jablotron JA-82K OASiS Installation Manual Download Page 5

JA-82K control panel installation manual   

- 5 - 

MKH51102 

3.7 

Wired keypad connection  

The control panel can be operated and programmed by a JA-80E hard-

wired keypad. A screened four-cord flat cable connecting the corresponding 
terminals should be used for permanent connection between the keypad and 
the control panel (see fig. 7.) 

The keypad can also be connected to a bus connector on the control 

panel box using a flat cable (max 10 metres) with RJ connectors for the 
purpose of servicing or system debugging.  

 

1

2

3

ABC

4

5

6

A

7

8

9

ON

0

#

B
?

OFF

ESC

A

B

C

OASiS

1

2

3

ABC

4

5

6

A

7

8

9

ON

0

#

B
?

OFF

ESC

A

B

C

OASiS

Control and programming

keypad JA-81E

Modular connection

cable

 

fig. 7 Wired keypad connection  

Note: 

When you use the INP keypad hard-wired input to connect the door detector, 
its reaction is always delayed (it triggers an entry delay) and it is assigned to 
section C. 
We recommend having only a single JA-80E hard-wired keypad in the 
system. 

3.8 

Control panel resetting  

If you need to set the factory-default settings in the control panel, perform the 
following:   

 

1.  Disconnect the back-up battery and the mains (using the terminal 

board fuse), 

2. 

Connect the RESET link

 and leave it connected, 

3. 

Connect

 the back-up battery and the 

mains

,  

4. 

Wait

 until the green LED starts flashing and then 

disconnect the 

RESET link.

 

If you need to reset the control panel with preset parameters according to  EN 
50131-3 (see 6.48) follow these next steps: 

1.  Disconnect the back-up battery and the mains (using the terminal 

board fuse), 

2. 

Connect the RESET link

 and leave it connected, 

3. 

Connect

 the back-up battery and the 

mains

,  

4. 

Wait

 until the green LED starts flashing and 

key in the sequence 

8080

 an finally 

disconnect the RESET link.

 

Note: 

After a RESET, all wireless devices and access cards are erased from the 
control panel as well as user codes.  
The Master code changes to 1234, and the service code to 8080. 
If resetting is disabled (see 6.8) 

it is impossible to reset the control panel.

 

 

 

Control panel power supply 

Once the control panel is assembled and all modules are in place, you can 

proceed with putting the control panel into operation. We recommend 
switching the control panel on without any wired detectors connected, using 
only the wired keypad (if it is used in the system) for the first time. Only then 
should you continue connecting the detectors. Beware of short circuits – it is 
strongly recommended to switch off the power when working. 

4.1 

Backup battery connection  

It is possible to use a 12V gel cell backup battery, with a capacity of up to 2.4 
Ah in the control panel. The EN 50131-1 standard requires a 12-hour minimum 

backup time in case of a power grid failure. For the standby consumption of all 
system devices, see fig. 8. 
 

 

 
ATTENTION – the backup battery is sold 
charged, avoid shorting out its terminals! 

 

 

The average backup battery lifetime is up to 5 years after which it must be 
replaced

. Checking its capacity during regular maintenance is 

recommended. 

The control panel automatically recharges the backup battery 

and monitors its condition.

 When the system runs only on the backup 

battery, the battery status is monitored and a technical alarm is triggered 
before its complete depletion. The backup battery is then disconnected. 

Once the

 

power supply has been restored, the battery reconnects and is 

recharged

.  

Ensure that the battery is correctly connected (Polarity: RED = po, 
BLACK = negative -).  
 
 

fig. 8 power consumption of individual components  

4.2 Power 

supply 

connection 

 

Only a person with corresponding electro-
technical qualification can connect the power 
supply.   
The control panel power supply is double-
insulated (safety class 2) and does not 
incorporate a protective grounding wire. 

 
The control-panel power cable should only be installed by a person holding 

a sufficient electro-technical qualification.

 

 

The control panel power supply is double-insulated (protection class II) and 

does not incorporate a protective earth wire. 

  A double-insulated power cable should be used with a minimum cross-

sectional area of 0.75 to 1.5 mm

2

. The power cable should be connected 

to a switched mains supply fused to 10 Amps. 

  In the control panel, connect the cable to the power terminals equipped 

with a fuse of type T200mA/250V.  

 

Fix the cable firmly to the cable holder 

in the control panel making sure 

that the wire ends are properly secured and connected in the terminals. 

 

 

Mains fuse

 T 200 mA

 

 

4.3 

Powering-up the control panel for the first time 

13. First check all the wiring, and if a GSM communicator is installed, insert its SIM 

card (PIN code disabled). 

