High temperature difference heating system
water
Description: The temperature difference between T8 and T9 is greater than X, where X is calculated as a linear
function of the compressor frequency. 20Hz=10K and 90Hz=18K.
Check
Action
1.
B
Clean the dirt filter on the hot side.
B
Remove the filter basket and clean it.
Does the error message recur?
Æ
2
2.
B
Go to temperatures and check the
value on T8 and T9.
B
Use a digital thermometer and meas-
ure at the sensor.
Do the values correspond?
yes:
Æ
3
no:
B
Check the sensors and replace if necessary.
Does the error message recur?
Æ
4
3.
B
Check the flow in the heating system.
B
Check that the thermostat valves are open.
Does the error message recur?
Æ
4
4.
The heating system is not sufficiently
large for the relevant heat pump.
B
Expand the system volume (volume tank or several
radiators).
Tab. 6