4.2 

Fill Safety Lockout Mode

The Levolor is equipped with a Fill Safety Lockout 

Mode. This means that if the Fill Sensor probe has 

not been touched by water within the pre-set Fill time 

period, the controller turns the valve off for 24 hours 

and changes the Fill light from green to red.
The pre-set factory Fill time period is 20 minutes. See 

Table 2, LED Indicators, page 13.
To change the Fill time, follow the steps in 

Section 

4.5, Change Jumpers and Dip Switches

, and cut the 

appropriate jumper(s) as shown below in Table 3.

Jumper(s)

Fill Time Period

Factory Default

20 minute Fill before Lockout

Cut Either

 A or B

40 minute Fill before Lockout

Cut Both 

A and B

60 minute Fill before Lockout

NOTE  Cutting the S-1 Jumper will disable the Safety 

Lockout function.

The jumpers are located at the top left of the circuit 

board. See Figure 13.

4.3  Pump On Delay Variable Timer

When water touches the High Water Sensor, there is 

a delay before the controller activates the High Water 

Pump. 
The pre-set factory delay time is 2 ½ minutes.  

See Table 2, LED Indicators, page 13.
To change the delay time, follow the steps in 

Section 

4.5, Change Jumpers and Dip Switches

, and cut the 

appropriate jumper(s), as shown below in Table 4.

 

Table 4.  Pump On Delay Settings

Jumper

Delay

Factory Default

2½ minutes

Jumper 1 

20 seconds

Jumper 2

1 minute

Jumpers 1 and 2

5 minutes

The jumpers are located between the top left and middle 

controller lights on the circuit board. See Figure 13.

A

S 1

B

Lock-out

Jumpers

1

2

Pump On 

Delay

Jumpers

OFF                        ON             20 sec

OFF                        ON             2.5 min

OFF                        ON             5   min

OFF                        ON             10 min

OFF                        ON             15 min

OFF                        ON             20 min

OFF                        ON             25 min

OFF                        ON             30 min

OFF                        ON             35 min

OFF                        ON             40 min

Pump Off 

Delay

Dip Switches

Figure 13.  Jumpers and Dip Switches

Table 3.  Fill Safety Lockout Mode Settings

Page 14

ENGLISH

Jandy Pro Series Levolor

®

 II Electronic Water Leveler 

Models K-2000  

 

 

    

 

  

|

   Installation and Operation Manual

Summary of Contents for Levolor II

Page 1: ...ailure to follow warning notices and instructions may result in property damage personal injury or death Improper installation and or operation will void the warranty Improper installation and or oper...

Page 2: ...Page 2 ENGLISH Jandy Pro Series Levolor II Electronic Water Leveler Models K 2000 Installation and Operation Manual...

Page 3: ...7 Vanishing Edge Pool Installation 12 Section 4 Operation 13 4 1 Controller Lights 13 4 2 Fill Safety Lockout Mode 14 4 3 Pump On Delay Variable Timer 14 4 4 Pump Off Delay Variable Timer 15 4 5 Chan...

Page 4: ...ON INSTALLER This manual contains important information about the installation operation and safe use of this product This information should be given to the owner operator of this equipment WARNING R...

Page 5: ...1 coupling Depending on the kit the sensor comes with 50 to 500 feet of wire at the top and three 3 stainless steel contacts at the bottom The excess wire should be cut off after you have completed t...

Page 6: ...hite Wire High Level Sensor Yellow Red Red Wire Fill Sensor Yellow Blue Wires from Sensor Controller Sensor Wires Red Blue House or Irrigation 110VAC or 220VAC Power Supply Relay Coil 24VDC or Relay b...

Page 7: ...nd check to see that it contains the contents listed above If it does not contact your dealer or Zodiac technical support at 1 800 822 7933 3 2 Installing the Control Box 1 Mount the control box to th...

Page 8: ...ack white and the black red wires See Figure 3 2 Connect the black red wire with the black wire and connect to the line side of power See Figure 4 3 Connect the black white wire with the black yellow...

Page 9: ...he supplied grease filled wire nuts 2 Connect the wires from the Fill Valve to the blue wires in the control box using wire nuts See Figure 7 Control Box Wiring on page 10 3 Connect the wires from the...

Page 10: ...re to Power 24VAC High Level DC Relay Red Fill Valve Blue Yellow Wire to Sensor Common Sensor Common Yellow Black Wire Red Stripe Black Wire White Stripe Black Wire Yellow Stripe Black Wire Green Wire...

Page 11: ...ntrol box using a wire nut b Connect the red wire from the Fill Sensor probe to the yellow wire with the blue stripe in the control box using a wire nut c Connect the white wire from the High Water Se...

Page 12: ...obe NOTE When mounting a slip sensor on a static pipe glue 1 fittings with 793 IPS brand ABS PVC glue Do not glue 2 fittings Remote Sensor Housing Fill Sensor Probe Minimum Operating Water Level High...

Page 13: ...er Pump light turns green when the vanishing edge pump is running LED Function Indicated Color Operating Mode Delay to Turn Function ON Delay to Turn Function OFF Power Turn Power ON Green Power is ON...

Page 14: ...3 4 3 Pump On Delay Variable Timer When water touches the High Water Sensor there is a delay before the controller activates the High Water Pump The pre set factory delay time is 2 minutes See Table 2...

Page 15: ...ause a shock hazard resulting in severe personal injury or death To change the jumpers and dip switches do the following 1 Shut power off to the control box 2 Remove the three 3 screws from the upper...

Page 16: ...n the control box Valve or Relay Control Box Wires Valve Wires Blue Relay Wires Red and Gray Section 5 Troubleshooting Tools required Multimeter that can read AC and DC voltage and No 6 Phillips screw...

Page 17: ...troubleshooting flow charts on the following pages to find and fix the following problems Fill Will Not Turn Off Fill Will Not Turn On 5 2 2 Simulate Fill Valve and Activate Pump NOTE You have simula...

Page 18: ...blue wires with an AC volt meter YES PCB is bad Relay is stuck Does the voltage measure 24VAC Disconnect the blue wires from the controller Disconnect the yellow wire at the controller from the black...

Page 19: ...n on in 20 seconds NO YES YES Green Is there 24VAC at blue wires in control box NO YES Voltage is delivered to valve If gate is closed open it If solenoid port is dirty clean it If solenoid is not wor...