14. Check the backup battery connection  
15. Switch the power supply on – a green LED starts flashing on the control panel 

board. 

16. If a hard-wired keypad is connected it indicates “Service” mode  
17. The control panel can also be set up via the interface using OLink software – (A 

virtual keypad can be used in OLink to indicate system status). 

18. If you have neither the wired keypad, nor OLink, enrol a wireless keypad by the 

following means: 

a)  have an opened keypad and its battery ready, 
b)  check that the green LED in the control panel is flashing,  
c)  short the RESET link in the control panel for 1 second (enrollment mode 

opens), 

device 

mA 

note 

JA-82K control panel 

30 

without a communicator  

JA-82R module 

20 

 

JA-82C module 

15 

 

JA-80E keypad 

30 

 

JA-80H (N)  keypad 

60 

including WJ-80 interface 

JA-80Y communicator 

35 

 

JA-80V communicator 

30 

 

JA-80X communicator 

15 

 

Wireless devices are not powered from the control panel 

Summary of Contents for JA-82K OASiS

Page 1: ...JA 82K OASiS Control panel installation manual...

Page 2: ...6 21 Bypass user approval 9 6 22 Final door detectors 9 6 23 Partial setting arming or system splitting 9 6 24 Automatic summer time daylight saving time 10 6 25 Pulse reaction of tamper sensors 10 6...

Page 3: ...ring the control panel for installation The control panel can be attached to the wall using 3 screws If the control panel communicates via radio it should not be installed near any large metal objects...

Page 4: ...input modules By adding the JA 82C module it is possible to extend the amount of inputs to fourteen addresses 01 14 All hard wire inputs behave identically they are double balanced inputs which are ab...

Page 5: ...p time in case of a power grid failure For the standby consumption of all system devices see fig 8 ATTENTION the backup battery is sold charged avoid shorting out its terminals The average backup batt...

Page 6: ...and then wait until it is ready for testing 3 The keypad its cover should be flipped open beeps and displays a description of the signal received from the device under test 4 You can test the enrolle...

Page 7: ...a code or card These PG output functions can also be controlled by signals from keyfobs or detectors see 6 40 Notes The PGX and PGY outputs are not only provided as control panel terminals but the si...

Page 8: ...r detector gets triggered i e a detector with an instant delayed or next delayed reaction an alarm will not be caused but the control panel will record a so called unconfirmed alarm If any other intru...

Page 9: ...door is not opened again during this short period the exit delay will terminate and the system will be set immediately The duration of the exit delay therefore depends on the time the final door stay...

Page 10: ...sed in Service Mode the display turns off after 15 minutes of no use by the installer Factory default setting only 3 minutes of display time 6 28 Tamper alarm if unset According to EU legislation an u...

Page 11: ...erference was present Factory default setting standard control panel sensitivity 6 37 Access by code plus card This feature increases security against unauthorised setting unsetting arming disarming 6...

Page 12: ...e buttons or The button has no effect can still be used for controlling UC AC receivers Factory default setting All addresses from 01 to 50 have a natural reaction r 1 and are assigned to section C s...

Page 13: ...called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Central on the menu and then Text synchronization Comparison or F11 After ed...

Page 14: ...still set he will not need to unset the whole system before leaving the house and setting the whole system The route used by the user to leave the house must be covered by delayed or next delayed det...

Page 15: ...he installation in a very professional and conscientious manner and always tidy up the site afterwards It is very important to teach the end user how to use and test the system and to check his level...

Page 16: ...e after 10 events Fault signal or message after 1 event Security grade 2 according to EN 50131 1 EN 50131 6 and EN 50131 5 3 Environmental class II indoor general 10 to 40 C compliant with EN 50131 1...

Page 17: ...ay A PG on 3 entrance delay B PG on 4 A set X on B set Y on 5 A panic X on B panic Y on 6 Fire X on AC dropout Y on 7 PG on off by 80 81for PGX and 90 91 for PGY 8 Single 2 s pulse keys 8 X 9 Y Enable...

Page 18: ...ber of triggered tamper sensors 681x 6811 ignore permanently triggered tamper sensors i e only react to an increase in the number of triggered tamper sensors 6810 react with a tamper alarm to all trig...

Page 19: ...switch in the detector for wired inputs DELay for Codes cards SET UNSET 2 Panic 3 Fire 4 24 hours 5 Next DELay 6 INStant 7 SET arm 8 PG control s 1 PGX 2 PGY 3 PGX PGY 9 SET UNSET toggle s section 1...

Page 20: ...To make handing over the system to the end user easier we recommend programming the system card provided with the control panel to the master code Example 5 1234 and then presenting the card to the ke...

Page 21: ...Notes...

Page 22: ......

Reviews: