background image

JA-82K control panel installation manual   

- 9 - 

MKH51102 

6.19  Sirens always sound during audible alarms 

Using this sequence it is possible to disable internal and external sirens (IW 

and EW) if any part of the system is unset (partial setting), i.e. when someone 
is home. 

3 7 1

 

Sirens always sound during audible alarms 

3 7 0

 

Sirens only sound during audible alarms when all sections 
are set, i.e. no one is at home 

 

Factory default setting: 

Sirens always sound during audible alarms. 

6.20  Wireless siren alarm enabled (IW and EW) 

This setting is for enabling and disabling wireless sirens in the system:   

3 8 1

 

wireless sirens enabled 

3 8 0

 

wireless sirens disabled 

 

Note:

 This setting applies both to internal and external wireless sirens. 

Factory default setting:

 wireless sirens enabled 

6.21  Bypass user approval   

This setting can change the function of the system when it is being set 

(armed) and if there is: 

 any 

detector 

triggered 

  any tamper alarm 

  any trouble in the power source 

  lost communication with any wireless device (for more than 20 minutes) 

  any panic button triggered 

If bypass user approval is set (391), then during setting (arming), the 

system notes which problems mentioned above are active and displays 
informative text on the keypad and only bypasses them if the user approves 
the bypassing by keying in a 

 within 6 seconds of being notified. 

The system has a built-in auto-bypass function (setting 390) so that if any 
number of detectors are being triggered during setting (arming) then they will 
be bypassed and ignored automatically without consulting the user.  

 

3 9 1

 

Approval by pressing the

 

 key is requested

 from the user 

3 9 0

 

Bypassing occurs automatically without user approval 

 

Notes regarding setting the system with (a) triggered detector(s) or 
problems as mentioned above: 

 

Details can be viewed by pressing the 

?

 key (e.g. open doors or 

windows). 

 

If a wireless keyfob is used to set the system and auto-bypass user 
approval is enabled, the system will set without bypass approval, i.e. 
setting by keyfob does not trigger an approval request.  

 

The automatic bypass of a detector will end after the detector has been 
de-triggered (for example if a door is closed) or the problem disappears. 

 

If auto-bypass user approval is enabled and Service mode is being exited 
while a detector is being triggered, the installer will be notified about the 
bypass. The installer can then approve the bypass by pressing #  twice. 

 

To comply with the EN-50131-1, 3 standards 391 should be set.

 

 

Factory default setting:

 Bypassing occurs automatically without user 

approval. 

6.22 Final-door 

detectors   

In this mode, up to 5 detectors can be defined as final-door detectors and 

assigned to addresses 01 to 05 or 46 to 50 in order to make leaving a 
building much easier, especially via a garage:  

65x 

where 

x = 0 

none,  

x = 1

 

detectors on addresses 01 to 05, 

x = 2

 

detectors on addresses 46 to 50.

 

 

Description of final-door detector mode: 

  If a final-door detector is used in the system then the value of x for exit 

delay programming is multiplied by 30 s (see 12) thereby extending the 
delay, and if an entrance delay is triggered by a final-door detector then 
the value of x for the entrance delay is also multiplied by a larger value of 
30 s. 

  A final-door detector should be programmed to have a natural reaction, 

otherwise it works as it is set (e.g. instant reaction).  

  Only door/window detectors, hard-wired control panel inputs or hard-wired 

inputs in the wireless keypad unit to whose alarm input the final-door 
detector is connected should be assigned to the addresses which you set 
with this sequence as belonging to final-door detectors. 

  If a final-door detector is used for a garage door, no instant detectors 

should be inside the garage. Next-delay detectors would however be 
acceptable. 

 

Setting (arming) the system with a final-door detector: 

  After entering a request to set the system, an exit delay of between 30 to 

270 seconds will begin and be indicated.  

  If a final-door detector is triggered during the exit delay, the exit delay will 

be extended by the time in which the detector is still triggered. So, if for 
example, the door is left continuously open, the exit delay will never end. 

  If a final-door detector is de-triggered, the system will wait five more 

seconds during which beeping gets faster, and if the door is not opened 
again during this short period, the exit delay will terminate and the system 
will be set immediately. 

  The duration of the exit delay therefore depends on the time the final door 

stays open. For instance, in winter if the driveway in front of a garage 
needs to be cleared of snow there will be plenty of time to do it, and in 
summer when garages can be exited easily and therefore quickly, the exit 
delay can be rather shorter. The exit delay only depends on the length of 
time the garage door is left open. 

  If no final-door detectors are triggered during the exit delay, the system 

will provide an exit delay and then set.  

  If the final door detector stays continuously triggered, an endless exit 

delay will result with the system never being set. This means all delayed 
and next-delayed detectors will not be set (armed). 

  If there are multiple final-door detectors in the system, the exit delay is 

extended if any of them is triggered and ends after all final-door detectors 
have been de-triggered. 

 

Unsetting (disarming) the system with a final door detector: 

  If a final-door detector gets triggered in a set (armed) system, an entrance 

delay will begin with a duration of between 30 and 270 seconds. 

  If a normal delayed detector gets triggered while the user enters a 

building, the system starts an ordinary entrance delay of between 5 and 
45 seconds.  

  If a final-door detector is triggered first, a longer entrance delay will begin. 

If during this delay an ordinary delayed detector is then triggered, the 
remaining entrance delay will then be shortened to the delay associated 
with detectors of this kind. 

Note: 

Only use status-reporting detectors such as the JA-81M or JA-82M, or 

the hard-wired inputs of wireless keypads, or the hard-wired inputs of a 
control panel as final-door detectors.  This mode is unsuitable for pulse 
detectors such as JA-80P motion detectors, or the hard-wired inputs of JA-
80E hard-wired keypads which also have a pulse reaction. 

Factory default setting:

 No final-door detectors in the system. 

6.23  Partial setting (arming) or system splitting 

 

The control panel can be configured in three ways as follows: 

  the entire system sets and unsets together or, 

  the system partially sets and unsets to protect only certain parts of a 

house during the day, while people are still present in the unset parts 
or, 

  the system can be split into two independently set/unset sections for 

two separate users and also with a common section if desired. 

 

Program as follows to configure the system as desired: 

66x 

where 

x = 0 

unsplit system 

(setting/unsetting as an entire system)

   

x = 1 

partial setting 

(for setting sections A, AB, or ABC) 

x = 2 

split  system 

(sections A and B can be set/unset 

independently by separate users, with section C only being 
automatically set when both A and B are manually set) 

Notes: 

 

For an unsplit system, 

all intruder detectors are set/unset 

immediately after the user sets/unsets the system. Assigning wireless 
devices, access codes and keyfobs to various sections of the system 
has no effect in this mode. 

 

Partial setting 

is especially suitable

 

for homes and apartments 

where the user wishes to protect different parts of the premises 
during the day. Detectors can be assigned to three sections, A, B and 
C. Using setting (arming) key A on the system keypad, you can set 
section A, e.g. setting the garage area in the afternoon. Using setting 
key B you can set sections A and B simultaneously e.g. in the 
evening before going to sleep  to protect the garage (section A) and 
the ground floor of the house (section B). The ABC total-setting 
button is used when leaving the home to set all sections, A,B and C. 
If you then use a valid access code or card for unsetting (disarming), 
all sections will be unset. The assignment of codes or cards to 
sections has no effect in this mode. A and B keypad buttons are used 
for partial setting.   

 

A keyfob can also be used for partial setting control. Buttons 

 and 

 can be programmed to set and unset the entire system, and 

buttons 

+

 can be programmed for setting (arming) sections A 

and AB respectively to partially set the system (this pair of buttons 
must be assigned to section A or B if it is to be used for partial 
setting. See 6.40 for details on partial setting by keyfob). 

