JA-60SR Wireless Smoke Detector

 

The JA-60SR detects smoke and wirelessly transmits this information 

to a receiving unit (control panel). It also has a built in siren to warn 
people in the immediate vicinity. For testing purposes the detector is 
equipped with a testing button. You can also test it remotely using any 
audio/video remote control. 

The detector makes regular auto testing and reports its condition to 

the system regularly for full supervision.   

 

 

JA-60SR 

1 / 3  

MFO51600

 

 

Specifications 

 

power 

3 V  - 2 x AA battery 1.5V  

battery life time 

about 1 year 

working freguency 

433,92 MHz 

working range 

max. 100 m  (open area) 

built in sensor 

ionic chamber 

radiation of sensor 

max. 4 kBq 

sensitivity 

y = 0,4 

÷

 0,7  (EN 54-7) 

built in siren 

95dB/1m 

RF immunity 

30V / 1m 

blowing air immunity 

max. 12m / s 

working environment 

indoor use ,  -10 to +60°C  

enclosure                                             IP 40          
complies with ISO 12239, EN 54-7  
can be operated according to ERC REC 70-03 

Hereby, Jablotron Ltd., declares that this JA-60SR

 

is in 

compliance with the essential requirements and other relevant 
provisions of Directive 1999/5/EC. 

 

Original of the conformity assessment can be found at the web page 
www.jablotron.cz, section Technical support.

 

 
Contents  of the set: 

detector, 2 plastic dowels, 2 screws, 2 AA 

batteries (inside the detector) 

 

Installation 

 

The detector should be installed on the ceiling, with the distance 

from walls 0.6 m as a minimum. The detector should not be installed in 
a place with poor air circulation. If you install the JA60SR in a long 
corridor (9 m and more), install at least two detectors , one at each 
end. A detector can cover an area of about 50 m

of free space (no 

partitions). The detector should not be installed close to any fan, 
heating/cooling vent, fluorescent lamp or air ionizer. The JA-60SR is 
not suitable for places with a high concentration of paint solvents or car 
exhausts (fumes). While deciding where to install the detector, keep in 
consideration that detector’s batteries have to be replaced from time to 
time (approximately once a year). 

Note:

 the detector can also be triggered by heavy cigarette smoke or 

fumes from cooking. 

 

• 

Open the cover of the detector (press it from both sides up to the 
lines on the housing

.

 – see the picture) 

• 

Attach the rear panel with the two provided screws to the desired 
location. Tighten the screws firmly, being sure that  the panel is not 
crooked. 

• 

Study the installation manual of the receiver unit (control panel) to 
learn how to enter the enrolling mode to enroll the detector.  

• 

Connect batteries in the detector (removing the plastic tape). The 
JA-60SR will transmit an enrollment signal and its buzzer will make 
a sound. From this moment the detector is ready to work. 

• 

Attach the detector’s front cover to the rear panel so that both tabs 
click. Check that the detector is fixed firmly. Warning – for safety 
reasons it is 

impossible to close the detector without the 

batteries! 

• 

Press and hold the testing button. The detector will make an alarm 
sound in few seconds. If the detector is 
tested after 15 minutes from the first 
testing, it won’t transmit alarm signal to the 
central unit (only local indication).

 

 

 

    IR

OFF           ON

Jumper IR ON / OFF 

-

 

the internal IR remote 

control testing can be disabled by this jumper. 
 

Normal operating mode of the detector 

 

performs a self testing ev

The detector, in normal operating mode, 

ery 60 

s

 detected

, the JA-60SR will make a “soft” warning sound at 

fi

 will go to stand by 

m

itch the control panel to the user or service 

m

econds (indicated by a short flash of the LED) and reports its condition to 

the system.  

If smoke is

rst and if the smoke concentration does not go down in 10 seconds, it will 

trigger an alarm (siren & signal to the alarm system).  

After the smoke concentration drops, the detector

ode again. You can stop the siren by pressing the test button or using a 

remote control (see bellow). 

To test the detector

 – sw

ode first. Then 

press and hold the testing button or use any IR 

remote control (TV, stereo etc.).

 Standing under the installed smoke 

sensor aim the remote control up to the detector holding any button 
pressed. The detector, at first, will generate soft beeps and within a few 
seconds it should start an alarm (siren sound and control panel 
triggering). Note, that different remote controls can differ in working 
distance. 

 

Battery testing and replacement 

 

The detector checks the condition of its batteries automatically. If it is 

n

nly high quality alkaline AA batteries for replacement. After 

in

e batteries are installed and the LED is 

fl

impossible to close the detector 

w

d to remove dust from the detector every time you 

ote:

 Dispose of batteries safely depending on the type of the batteries 

ecessary to replace batteries, the detector will inform the system about 

the need for new batteries and it will start to generate “soft” beeps every 
minute. 

Use o

stallation of new batteries the detector’s buzzer will make a sound to 

confirm that it is ready again.  

 If there is no sound after th

ashing, it means that the installed batteries have a low voltage and 

should be changed for new ones. 

Warning

 – for safety reasons it i

ithout batteries! 

 

Note: we recommen
replace its batteries. Use a dry cloth or blow on it gently. 
 

N

and local regulation. Although this product does not contain any harmful 
materials we suggest you to return the product to the dealer or directly to 
the producer after usage. 