Engine does not start from the AMF panel in any mode.
Ø
Check the DC supply control MCBs and 3 Phase mains supply. These should be
in ON Position.
Ø
Check the battery voltage at terminal 1 and 2 in the AMF Panel. It should be equal
to 12V/24V. If not, get the battery charged before making further attempts as the
battery is weak.
Ø
Check all control wires at control terminals in AMF panel.
Ø
Check battery terminals. They should be properly tightened and should not be
corroded.
Ø
Check LLOP connection , it should be properly connected on engine terminal.
Ø
Check all wiring connection should be properly tighten and all should be in order
as per drawing.
l
The battery connection may be loose or corroded. Check and correct the
problem.
l
If the MAINS supply is available, set the battery charger to boost and wait till
the battery voltage is 12/24V.
l
Refer KG controller manual for further trouble shooting related to KG
controller