background image

JA-82K control panel installation manual   

- 7 - 

MKH51102 

Control panel programming 

The most convenient way to program the system is to use a PC running 

OLink software. However, the system can also be programmed by keying in 
the below mentioned sequences. The sequence summary table can be found 
at the end of this manual.  

  The control panel must have its antenna connected and it must be in 

Service mode (If this is not the case, enter *0 service code (factory 
default: 8080). The control panel must be disarmed). 

  Enter the appropriate programming sequences – see the following 

description (an unfinished sequence can be escaped from by pressing the 
# key). 

 

To exit Service

 

Mode

 press the # key. 

6.1 

Exit delay time   

An exit delay time occurs while setting (arming) the system. During this time 

period delayed or next-delayed detectors can be triggered without an alarm 
occurring. To program the delay time, enter: 

20x 

where 

is a number from 1 to 9 determining the duration in steps of tens 

of seconds (1=10 s, 2=20 s,....) 

If there is a final-door detector in the system then the exit delay is multiplied 
by 30 s instead (1=30 s, 2=60 s,...). 

Example:

 To program a 20 seconds exit delay, use the sequence 202 (if 

there is a final-door detector, a 60 seconds delay will result).  

Factory default setting:

 x = 3 

 

6.2 

Entrance delay time 

 

The entrance delay time is provided to unset (disarm) the system after a 

first delayed detector has been triggered. To program this time, enter: 

21x 

where 

is a number from 1 to 9 determining the delay in multiples  

   of 5 seconds (1=5 s, 2=10 s,....) 

If the entrance delay is triggered by a final-door detector, then parameter x 

is multiplied by 30 s instead. (1=30 s, 2=60 s,...) – in this case it means that 
the entrance delay would be six times longer than if it had been triggered by 
an ordinary detector.   

Example:

 To program a 20 seconds entrance delay, enter the sequence 214 

(if the delay has been activated by a final-door detector, a 120 seconds delay 
will result instead). 

Factory default setting:

 x = 4  

6.3 

Alarm duration time 

This parameter limits the duration of a triggered alarm. After the alarm state 

expires, the control panel will return to its previous state, i.e. as before the 
alarm occurred. The alarm state can also be terminated by an authorised 
user. To program the alarm duration enter:  

22x 

where 

is

 

a number from 0 to 9 determining the alarm duration: 0 = 10 s, 

1 = 1 min., 2 = 2 min. up to 8 = 8 min., 9 = 15 min.   

Note:

 There can be up to 5 different alarms in the system: intruder, tamper, 

fire, panic, and technical alarm.   

 

Example:

 Alarm duration of  5 min. = sequence 225 

Factory default setting:

 

 

4 minutes 

 

6.4 

PGX and PGY functions 

 

The functions of PGX and PGY can be programmed by entering 

sequences: 

2 3 x

   for PGX 

2 4 x

   for PGY 

 

where  

x

  determines the PG function or the event which triggers a change of 

PG state:  

Unsplit system 

Split system 

Completely (ABC) set 
= PG on 

Alarm A = PG on 

Anything set = PG on 

Alarm B = PG on 

AB set 

(not ABC) 

= PG 

on 

Entrance delay A = PG on 

Fire alarm = PG on 

Entrance delay B = PG on 

Panic = PG on 

A set = PGX on, B set = PGY on 

Any alarm = PG on 

(excluding Panic) 

Panic A = PGX on 
Panic B = PGY  on 

AC dropout = PG on 

Fire = PGX on, dropout =PGY on  

7* 

ON/OFF   

8* 

2 seconds pulse  

fig. 9 PG outputs settings

 

 

* The ON / OFF and 2 second pulse functions can be controlled from the 
keypad by keying in * 8, *9 or using the arrow keys

 

 

(see 6.26) or 

they can be operated by a code or card. These PG output functions can also 
be controlled by signals from keyfobs or detectors (see 6.40). 

Notes:  

 

The PGX and PGY outputs are not only provided as control panel terminals, 
but the signals are also wirelessly transmitted for UC and AC modules. 

 

The status of PGX and PGY  outputs can be displayed by pressing the 

?”

 key. The names of the outputs can be edited  – see 6.47. 

Example (for unsplit systems): 

Assigning an ON/OFF function to the PGX 

output = sequence 237. Assigning a panic function to the PGY output = 
sequence 244. 

Factory default setting:

 PgX= ON/OFF, PgY= anything set 

 

6.5  Changing telephone numbers in maintenance 

mode 

If the control panel is equipped with a JA-80Y, JA-80V or JA-80X 

communicator, then this sequence enables the 

holder of the master code 

(system administrator) 

to program telephone numbers for alarm reporting in 

maintenance mode. Programming telephone numbers is the same as in 
Service mode (see communicator manual): 

 

2 5 1

 programming 

enabled

 

2 5 0

 programming 

disabled

 

 

Factory default setting:

 

programming disabled

6.6 

Radio interference indication 

The control panel is capable of detecting and indicating radio communication 
jamming. If this function is enabled, any radio jamming longer than 30 s will 
trigger fault indication and if armed the alarm is triggered. 

 

2 6 1

 enabled 

2 6 0

 disabled 

 

 

Factory default setting:

 disabled. 

 

Note: In some places the system can be permanently or occasionally  
affected by radio interference, e.g. by nearby radar stations, TV 
transmitters etc. In most cases the system can tolerate such effects, but 
with this anti-jamming function disabled.  

6.7 

Radio communications supervision 

If enabled, the control panel can routinely check the wireless 

communication of its devices. If communication with a particular device is lost 
for two hours, the control panel can report a fault indication.  

2 7 1

 indication 

enabled

 

2 7 0

 indication 

disabled

  

Notes:  

 

In the OASiS system, communication is checked every 9 mins. 

 

In detectors used for car protection, (JA-85P, JA-85B) it is possible to 
disable radio communication supervision. It allows car detectors to be 
excluded from supervision to avoid alarm triggering when driving the car 
away from the system. 

 

Random dropouts in communication can occur in some installations near 
e.g. airports or TV towers. The system is still reliable in such situations as 
high-priority transmissions are repeated often. We recommend disabling 
communications supervision in cases like this. 

 

Factory default setting:

 supervision disabled. 

6.8 RESET 

enabled 

If resetting is enabled, it is possible to return the control panel to its original 

factory-default settings via the reset link on the main board. (see section 3.8). 

2 8 1

 RESET 

enabled

 

2 8 0

 RESET 

disabled

  

Warning:

 If resetting is disabled and the service code has been forgotten, it 

would no longer be possible to enter Service mode. If this happens, send the 
control panel back to the manufacturer. 

Factory default setting:

 RESET enabled. 

6.9  Enrollment to a sub control panel for setting  

control  

 

If the control panel has another OASiS control panel enrolled as a sub-

system, then the sub-system reports all alarms, tampering and faults to the 
master control panel. The master control panel reacts to particular signals 
accordingly, and displays the sub control panel’s address as the source.  

After sub control panel enrollment to the master control panel, these two 

panels are independent concerning setting control. Each panel can be 
operated by its own keypads or key fobs. If there is an alarm or fault in the 

Summary of Contents for JA-82K OASiS

Page 1: ...JA 82K OASiS Control panel installation manual...

Page 2: ...6 21 Bypass user approval 9 6 22 Final door detectors 9 6 23 Partial setting arming or system splitting 9 6 24 Automatic summer time daylight saving time 10 6 25 Pulse reaction of tamper sensors 10 6...

Page 3: ...ring the control panel for installation The control panel can be attached to the wall using 3 screws If the control panel communicates via radio it should not be installed near any large metal objects...

Page 4: ...input modules By adding the JA 82C module it is possible to extend the amount of inputs to fourteen addresses 01 14 All hard wire inputs behave identically they are double balanced inputs which are ab...

Page 5: ...p time in case of a power grid failure For the standby consumption of all system devices see fig 8 ATTENTION the backup battery is sold charged avoid shorting out its terminals The average backup batt...

Page 6: ...and then wait until it is ready for testing 3 The keypad its cover should be flipped open beeps and displays a description of the signal received from the device under test 4 You can test the enrolle...

Page 7: ...a code or card These PG output functions can also be controlled by signals from keyfobs or detectors see 6 40 Notes The PGX and PGY outputs are not only provided as control panel terminals but the si...

Page 8: ...r detector gets triggered i e a detector with an instant delayed or next delayed reaction an alarm will not be caused but the control panel will record a so called unconfirmed alarm If any other intru...

Page 9: ...door is not opened again during this short period the exit delay will terminate and the system will be set immediately The duration of the exit delay therefore depends on the time the final door stay...

Page 10: ...sed in Service Mode the display turns off after 15 minutes of no use by the installer Factory default setting only 3 minutes of display time 6 28 Tamper alarm if unset According to EU legislation an u...

Page 11: ...erference was present Factory default setting standard control panel sensitivity 6 37 Access by code plus card This feature increases security against unauthorised setting unsetting arming disarming 6...

Page 12: ...e buttons or The button has no effect can still be used for controlling UC AC receivers Factory default setting All addresses from 01 to 50 have a natural reaction r 1 and are assigned to section C s...

Page 13: ...called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Central on the menu and then Text synchronization Comparison or F11 After ed...

Page 14: ...still set he will not need to unset the whole system before leaving the house and setting the whole system The route used by the user to leave the house must be covered by delayed or next delayed det...

Page 15: ...he installation in a very professional and conscientious manner and always tidy up the site afterwards It is very important to teach the end user how to use and test the system and to check his level...

Page 16: ...e after 10 events Fault signal or message after 1 event Security grade 2 according to EN 50131 1 EN 50131 6 and EN 50131 5 3 Environmental class II indoor general 10 to 40 C compliant with EN 50131 1...

Page 17: ...ay A PG on 3 entrance delay B PG on 4 A set X on B set Y on 5 A panic X on B panic Y on 6 Fire X on AC dropout Y on 7 PG on off by 80 81for PGX and 90 91 for PGY 8 Single 2 s pulse keys 8 X 9 Y Enable...

Page 18: ...ber of triggered tamper sensors 681x 6811 ignore permanently triggered tamper sensors i e only react to an increase in the number of triggered tamper sensors 6810 react with a tamper alarm to all trig...

Page 19: ...switch in the detector for wired inputs DELay for Codes cards SET UNSET 2 Panic 3 Fire 4 24 hours 5 Next DELay 6 INStant 7 SET arm 8 PG control s 1 PGX 2 PGY 3 PGX PGY 9 SET UNSET toggle s section 1...

Page 20: ...To make handing over the system to the end user easier we recommend programming the system card provided with the control panel to the master code Example 5 1234 and then presenting the card to the ke...

Page 21: ...Notes...

Page 22: ......

Reviews: