jaga
|
AURORA Installation instructions
65
EN
HYDRAULIC SETTING JAGA HEIMEIER ECLIPSE VALVE
Setting
0
I
I
I
5
I
I
I
I
10
I
I
I
I
15
litre/h
10
20
30
40
50
60
70
80
90 100 110 120 130 140 150
Q[W]
∆T[K]
5
10
15
20
30
200
3
2
1
1
1
250
4
2
1
1
1
300
5
3
2
1
1
400
7
3
2
2
1
500
9
4
3
2
1
600
10
5
3
3
2
700
12
6
4
3
2
800
14
7
5
3
2
900
15
8
5
4
3
1000
9
6
4
3
1200
10
7
5
3
1400
12
8
6
4
1600
14
9
7
5
1800
15
10
8
5
2000
11
9
6
2200
13
9
6
2400
14
10
7
2600
15
11
7
2800
12
8
3000
13
9
3200
14
9
3400
15
10
3600
15
10
3800
11
4000
11
4800
14
5300
15
∆p min. 10 - 100 L/h = 0.10 bar (10 kPa)
∆p min. 100 - 150 L/h = 0.15 bar (15 kPa)
ADJUSTING THE H-BLOCK
(two pipes – single pipe)
6 mm
Number of rotations to open the by-pass
100
90
80
70
60
50
40
30
20
10
0
1.5
0.5
0
1
2
3
4
2.5
3.5
Ra
di
at
or fl
ow R
a i
n % f
ro
m w
at
er fl
ow
80
60
40
20
0
0
100
120
140
160
0.5 bar
0.1
0.2
0.3
0.4
0.6
50 kPa
10
20
30
40
60
Min.
Max.
Technical data
> Max. water flow temperature : 120 °C
> Max. pressure of system: 10 bar
> Max. pressure drop: 0.6 bar complying to the noise standard ref. ISO 3743
Automatic flow limiter
L/u
Example:
Heat exchanger 1 kW (Table 75/65-20)
∆
T = 10°C (75–65 = 10°C)
Flow rate: 86 l/u
Setting = 9
Q = radiator power in Watt (
∆
T =50)
∆T = temperature difference
∆P = differential pressure