JA-82K control panel installation manual
- 7 -
MKH51102
6
Control panel programming
The most convenient way to program the system is to use a PC running
OLink software. However, the system can also be programmed by keying in
the below mentioned sequences. The sequence summary table can be found
at the end of this manual.
•
The control panel must have its antenna connected and it must be in
Service mode (If this is not the case, enter *0 service code (factory
default: 8080). The control panel must be disarmed).
•
Enter the appropriate programming sequences – see the following
description (an unfinished sequence can be escaped from by pressing the
# key).
•
To exit Service
Mode
press the # key.
6.1
Exit delay time
An exit delay time occurs while setting (arming) the system. During this time
period delayed or next-delayed detectors can be triggered without an alarm
occurring. To program the delay time, enter:
20x
where
x
is a number from 1 to 9 determining the duration in steps of tens
of seconds (1=10 s, 2=20 s,....)
If there is a final-door detector in the system then the exit delay is multiplied
by 30 s instead (1=30 s, 2=60 s,...).
Example:
To program a 20 seconds exit delay, use the sequence 202 (if
there is a final-door detector, a 60 seconds delay will result).
Factory default setting:
x = 3
6.2
Entrance delay time
The entrance delay time is provided to unset (disarm) the system after a
first delayed detector has been triggered. To program this time, enter:
21x
where
x
is a number from 1 to 9 determining the delay in multiples
of 5 seconds (1=5 s, 2=10 s,....)
If the entrance delay is triggered by a final-door detector, then parameter x
is multiplied by 30 s instead. (1=30 s, 2=60 s,...) – in this case it means that
the entrance delay would be six times longer than if it had been triggered by
an ordinary detector.
Example:
To program a 20 seconds entrance delay, enter the sequence 214
(if the delay has been activated by a final-door detector, a 120 seconds delay
will result instead).
Factory default setting:
x = 4
6.3
Alarm duration time
This parameter limits the duration of a triggered alarm. After the alarm state
expires, the control panel will return to its previous state, i.e. as before the
alarm occurred. The alarm state can also be terminated by an authorised
user. To program the alarm duration enter:
22x
where
x
is
a number from 0 to 9 determining the alarm duration: 0 = 10 s,
1 = 1 min., 2 = 2 min. up to 8 = 8 min., 9 = 15 min.
Note:
There can be up to 5 different alarms in the system: intruder, tamper,
fire, panic, and technical alarm.
Example:
Alarm duration of 5 min. = sequence 225
Factory default setting:
4 minutes
6.4
PGX and PGY functions
The functions of PGX and PGY can be programmed by entering
sequences:
2 3 x
for PGX
2 4 x
for PGY
where
x
determines the PG function or the event which triggers a change of
PG state:
x
Unsplit system
Split system
0
Completely (ABC) set
= PG on
Alarm A = PG on
1
Anything set = PG on
Alarm B = PG on
2
AB set
(not ABC)
= PG
on
Entrance delay A = PG on
3
Fire alarm = PG on
Entrance delay B = PG on
4
Panic = PG on
A set = PGX on, B set = PGY on
5
Any alarm = PG on
(excluding Panic)
Panic A = PGX on
Panic B = PGY on
6
AC dropout = PG on
Fire = PGX on, dropout =PGY on
7*
ON/OFF
8*
2 seconds pulse
fig. 9 PG outputs settings
* The ON / OFF and 2 second pulse functions can be controlled from the
keypad by keying in * 8, *9 or using the arrow keys
(see 6.26) or
they can be operated by a code or card. These PG output functions can also
be controlled by signals from keyfobs or detectors (see 6.40).
Notes:
•
The PGX and PGY outputs are not only provided as control panel terminals,
but the signals are also wirelessly transmitted for UC and AC modules.
•
The status of PGX and PGY outputs can be displayed by pressing the
“
?”
key. The names of the outputs can be edited – see 6.47.
Example (for unsplit systems):
Assigning an ON/OFF function to the PGX
output = sequence 237. Assigning a panic function to the PGY output =
sequence 244.
Factory default setting:
PgX= ON/OFF, PgY= anything set
6.5 Changing telephone numbers in maintenance
mode
If the control panel is equipped with a JA-80Y, JA-80V or JA-80X
communicator, then this sequence enables the
holder of the master code
(system administrator)
to program telephone numbers for alarm reporting in
maintenance mode. Programming telephone numbers is the same as in
Service mode (see communicator manual):
2 5 1
programming
enabled
2 5 0
programming
disabled
Factory default setting:
programming disabled
.
6.6
Radio interference indication
The control panel is capable of detecting and indicating radio communication
jamming. If this function is enabled, any radio jamming longer than 30 s will
trigger fault indication and if armed the alarm is triggered.
2 6 1
enabled
2 6 0
disabled
Factory default setting:
disabled.
Note: In some places the system can be permanently or occasionally
affected by radio interference, e.g. by nearby radar stations, TV
transmitters etc. In most cases the system can tolerate such effects, but
with this anti-jamming function disabled.
6.7
Radio communications supervision
If enabled, the control panel can routinely check the wireless
communication of its devices. If communication with a particular device is lost
for two hours, the control panel can report a fault indication.
2 7 1
indication
enabled
2 7 0
indication
disabled
Notes:
•
In the OASiS system, communication is checked every 9 mins.
•
In detectors used for car protection, (JA-85P, JA-85B) it is possible to
disable radio communication supervision. It allows car detectors to be
excluded from supervision to avoid alarm triggering when driving the car
away from the system.
•
Random dropouts in communication can occur in some installations near
e.g. airports or TV towers. The system is still reliable in such situations as
high-priority transmissions are repeated often. We recommend disabling
communications supervision in cases like this.
Factory default setting:
supervision disabled.
6.8 RESET
enabled
If resetting is enabled, it is possible to return the control panel to its original
factory-default settings via the reset link on the main board. (see section 3.8).
2 8 1
RESET
enabled
2 8 0
RESET
disabled
Warning:
If resetting is disabled and the service code has been forgotten, it
would no longer be possible to enter Service mode. If this happens, send the
control panel back to the manufacturer.
Factory default setting:
RESET enabled.
6.9 Enrollment to a sub control panel for setting
control
If the control panel has another OASiS control panel enrolled as a sub-
system, then the sub-system reports all alarms, tampering and faults to the
master control panel. The master control panel reacts to particular signals
accordingly, and displays the sub control panel’s address as the source.
After sub control panel enrollment to the master control panel, these two
panels are independent concerning setting control. Each panel can be
operated by its own keypads or key fobs. If there is an alarm or fault in the