 

Split system mode

 is especially suitable where two families (A and 

B) live in a single house or two companies (A and B) share one 
building. The system behaves as two independent systems, one 
being section A and the other, section B. There is also a common 

Summary of Contents for JA-82K OASiS

Page 1: ...JA 82K OASiS Control panel installation manual...

Page 2: ...6 21 Bypass user approval 9 6 22 Final door detectors 9 6 23 Partial setting arming or system splitting 9 6 24 Automatic summer time daylight saving time 10 6 25 Pulse reaction of tamper sensors 10 6...

Page 3: ...ring the control panel for installation The control panel can be attached to the wall using 3 screws If the control panel communicates via radio it should not be installed near any large metal objects...

Page 4: ...input modules By adding the JA 82C module it is possible to extend the amount of inputs to fourteen addresses 01 14 All hard wire inputs behave identically they are double balanced inputs which are ab...

Page 5: ...p time in case of a power grid failure For the standby consumption of all system devices see fig 8 ATTENTION the backup battery is sold charged avoid shorting out its terminals The average backup batt...

Page 6: ...and then wait until it is ready for testing 3 The keypad its cover should be flipped open beeps and displays a description of the signal received from the device under test 4 You can test the enrolle...

Page 7: ...a code or card These PG output functions can also be controlled by signals from keyfobs or detectors see 6 40 Notes The PGX and PGY outputs are not only provided as control panel terminals but the si...

Page 8: ...r detector gets triggered i e a detector with an instant delayed or next delayed reaction an alarm will not be caused but the control panel will record a so called unconfirmed alarm If any other intru...

Page 9: ...door is not opened again during this short period the exit delay will terminate and the system will be set immediately The duration of the exit delay therefore depends on the time the final door stay...

Page 10: ...sed in Service Mode the display turns off after 15 minutes of no use by the installer Factory default setting only 3 minutes of display time 6 28 Tamper alarm if unset According to EU legislation an u...

Page 11: ...erference was present Factory default setting standard control panel sensitivity 6 37 Access by code plus card This feature increases security against unauthorised setting unsetting arming disarming 6...

Page 12: ...e buttons or The button has no effect can still be used for controlling UC AC receivers Factory default setting All addresses from 01 to 50 have a natural reaction r 1 and are assigned to section C s...

Page 13: ...called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Central on the menu and then Text synchronization Comparison or F11 After ed...

Page 14: ...still set he will not need to unset the whole system before leaving the house and setting the whole system The route used by the user to leave the house must be covered by delayed or next delayed det...

Page 15: ...he installation in a very professional and conscientious manner and always tidy up the site afterwards It is very important to teach the end user how to use and test the system and to check his level...

Page 16: ...e after 10 events Fault signal or message after 1 event Security grade 2 according to EN 50131 1 EN 50131 6 and EN 50131 5 3 Environmental class II indoor general 10 to 40 C compliant with EN 50131 1...

Page 17: ...ay A PG on 3 entrance delay B PG on 4 A set X on B set Y on 5 A panic X on B panic Y on 6 Fire X on AC dropout Y on 7 PG on off by 80 81for PGX and 90 91 for PGY 8 Single 2 s pulse keys 8 X 9 Y Enable...

Page 18: ...ber of triggered tamper sensors 681x 6811 ignore permanently triggered tamper sensors i e only react to an increase in the number of triggered tamper sensors 6810 react with a tamper alarm to all trig...

Page 19: ...switch in the detector for wired inputs DELay for Codes cards SET UNSET 2 Panic 3 Fire 4 24 hours 5 Next DELay 6 INStant 7 SET arm 8 PG control s 1 PGX 2 PGY 3 PGX PGY 9 SET UNSET toggle s section 1...

Page 20: ...To make handing over the system to the end user easier we recommend programming the system card provided with the control panel to the master code Example 5 1234 and then presenting the card to the ke...

Page 21: ...Notes...

Page 22: ......

Reviews: