Digital communicator JA-65X

  

– installation manual 

 

The JA-65X digital communicator is designed for JA-63 and  

JA-65 alarm control panels. If the 65X module is installed, the 

control panel can communicate with a Monitoring Station, send 

voice messages, SMS messages and dial a numeric Pager as 

well as  communicate with a remote PC. A  standard analog 

telephone line (type TNV 1-3) must be connected to the module for 

these functions. 

 

Installation of the digital telephone 

communicator

 

 

  Use 

the provided 

telephone cable to 

connect the telephone 

line to the IN jack on the 

X module (see diagram )  

  Connect a telephone, fax 

or other phone operated 

device to the OUT  jack, 

marked with a phone 

symbol   

  When the control panel 

is in normal stand-by mode, the phone line and any 

attached device will operate as normal 

 

Note: The communicator must be plugged directly to a 

telephone line socket. All other devices (telephone, facsimile 

machine, modem etc.) should be connected to the 

communicator output. 

 

2  Voice & SMS messages setting 

 

 

A control panel equipped with the X module can automatically 

send 2 voice and 5 short text messages (or dial a Pager). The 

most convenient programming of the dialer is via a connected 

PC using the Comlink software. Programming can also be 

performed manually from the keypad: 

  Enter the programming mode (

F 0 

Service Code

factory default = 6060), indicated by „P“  

  Any unfinished programming sequence can be 

terminated by pressing the 

N

 key. 

 

To exit the programming mode, press the N 

key („P“ 

will turn off). If any fault is indicated when you try to exit 

the programming mode, the control panel will inform 

you about the problem. 

  Telephone numbers and messages can also be set up 

in the User Mode when enabled (see installation 

manual of the control panel). 

 

2.1 

Telephone numbers for voice message  

 

sending 

sequence:

  7xxx....xxFy

 

Store telephone numbers for voice message by entering:

 

7 xx... xx F y

 

 

 

where

xx...xx

 = telephone number 

y

  

= memory number from 1 to 4 

A telephone number can have a maximum of 16 digits. A 

pause

 can be entered by 

F0 

 

Example:

 to store tel. number 0 123456 to memory no. 2 enter: 

7 0 F0 12345 F2 

 

Note:

 enter a pause (F0) after the last digit of a 

number which is 

calling a mobile phone

. This way the number will be called only 

once and the dialer will not check the line signals (some mobile 

phone systems do not generate standard telephone line signals).  

 

To delete a telephone number 

enter: 

7 F0 F

y

 

 

 

where

:  

memory number from 1 to 4 

note: 

entering 

7 F0 F0

 will erase all tel. numbers, including the 

SMS settings 

When activated, the dialer will

  disengage all other devices 

hooked up to the phone line. It will then, one by one, call all 

programmed numbers and play the user recorded message 

which corresponds to the event. If the dialer makes a successful 

connection to a programmed number, it will not call that number 

again. If the number is busy, the dialer will make 3 more 

attempts to call it. Empty tel. number memories are skipped. If 

all memories are empty, the dialer is completely disabled. If the 

dialer is also programmed to communicate with a monitoring 

station, the data will first be sent to the monitoring station. 

 

Factory default setting:

 all telephone numbers are deleted. 

 

 

2.2 

Automatic SMS sending 

sequence:

   7xxx....xxF5 

 

 

If Jablotron’s SMS server service is provided in your country 

(check with your distributor), the following setting allows the 

control panel to send alarm text messages (SMS) automatically 

to a desired mobile phone:  

 

7 xx…x F9 yy....y F7 00F9 F7zz..z F5

 

 

 

where:    

xx…x

  = telephone number of the SMS server (check with 

your distributor if this service is provided in your 

country)  

F9  

= separator (recognition of server’s reaction)  

yy…y

  = mobile phone number (where the SMS should be 

sent to) 

F7  

= event code separator  

00F9  

= automatic event code – control panel will insert 

there a digital code representing the alarm 

(depends on setting in section 2.4)  

F7  

= ID separator

  

zz..z

   = optional ID number which will be sent as a part of 

the SMS (ending). ID distinguishes which alarm 

system sent the SMS).  If ID is not required, do not 

enter it 

F5

  

= storing of the sequence to memory 5 (32 digits can 

be stored to memory 5 as a maximum - separators 

F9 and F7 takes only 1 digit each). 

How the SMS server works

: when activated, the control panel 

dials the SMS server. After the connection is established, it 

sends telephone number of the mobile phone, to which the SMS 

should be sent. Then the control panel specifies what happened 

by a digital code and in the end the ID number is transferred (if 

programmed). In this moment the SMS server makes 

corresponding text message and this message is sent to the 

GSM network. 

 

Example:

 If SMS server number is 483559876, SMS should be 

sent to number 606123456 and ID number of the installation is 

41 enter: 

7 483559876 F9 606123456 F7 00F9 F7 41 F5 

 

Deleting of automatic SMS sending 

– to erase SMS sending 

enter: 

7 F0 F5

   

Note:

 memory 5 can also be used to dial a Pager instead of SMS 

sending.  

To dial a Pager

 enter 

7 xx..x F9 zzz....z F5 

where

 

xx..x 

is number of the provider, zz…z is number of the pager and code 

of the message (check with a local Pager provider for details). 

Pause in the dialing can be entered with F0, 

 with F7 and 

 with 

F8. Pager dialing can be deleted with 7 F0 F5.   

 

Factory default setting:

 SMS sending (Pager dialing) is erased. 

tel. line

jack

LED diode

Microphone

Recording

button

JA-65X

IN
OUT

Summary of Contents for JA-65X

Page 1: ...will disengage all other devices hooked up to the phone line It will then one by one call all programmed numbers and play the user recorded message which corresponds to the event If the dialer makes...

Page 2: ...g method setting is also valid for Central monitoring station communications Factory default tone dialing 2 6 Telephone line checking sequence 9 9 x If this function is enabled the dialer will check r...

Page 3: ...s the connection is established All events are reported to the Monitoring Station in the same order as they happened Once communication has started it can not be interrupted unless the control panel i...

Page 4: ...tting sequence 04 If a dialer is triggered it attempts to make a connection alternating between the primary and the backup telephone number If it is not possible to make a connection after 8 attempts...

Page 5: ...rc 061 Zone alarm 4 rc 062 Zone alarm 5 rc 063 Zone alarm 6 rc 064 Zone alarm 7 rc 065 Zone alarm 8 rc 066 Zone alarm 9 rc 067 Zone alarm 10 rc 068 Zone alarm 11 rc 069 Zone alarm 12 rc 070 Zone alar...

Page 6: ...own fuse in control panel or other general failure 4 4 4 4 4 4 052 3 300 Control panel powering 4 148 3 300 No failure in the system 4 4 4 4 4 4 172 1 301 AC failure 4 173 3 301 AC switched on 4 054 1...

Page 7: ...e programmed in the control panel 8 digits optional bypassing of answering machine if this option was programmed in the control panel if the connection can not be established try to enter space after...