Value of Zero indicates normal, healthy operation. Any other value indicates a subsystem or multiple
subsystem errors. See below.
Binary
Designation(s)
Decimal
Value
Error Meaning
Bit 0 = 1
1
GPS Communication (Comm) Error
Bit 2 = 1
4
Motor Comm Error
Bits 0 and 2 = 1
5
GPS Comm and Motor Comm Error
Bit 3 = 1
8
Analog Out of Range (OOR) Error
Bits 0 and 3 = 1
9
GPS Comm and Analog OOR Error
Bits 2 and 3 = 1
12
Motor Comm and Analog OOR Error
Bits 0, 2, and 3 = 1
13
GPS Comm, Motor Comm, and Analog OOR Error
For Customer Service, contact Ixom Watercare, Inc. Office and Service Center at 866-437-8076.
Table 4 - Visual Status Indicator (Register Address 9) - Priority Levels
Priority Level
LED
Behavior
Indication / Cause
Priority 1
3X Red
Motor Controller not communicating properly.
If the Charge Controller has the Auxiliary Output turned off, this
error is not displayed.
Priority 2
4X Red
Normal machine operation.
©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]
GridBee GF SCADA
System Status for GridBee GF SCADA
Register Address 7 (Base 10)
2077_10327_20220110
O&M_GF2500_10115_20220121 - 41