07610-001-76-22-N
15
All electrical connections must be made in accordance with applicable portions of local,
state, territorial, and national codes.
Refer to the data plate for machine operating requirements, machine voltage, total
amperage, and serial number.
1. Locate main power terminal blocks (for machine and gas booster) at the top
of the machine.
2. Remove the top cover to access terminal blocks.
3. Route incoming power lines within conduit that will connect via fittings to the pre-
punched holes in the back of the control box.
4.
Install power and ground wires to lugs as indicated by the appropriate decals in the
control box. Use copper conductors only. Use of an anti-oxidation agent is
recommended on the power connections.
5. Tighten all connections.
6. Verify the incoming voltage matches the voltage indicated on the decal next to the
incoming power pre-punched hole.
The machine has a separate power connection for gas boosters and the circuit
protection requirements are different for each. Consult booster manufacturer for
information.
ELECTRICAL
POWER
CONNECTIONS
Disconnect electrical
power at the breaker
or disconnect switch
and tagout in accordance
with procedures and
codes.
INSTALLATION
INSTRUCTIONS
i
NOTICE
Imbalanced
wild leg goes
to L3.
NOTICE
L1
L2
L3
Ground
3
Φ
Summary of Contents for AJ-44
Page 72: ...64 07610 001 76 22 N PARTS AJ 66 RACK RAILS Left to Right Right to Left 1 4 2 3 4 5 6 7 1 ...
Page 84: ...76 07610 001 76 22 N SCHEMATICS AJ 44CGP 208 230 V 60 HZ 1 PHASE AJ 44CGP SCHEMATIC ...
Page 85: ...07610 001 76 22 N 77 SCHEMATICS AJ 44CGP 208 230 V 60 HZ 3 PHASE AJ 44CGP SCHEMATIC ...
Page 86: ...78 07610 001 76 22 N SCHEMATICS AJ 44CGP 460 V 60 HZ 3 PHASE AJ 44CGP SCHEMATIC ...
Page 87: ...07610 001 76 22 N 79 SCHEMATICS AJ 66CGP 208 230 V 60 HZ 1 PHASE AJ 66CGP SCHEMATIC ...
Page 88: ...80 07610 001 76 22 N SCHEMATICS AJ 66CGP 208 230 V 60 HZ 3 PHASE AJ 66CGP SCHEMATIC ...
Page 89: ...07610 001 76 22 N 81 SCHEMATICS AJ 66CGP 380 460 600 V 60 HZ 3 PHASE AJ 66CGP SCHEMATIC ...