4.2
Fill Safety Lockout Mode
The Levolor is equipped with a Fill Safety Lockout
Mode. This means that if the Fill Sensor probe has
not been touched by water within the pre-set Fill time
period, the controller turns the valve off for 24 hours
and changes the Fill light from green to red.
The pre-set factory Fill time period is 20 minutes. See
Table 2, LED Indicators, page 13.
To change the Fill time, follow the steps in
Section
4.5, Change Jumpers and Dip Switches
, and cut the
appropriate jumper(s) as shown below in Table 3.
Jumper(s)
Fill Time Period
Factory Default
20 minute Fill before Lockout
Cut Either
A or B
40 minute Fill before Lockout
Cut Both
A and B
60 minute Fill before Lockout
NOTE Cutting the S-1 Jumper will disable the Safety
Lockout function.
The jumpers are located at the top left of the circuit
board. See Figure 13.
4.3 Pump On Delay Variable Timer
When water touches the High Water Sensor, there is
a delay before the controller activates the High Water
Pump.
The pre-set factory delay time is 2 ½ minutes.
See Table 2, LED Indicators, page 13.
To change the delay time, follow the steps in
Section
4.5, Change Jumpers and Dip Switches
, and cut the
appropriate jumper(s), as shown below in Table 4.
Table 4. Pump On Delay Settings
Jumper
Delay
Factory Default
2½ minutes
Jumper 1
20 seconds
Jumper 2
1 minute
Jumpers 1 and 2
5 minutes
The jumpers are located between the top left and middle
controller lights on the circuit board. See Figure 13.
A
S 1
B
Lock-out
Jumpers
1
2
Pump On
Delay
Jumpers
OFF ON 20 sec
OFF ON 2.5 min
OFF ON 5 min
OFF ON 10 min
OFF ON 15 min
OFF ON 20 min
OFF ON 25 min
OFF ON 30 min
OFF ON 35 min
OFF ON 40 min
Pump Off
Delay
Dip Switches
Figure 13. Jumpers and Dip Switches
Table 3. Fill Safety Lockout Mode Settings
Page 14
ENGLISH
Jandy Pro Series Levolor
®
II Electronic Water Leveler
Models K-2000
|
Installation and Operation Manual