Operation chart
START/STOP key
Operation
•
Analog input operation (0 - 20 mA)
0 - 360 spm operation in proportion to 0 - 20 mA current input. Pump is fixed at 360 spm when came the
input signal exceeding 360 spm.
Straight line is automatically made by setting two points. So, the pump may not come to 0 spm even if 0
mA current comes.
(Condition)
1. A
1
, A
2
≤
20 mA
2. P
1
, P
2
≤
360 spm
3. A
1
≠
A
2
4. P
1
≠
P
2
0
A
1
SET point 1
Current
A
2
SET point 2
Current
20 mA
360 spm
SET point 2 spm
SET point 1 spm
4. Operation Function
•
Manual operation
Stroke rate can be set from 0 to 360 spm with keys
▲
and
▼
, and pump start and stop can be done with
keys START/STOP. Both setting can be done while the pump stops or operates.