Figure 4 – Correct and incorrect condensate drain connection
An y i m p r o p e r h a n d l i n g o f t h e w i r i n g t h a t c o u l d d a m a g e t h e h e a t r e c o v e r y o r c o o l i n g u n i t w i l l v o i d t h e
An y i m p r o p e r h a n d l i n g o f t h e w i r i n g t h a t c o u l d d a m a g e t h e h e a t r e c o v e r y o r c o o l i n g u n i t w i l l v o i d t h e
w a r r a n t y .
w a r r a n t y .
5
5 .. 5
5 .
. Com m ission in g
Com m ission in g
Prior to commissioning it is necessary to pay attention to completeness of the assembly, cleanliness of the equipment and throughput of air
ducts, correct directional insertion of filters, condensate drain functionality, correct electrical connection and readiness for the operation of all
technical components of the unit.
Any defects must be corrected before the commissioning!
Before commissioning it is necessary to set:
fan outputs for individual power levels 1 - 5,
fan speed coefficient for overpressure and anti-radon protection,
initialization of new filters.
The setting is made via the Bluetooth communicator in the MyCOMPANY application and is saved as a service (default) setting. The user can
return to default settings by resetting the unit.