 Main Power 17 6 2 Bonding 17 6 3 Auxiliary Time Clock Wiring 17 SECTION 7 Operating Instructions 7 1 Normal Operation 17 7 2...

Page 3: ...Tubs recommended by the U S Consumer Product Safety Commission should be observed when using the spa WARNING The U S Consumer Product Safety Commission warns that elevated water temperature can be ha...

Page 4: ...specified on the back cover of thismanual Make all warranty claims to an authorized Jandy representative or directly to the factory Claims must include the heater serial number and model this informa...

Page 5: ...helter and Outdoor 2 MinimumClearanceFromCombustibleMaterial See Table 2 in Section 2 3 2 3 Gas Pipe Heater Gas Valve Connection Natural Gas 3 4 NPT LP Gas 3 4 NPT For diameter of gas line from meter...

Page 6: ...l application and installationprocedurescompletelybeforecontinuing theinstallation 2 2 Field Assembly The Lite2 heater is shipped from the factory with the top assembly in the low profile configuratio...

Page 7: ...locations where it can cause damage by water or condensate leakage If this is not possible provide a suitable drain pan to catch and divert any leakage The pan must not block natural flow of air aroun...

Page 8: ...ation Lite2 heaters can be installed in the low profile top configuration as received from the factory or with an optional high wind vent cap Locate the heater in an open unroofed area Do not install...

Page 9: ...0 91 m from vertical surfaces e g nearby buildings and walls The addition of a vent cap may be necessary In Florida it is required that the heater be se curely fastened to the equipment pad Use a siz...

Page 10: ...ly through an outside wall each opening should have a minimum free area of one square inch per 4 000 BTU h 1 2kW input of the total input rating of all appliances in the enclosed area If air is provid...

Page 11: ...be desirable to add a vent cap directly to the top of the heater In all cases vent pipes and caps must be of the same diameter as the exhaust outlet of the heater Approved vent caps may be obtained t...

Page 12: ...st be used be sure to carefully inspect the venting system to ensure that it is in good condition and continues to be appropriate for the Lite2 heater Replace any parts that are not in good and servic...

Page 13: ...ring the piping pressure test 7 If the gas supply pressure is less than required check for undersized pipe between the meter and the heater a restrictive fitting or an undersized gas meter Gas supply...

Page 14: ...your manom eter The pressure will be zero when the heater is not running When the heater is operating the manifold gas pressure should be 4 0 WC for natural gas heaters and 9 0 WC for LP gas heaters...

Page 15: ...header of the Lite2 comes equipped with an automatic flow control valve The automatic flow control valve maintains the proper flow through the heater at rates up to approximately 125 Gallons Per Minut...

Page 16: ...retainer bracket off the bulb flange and remove the bulb from the header see Figure 10 Pull pressure switch tube through the hole in the vestibule cover and into the vestibule controls compart ment t...

Page 17: ...tor are installed into the grooves on the front and rear combustion chamber heat shield panels Be sure the sheet metal panels are not pinching any wires 22 Attach the flue collector hold down clamps t...

Page 18: ...m any area occupied during servicing 5 7 Auxiliary Components Chlorinators Ozone Generators and Sanitizing Chemicals The Lite2 heater is manufactured with materials that are not compatible with high c...

Page 19: ...itch into the heater wires see Figure 16 1 Remove heater door 2 Remove the factory installed wire between terminals 1 and 2 on the terminal strip see Figure16 3 Connect the wires from the time clock a...

Page 20: ...Page 18 Figure 17 LG Connection Schematic Wiring Diagram...

Page 21: ...n the pool and that the surface level is above the skimmer or other inlet of the pool s filter system Confirm that pool water is flowing normally through the pool system and equipment With any new poo...

Page 22: ...F 21 C to 40 C Use an accurate pool thermometer to determine the best water temperature for your uses The Lite2 temperature control panel has a rocker switch to turn the heater on and off It also has...

Page 23: ...If pilot goes out repeat steps 1 through 6 TO SHUT OFF HEATER To shut off main burners turn gas control knob clockwise until it stops at PILOT For complete shut off press down slightly on knob while t...

Page 24: ...1 Set the control panel rocker switch to the OFF position see Figure 18 2 Set the Pool temperature control to the Max position 3 Turn filter pump on If a two speed pump is used make sure it is at high...

Page 25: ...y 13 If the temperature rise is within the correct range complete the procedure as follows a Turn heater OFF b Wait 3 minutes turn filter pump OFF c Remove thermometer and Pete s plug d Replace the dr...

Page 26: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy Table 7 Chemical Concentration Levels Test Recommended Level Free Chlorine or 1 0 to 3...

Page 27: ...er or page 21 of this manual 8 3 Inspection and Service The Lite2 LG heater is designed and constructed heater to provide long performance life when installed and operated properly under normal condit...

Page 28: ...bove burner surface see Figure 22 7 Inspect the gas and electronic controls including the following a High temperature limit switch b Water pressure switch c Automatic gas valve d Fusible Link e Tempe...

Page 29: ...equate C Replace with heater of higher input 7 Heater pounding A Inadequate water flow A Check temperature rise between inlet and outlet heater or knocking through heater piping See section 7 6 for re...

Page 30: ...that there is no block age of the vent or louvers which supply combustion air to the burners 10 2 Natural Draft Combustion System The Lite2 model LG pool heater has an atmo spheric combustion system T...

Page 31: ...eater If this current is broken at any time the gas valve is immedi ately shut off and the heater stops firing This voltage is also used to activate the gas valve s pilot coil which allows gas to flow...

Page 32: ...ction 7 3 check the voltage reading between the PP terminal on the gas valve test point 1 and the TH terminal on the gas valve test point 17 If the meter shows less than 220mVDC then there is a proble...

Page 33: ...n This is normally due to excessive water temperature which should be thoroughly investigated before replacement of limit switches Excessive water temperature may be caused by low water flow Water flo...

Page 34: ...he internal contacts are working correctly The volt meter reading should drop to zero when the switch is OFF and return to at least 220mV when the switch is placed back in the ON position 10 4 7 2 Var...

Page 35: ...Model LG Pool and Spa Heater Page 33 Figure 24 Test Point Identification Diagram...

Page 36: ...000 67 Flange Sleeve 2 All S0078200 68 Flange Bolt All F0031700 69 Flange Gasket 1 1 2 2 All S0078100 70 Rubber Grommet for Drain Plug All R0316300 71 Grommet Slitted Not Shown All S0071100 72 Brass C...

Page 37: ...125 S0000300 88 Heat Exchanger End Baffles 2 Required 125 400 R0332301 05 FIREBOX COMPONENTS 89 Complete Combustion Chamber Assy 125 400 R0316701 05 JACKET COMPONENTS 90 Door with Latch 125 400 R03436...

Page 38: ...R TRAY SEE NEXT PAGE FOR DETAIL 44 45 46 54 48 47 49 50 53 UNITED STATES 70 70 73 73 89 90 91 92 93 94 95 96 HEAT EXCHANGER SEE NEXT PAGE FOR DETAIL TEMPERATURE CONTR0L SEE NEXT PAGE FOR DETAIL 19 34...

Page 39: ...e 37 16 14 7 6 8 5 2 4 15 17 32 26 74 85 43 42 69 41 38 39 68 65 67 66 78 81 76 94 79 33 24 25 37 64 75 3 11 18 12 40 36 35 72 77 80 13 1 58 86 84 85 63 60 63 62 83 57 60 61 62 59 61 56 27 28 22 21 23...

Page 40: ...se of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing ch...

Reviews: