P/N 24-132 REV A 7/00
Page 3
PREPARATION FOR INSTALLATION
Safe and satisfactory operation of your equipment depends to a great extent upon its proper
installation. Installation must conform with local codes, or in the absence of local, with the
National fuel code,
ANSI Z233.1-1988
or later. Electrical installation must conform with all
applicable state and local codes and be in compliance with the National Electrical Code,
ANSI/NFPA 70-1990
.
NOTE: AFTER ELECTRICAL INSTALLATION TO THE CONVECTION OVEN MASTER
SWITCH (TOGGLE SWITCH) SHOULD BE TURNED OFF UNTIL OVEN POLOT IS IGNITED
AND APPLIANCE READY FOR USE.
Refer to rating plate for gas-orifice type. If orifices are converted in the field, the rating plate
must be corrected by an experienced and responsible service person. Gas regulator must be
changed to suit gas to be used.
Check with appliance manufacturer.
INSTALLATION AND GAS PIPING
♦
Appliances battery-mounted (minimum of two appliances) must be lined up, leveled, and
have manifolds leveled and connected. Plate shelves are adjustable and holes are provided
to take 3/8-16T.P.I. bolts for securely locking plate shelves together. Similar provisions are
provided when appliances are equipped with high shelves.
♦
Adjusting legs that are provided can adequately level floor-mounted appliances. Kerb or
platform-mounted appliances (legs removed) have adjustable leveling bolts located within
the body (Front and rear on bottom of control box area, and within combustion area bottom
on right side of inner body. Remove oven bottom.)
♦
Connect appliances to gas supply line. Under no circumstances should the gas supply line
be smaller than the inlet pipe on the appliance. Use pipe compound on all pipe joints.
Compound must be resistant to the action of liquefied petroleum gases.
♦
Check all gas connections for leaks using soap and water solution. DO NOT USE AN
OPEN FLAME FOR CHECKING PURPOSES.
♦
The appliance and its individual shutoff valve must be disconnected from the gas supply
piping system during any pressure testing of that system at test pressures in excess of ½
psig (3.45 kPa).
♦
The appliance must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psig (3.5 kPa).
♦
Licensed or approved experienced personnel should do all installation and service work.