Page 12
4.2 DIP Switch Settings for Pool and Spa Combination
S1 DIP Switch #
OFF
ON
1
AUX1= any equipment
AUX1= Pool Cleaner
2
AUX2= any equipment
AUX2= Low Speed for a two-speed filter pump.
Filter pump circuit becomes High Speed.
3
NOT USED
NOT USED
4
Heater cool down operates.
Heater cool down disabled.
5
Normal operation
Factory adjustment- when this switch is on,
temperature delays are eliminated and solar
temperature is displayed.
Do not leave this switch in the ON position.
6
Separate Pool and Spa heater.
Sharing one heater for pool and spa.
7
No solar system installed. Air temperature
is displayed.
Changes air sensor to solar sensor. Air temperature
no longer displayed. Adjustable Freese Kit must be
added for freeze protection.
8
After thermostat setting has been
reached, heater will remain OFF for 3
minutes.
Heat Pump installed; after thermostat setting
has been reached, heater will remain OFF for 5
minutes.
6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
4 3 2 1 4 3 2 1
RESET
SERVICE
TIME OUT
FIL
TER PU
MP
AU
X 1
AU
X 2
AU
X 3
AU
X 4
AU
X 5
AU
X 6
SPA PUMP
AUTO
POOL HEATER SPA HEATER
SOLAR
1
OFF ON
3
4
5
6
7
8
2
1
2
3
4
S1
S2
S2 DIP Switch #
OFF
ON
1
The AquaLink RS will be able to control a
Solar Heating system (If a solar sensor is
connected to the solar sensor input).
The AquaLink RS will be able to control a Heat
Pump. (The AquaLink RS will not be able to control
a Solar Heating system.)
2
NOT USED
3
NOT USED
4
NOT USED