Cathedral Vertical Installation
The wood appliance must be installed in accordance with the
applicable local laws or the CAN/CSA-B365, NFPA211 (USA)
norms. Follow the chimney manufacturer’s instructions to install
the chimney.
Always pass chimney between joists. If a joist need to be cut,
referring to the National Building code to know how to do it safely
to avoid structural integrity fail. Call a carpenter or a certified
Installer.
Always frame around chimney. Keep minimal clearances written
into your chimney manual.
Do not fill the gap between the fire stop and the chimney.
Nothing must be in contact with the chimney.
Always install a fire stop at each level, in a Floor, in a ceiling,
attic and in a Roof.
Always pass with a straight section into a level joist.
The chimney should be support by the cathedral roof. Build a
box around it to install ceiling support at is base.
Weight of the chimney never be allow to be support by the stove.
Offset Installation
The wood appliance must be installed in accordance with the
applicable local laws or the CAN/CSA-B365, NFPA211 (USA)
norms. Follow the chimney manufacturer’s instructions to install
the chimney.
Always pass chimney between joists. If a joist need to be cut,
referring to the National Building code to know how to do it safely
to avoid structural integrity fail. Call a carpenter or a certified
Installer.
Always frame around chimney. Keep minimal clearances written
into your chimney manual.
Do not fill the gap between the fire stop and the chimney. Nothing
must be in contact with the chimney.
Always install a fire stop at each level, in a Floor, in a ceiling, attic
and in a Roof.
A special fire stop need to be install into the attic. It keep isolation
and avoid the attic isolation to be in contact with the chimney.
Always pass with a straight section into a level joist.
Chimney weight have to be support by the lower level with a
Ceiling support.
Chimney weight have to never be onto the elbows. Install a support
band to support the upper straight section over the elbow.
Weight of the chimney never be allow to be support by the stove.
Some restriction have to be respect regarding the maximum angle
and length of the offset. See chimney manual for this restriction.
Or local building code.
Summary of Contents for PIONEER
Page 4: ...PR_I017 2023 01 23 EN 4 RATING PLATE...
Page 5: ...PR_I017 2023 01 23 EN 5 APPLIANCE DIMENSION...
Page 6: ...PR_I017 2023 01 23 EN 6...
Page 7: ...PR_I017 2023 01 23 EN 7...
Page 34: ...PR_I017 2023 01 23 EN 34 ANNEX 1 Exploded diagram of door Arc door...
Page 35: ...PR_I017 2023 01 23 EN 35 ANNEX 2 Fans electric wiring diagram...