34
8g.
8h.
The WHR has a cable and a Perilex plug for the electrical connection. The
connection must comply with NEN 50110 and locally applicable regula-
tions. The unit is not suitable for connection to the three-phase mains.
☞
Inspect the complete installation.
9. Starting up
9.1 Menu structure
The [MENU], [
▼
], [
▲
] and the [OK] keys can be used to select the following programs.
Set timer
Menu
P1
Menu not in use
Set time delay
Menu
P2
Set ventilation
Menu
P3
Set temperature
Menu
P4
Display status
Menu
P5
Display malfunction history
Menu
P6
Reset
Menu
P7
The menus P1 and P2 are freely accessible while the menus P3 to P7
require an "access code" (352).
Accessing the menus
Order
Key
Display
Description
1
Menu
P1
Timer
2
▲
P2
Time delays
3
▲
"1 - -"
Access code required (352)
4
▲
"3 - -"
First numeral of access code
5
OK
"- 2 -"
6
▲
"- 5 -"
Second numeral of access code
7
OK
"- - 3"
8
▼
"- - 2"
Third numeral of access code
9
OK
P3
Ventilation
10
▲
P4
Temperatures
11
▲
P5
Status
12
▲
P6
Malfunction history
13
▲
P7
Reset
Press [MENU] twice to exit the program. If no more keys are pressed, the program
will stop after five minutes and the display will return to the ventilation position.
The exception to this rule is menu P3. A period of thirty minutes applies here.
9.2 Example
Set the central position of the intake fan to 40%.
Order
Key
Display
Description
1
Menu
P1
Timer
2
▲
P2
Time delays
3
▲
"1 - -"
Access code required (352)
4
▲
"3 - -"
First numeral of access code
5
OK
"- 2 -"
6
▲
"- 5 -"
Second numeral of access code
7
OK
"- - 3."
8
▼
"- - 2"
Third numeral of access code
9
OK
P3
Ventilation
10
OK
P31
Ventilation procedure
11
▲
P35
Select P35
12
OK
50
Current setting
13
▼
40
Select 40
14
OK
P35
Saves value 40
15
MENU
P3
16
MENU
1
Ventilation position
9.3 Set parameters
P1 Timer: Menu not in use. P2 Time delays
No. Description
Min.
Max.
Default
Unit
21 Switch-on delay high position
0
15
5
Minutes
Low voltage input
22 Switch-off delay high position 0
120
30
Minutes
Low voltage input
P3 Ventilation
No. Description
Min.
Max.
Default
Unit
31 Exhaust fan low position
15
98
30
%
32 Exhaust fan medium position
16
99
50
%
33 Exhaust fan high position
17
100
90
%
34 Intake fan low position
15
98
30
%
35 Intake fan medium position
16
99
50
%
36 Intake fan high position
17
100
90
%
37 Current exhaust fan position
Current value
%
38 Current intake fan position
Current value
%
Unievent check valve
WHR
yellow/green
blue
brown
black
black+
yellow/green
blue
brown
black
black+
Valve
M
쵰
N
L
N
L1
L2
L3
N
L1
L2
L3
Low - Medium - High by means of SA 1-3 V
WHR
PERILEX:
SA 1-3 V
230V 50Hz
PE N
L
N
L1
L2
L3
2
4
1
WHR
SA 1-3 V
yellow/green
blue
brown
black
black+
230V 50Hz
PE N
L
2
4
1
English